Historical snapshot · Cybersecurity

CISA Advisories

Cybersecurity advisories and mitigation guidance for networks and critical infrastructure.

This page is an archived snapshot of the CISA Advisories feed collected on Feb 6, 2026, preserved by BioThreat Corporation. Publication dates belong to the original source; this snapshot is not a current advisory.
30 recordsOfficial source · JSON
· CISA Cybersecurity Advisory

TP-Link Systems Inc. VIGI Series IP Camera

View CSAF Summary Successful exploitation of this vulnerability could result in unauthorized users gaining administrative access to affected closed circuit television cameras. The following versions of TP-Link Systems Inc. VIGI Series IP Camera are affected: VIGI Cx45 Series Models C345, C445 <=3.1.0_Build_250820_Rel.57668n (CVE-2026-0629) VIGI Cx55 Series Models C355, C455 <=3.1.0_Build_250820_Rel.58873n…
Read full source summary
View CSAF Summary Successful exploitation of this vulnerability could result in unauthorized users gaining administrative access to affected closed circuit television cameras. The following versions of TP-Link Systems Inc. VIGI Series IP Camera are affected: VIGI Cx45 Series Models C345, C445 <=3.1.0_Build_250820_Rel.57668n (CVE-2026-0629) VIGI Cx55 Series Models C355, C455 <=3.1.0_Build_250820_Rel.58873n (CVE-2026-0629) VIGI Cx85 Series Models C385, C485 <=3.0.2_Build_250630_Rel.71279n (CVE-2026-0629) VIGI C340S Series <=3.1.0_Build_250625_Rel.65381n (CVE-2026-0629) VIGI C540S Series Models C540S, EasyCam C540S <=3.1.0_Build_250625_Rel.66601n (CVE-2026-0629) VIGI C540V Series <=2.1.0_Build_250702_Rel.54300n (CVE-2026-0629) VIGI C250 Series <=2.1.0_Build_250702_Rel.54301n (CVE-2026-0629) VIGI Cx50 Series Models C350, C450 <=2.1.0_Build_250702_Rel.54294n (CVE-2026-0629) VIGI Cx20I (1.0) Series Models C220I 1.0, C320I 1.0, C420I 1.0 <=2.1.0_Build_251014_Rel.58331n (CVE-2026-0629) VIGI Cx20I (1.20) Series Models C220I 1.20, C320I 1.20, C420I 1.20 <=2.1.0_Build_250701_Rel.44071n (CVE-2026-0629) VIGI Cx30I (1.0) Series Models C230I 1.0, C330I 1.0, C430I 1.0 <=2.1.0_Build_250701_Rel.45506n (CVE-2026-0629) VIGI Cx30I (1.20) Series Models C230I 1.20, C330I 1.20, C430I 1.20 <=2.1.0_Build_250701_Rel.44555n (CVE-2026-0629) VIGI Cx30 (1.0) Series Models C230 1.0, C330 1.0, C430 1.0 <=2.1.0_Build_250701_Rel.46796n (CVE-2026-0629) VIGI Cx30 (1.20) Series Models C230 1.20, C330 1.20, C430 1.20 <=2.1.0_Build_250701_Rel.46796n (CVE-2026-0629) VIGI Cx40I (1.0) Series Models C240I 1.0, C340I 1.0, C440I 1.0 <=2.1.0_Build_250701_Rel.46003n (CVE-2026-0629) VIGI Cx40I (1.20) Series Models C240I 1.20, C340I 1.20, C440I 1.20 <=2.1.0_Build_250701_Rel.45041n (CVE-2026-0629) VIGI C230I Mini Series <=2.1.0_Build_250701_Rel.47570n (CVE-2026-0629) VIGI C240 1.0 Series <=2.1.0_Build_250701_Rel.48425n (CVE-2026-0629) VIGI C340 2.0 Series <=2.1.0_Build_250701_Rel.49304n (CVE-2026-0629) VIGI C440 2.0 Series <=2.1.0_Build_250701_Rel.49778n (CVE-2026-0629) VIGI C540 2.0 Series <=2.1.0_Build_250701_Rel.50397n (CVE-2026-0629) VIGI C540‑4G Series <=2.2.0_Build_250826_Rel.56808n (CVE-2026-0629) VIGI Cx40‑W Series Models C340‑W 2.0/2.20, C440‑W 2.0, C540‑W 2.0 <=2.1.1_Build_250717 (CVE-2026-0629) VIGI Cx20 Series Models C320, C420 <=2.1.0_Build_250701_Rel.39597n (CVE-2026-0629) VIGI InSight Sx45 Series Models S245, S345, S445 <=3.1.0_Build_250820_Rel.57668n (CVE-2026-0629) VIGI InSight Sx55 Series Models S355, S455 <=3.1.0_Build_250820_Rel.58873n (CVE-2026-0629) VIGI InSight Sx85 Series Models S285, S385 <=3.0.2_Build_250630_Rel.71279n (CVE-2026-0629) VIGI InSight Sx45ZI Series Models S245ZI, S345ZI, S445ZI <=1.2.0_Build_250820_Rel.60930n (CVE-2026-0629) VIGI InSight Sx85PI Series Models S385PI, S485PI <=1.2.0_Build_250827_Rel.66817n (CVE-2026-0629) VIGI InSight S655I Series <=1.1.1_Build_250625_Rel.64224n (CVE-2026-0629) VIGI InSight S345‑4G Series <=2.1.0_Build_250725_Rel.36867n (CVE-2026-0629) VIGI InSight Sx25 Series Models S225, S325, S425 <=1.1.0_Build_250630_Rel.39597n (CVE-2026-0629) CVSS Vendor Equipment Vulnerabilities v3 8.8 TP-Link Systems Inc. TP-Link Systems Inc. VIGI Series IP Camera Improper Authentication Background Critical Infrastructure Sectors: Commercial Facilities Countries/Areas Deployed: Worldwide Company Headquarters Location: China Vulnerabilities Expand All + CVE-2026-0629 An authentication bypass in the password recovery feature of the local web interface across multiple VIGI camera models allows an attacker on the LAN to reset the admin password without verification by manipulating client-side state. Attackers can gain full administrative access to the device, compromising configuration and network security. View CVE Details Affected Products TP-Link Systems Inc. VIGI Series IP Camera Vendor: TP-Link Systems Inc. Product Version: TP-Link Systems Inc. VIGI Cx45 Series Models C345, C445: <=3.1.0_Build_250820_Rel.57668n, TP-Link Systems Inc. VIGI Cx55 Series Models C355, C455: <=3.1.0_Build_250820_Rel.58873n, TP-Link Systems Inc. VIGI Cx85 Series Models C385, C485: <=3.0.2_Build_250630_Rel.71279n, TP-Link Systems Inc. VIGI C340S Series: <=3.1.0_Build_250625_Rel.65381n, TP-Link Systems Inc. VIGI C540S Series Models C540S, EasyCam C540S: <=3.1.0_Build_250625_Rel.66601n, TP-Link Systems Inc. VIGI C540V Series: <=2.1.0_Build_250702_Rel.54300n, TP-Link Systems Inc. VIGI C250 Series: <=2.1.0_Build_250702_Rel.54301n, TP-Link Systems Inc. VIGI Cx50 Series Models C350, C450: <=2.1.0_Build_250702_Rel.54294n, TP-Link Systems Inc. VIGI Cx20I (1.0) Series Models C220I 1.0, C320I 1.0, C420I 1.0: <=2.1.0_Build_251014_Rel.58331n, TP-Link Systems Inc. VIGI Cx20I (1.20) Series Models C220I 1.20, C320I 1.20, C420I 1.20: <=2.1.0_Build_250701_Rel.44071n, TP-Link Systems Inc. VIGI Cx30I (1.0) Series Models C230I 1.0, C330I 1.0, C430I 1.0: <=2.1.0_Build_250701_Rel.45506n, TP-Link Systems Inc. VIGI Cx30I (1.20) Series Models C230I 1.20, C330I 1.20, C430I 1.20: <=2.1.0_Build_250701_Rel.44555n, TP-Link Systems Inc. VIGI Cx30 (1.0) Series Models C230 1.0, C330 1.0, C430 1.0: <=2.1.0_Build_250701_Rel.46796n, TP-Link Systems Inc. VIGI Cx30 (1.20) Series Models C230 1.20, C330 1.20, C430 1.20: <=2.1.0_Build_250701_Rel.46796n, TP-Link Systems Inc. VIGI Cx40I (1.0) Series Models C240I 1.0, C340I 1.0, C440I 1.0: <=2.1.0_Build_250701_Rel.46003n, TP-Link Systems Inc. VIGI Cx40I (1.20) Series Models C240I 1.20, C340I 1.20, C440I 1.20: <=2.1.0_Build_250701_Rel.45041n, TP-Link Systems Inc. VIGI C230I Mini Series: <=2.1.0_Build_250701_Rel.47570n, TP-Link Systems Inc. VIGI C240 1.0 Series: <=2.1.0_Build_250701_Rel.48425n, TP-Link Systems Inc. VIGI C340 2.0 Series: <=2.1.0_Build_250701_Rel.49304n, TP-Link Systems Inc. VIGI C440 2.0 Series: <=2.1.0_Build_250701_Rel.49778n, TP-Link Systems Inc. VIGI C540 2.0 Series: <=2.1.0_Build_250701_Rel.50397n, TP-Link Systems Inc. VIGI C540‑4G Series: <=2.2.0_Build_250826_Rel.56808n, TP-Link Systems Inc. VIGI Cx40‑W Series Models C340‑W 2.0/2.20, C440‑W 2.0, C540‑W 2.0: <=2.1.1_Build_250717, TP-Link Systems Inc. VIGI Cx20 Series Models C320, C420: <=2.1.0_Build_250701_Rel.39597n, TP-Link Systems Inc. VIGI InSight Sx45 Series Models S245, S345, S445: <=3.1.0_Build_250820_Rel.57668n, TP-Link Systems Inc. VIGI InSight Sx55 Series Models S355, S455: <=3.1.0_Build_250820_Rel.58873n, TP-Link Systems Inc. VIGI InSight Sx85 Series Models S285, S385: <=3.0.2_Build_250630_Rel.71279n, TP-Link Systems Inc. VIGI InSight Sx45ZI Series Models S245ZI, S345ZI, S445ZI: <=1.2.0_Build_250820_Rel.60930n, TP-Link Systems Inc. VIGI InSight Sx85PI Series Models S385PI, S485PI: <=1.2.0_Build_250827_Rel.66817n, TP-Link Systems Inc. VIGI InSight S655I Series: <=1.1.1_Build_250625_Rel.64224n, TP-Link Systems Inc. VIGI InSight S345‑4G Series: <=2.1.0_Build_250725_Rel.36867n, TP-Link Systems Inc. VIGI InSight Sx25 Series Models S225, S325, S425: <=1.1.0_Build_250630_Rel.39597n Product Status: known_affected Remediations Mitigation TP-Link Communications strongly recommends that users with affected devices take the following actions: Mitigation Download and update to the latest firmware version to fix the vulnerability from the following links. Mitigation United States users should visit the TP-Link US Download Center here: https://www.vigi.com/us/support/download/. Mitigation Global English users should visit the TP-Link EN Download Center:https://www.vigi.com/es/support/download/. Mitigation India users should visit the TP-Link India Download Center:https://www.vigi.com/in/support/download/. Mitigation Please visit https://www.tp-link.com/us/support/faq/4906/ for the TP-Link advisory. Relevant CWE: CWE-287 Improper Authentication Metrics CVSS Version Base Score Base Severity Vector String 3.1 8.8 HIGH CVSS:3.1/AV:A/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H Acknowledgments Arko Dhar of Redinent Innovations reported this vulnerability to CISA Legal Notice and Terms of Use This product is provided subject to this Notification (https://www.cisa.gov/notification) and this Privacy & Use policy (https://www.cisa.gov/privacy-policy). Recommended Practices CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability, such as: Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the Internet. Locate control system networks and remote devices behind firewalls and isolating them from business networks. When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as the connected devices. CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures. CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies. CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets. Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies. Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents. No known public exploitation specifically targeting this vulnerability has been reported to CISA at this time. This vulnerability is not exploitable remotely. Revision History Initial Release Date: 2026-02-05 Date Revision Summary 2026-02-05 1 Initial Publication Legal Notice and Terms of Use
· CISA Cybersecurity Advisory

Mitsubishi Electric MELSEC iQ-R Series

View CSAF Summary Successful exploitation of this vulnerability may allow an attacker to read device data or part of a control program from the affected product, write device data in the affected product, or cause a denial-of-service condition on the affected product. The following versions of Mitsubishi Electric MELSEC iQ-R Series are affected: MELSEC iQ-R Series R08/16/32/120PCPU firmware <=48 (CVE-2025-15080)…
Read full source summary
View CSAF Summary Successful exploitation of this vulnerability may allow an attacker to read device data or part of a control program from the affected product, write device data in the affected product, or cause a denial-of-service condition on the affected product. The following versions of Mitsubishi Electric MELSEC iQ-R Series are affected: MELSEC iQ-R Series R08/16/32/120PCPU firmware <=48 (CVE-2025-15080) CVSS Vendor Equipment Vulnerabilities v3 9.4 Mitsubishi Electric Mitsubishi Electric MELSEC iQ-R Series Improper Validation of Specified Quantity in Input Background Critical Infrastructure Sectors: Critical Manufacturing Countries/Areas Deployed: Worldwide Company Headquarters Location: Japan Vulnerabilities Expand All + CVE-2025-15080 An information disclosure, information tampering, and denial-of-service vulnerability exists in Mitsubishi Electric proprietary protocol communication and SLMP communication used in FA products. An attacker may be able to read device data or part of a control program from the affected product, write device data in the affected product, or cause a denial-of-service condition on the affected product by sending a specially crafted packet containing a specific command to the affected product. View CVE Details Affected Products Mitsubishi Electric MELSEC iQ-R Series Vendor: Mitsubishi Electric Product Version: Mitsubishi Electric MELSEC iQ-R Series R08/16/32/120PCPU firmware: <=48 Product Status: known_affected Remediations Mitigation Mitsubishi Electric recommends users of the affected products follow the procedure below to update firmware version 49 or later. Download the update file for the fixed version, the engineering software for firmware upgrade, and the manual from the download website at https://www.mitsubishielectric.com/fa/download/index.html . For details on updating the firmware, see MELSEC iQ-R Module Configuration Manual "Appendix 2 Firmware Update Function". Mitigation Mitsubishi Electric recommends the following mitigations to reduce the risk of exploiting this vulnerability: Use a firewall or virtual private network (VPN) block access from untrusted networks and hosts using a firewall. Use the product within a LAN and block access from untrusted networks and hosts through a firewall. Use firewalls, IP filters, and similar controls to minimize connections to the product and prevent access from untrusted networks and hosts. For details on the IP filter function, refer to "IP Filter" in section 1.13, Security, of the MELSEC iQ-R Ethernet User's Manual (Application). Restrict physical access to the affected product and its connected LAN. Mitigation For specific update instructions and additional details see the Mitsubishi Electric advisory at https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2025-020_en.pdf . Mitigation For further information, contact your local Mitsubishi Electric representative at https://www.mitsubishielectric.com/fa/service-support/index.html . Relevant CWE: CWE-1284 Improper Validation of Specified Quantity in Input Metrics CVSS Version Base Score Base Severity Vector String 3.1 9.4 CRITICAL CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:H/A:H Acknowledgments Mitsubishi Electric reported this vulnerability to CISA Legal Notice and Terms of Use This product is provided subject to this Notification (https://www.cisa.gov/notification) and this Privacy & Use policy (https://www.cisa.gov/privacy-policy). Recommended Practices CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability. CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures. CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies. CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets. Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies. Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents. No known public exploitation specifically targeting this vulnerability has been reported to CISA at this time. Revision History Initial Release Date: 2026-02-05 Date Revision Summary 2026-02-05 1 Initial Republication of Mitsubishi Electric 2025-020 Legal Notice and Terms of Use
· CISA Cybersecurity Advisory

Hitachi Energy FOX61x

View CSAF Summary Hitachi Energy is aware of a vulnerability that affects FOX61x product versions listed in this document. Successful exploitation of this vulnerability can lead to forgery attacks potentially causing impact on confidentiality, integrity and availability for the product. Please refer to the Recommended Immediate Actions for information about the mitigation/remediation. Note: This is applicable only…
Read full source summary
View CSAF Summary Hitachi Energy is aware of a vulnerability that affects FOX61x product versions listed in this document. Successful exploitation of this vulnerability can lead to forgery attacks potentially causing impact on confidentiality, integrity and availability for the product. Please refer to the Recommended Immediate Actions for information about the mitigation/remediation. Note: This is applicable only if FOX61x devices are configured to use remote RADIUS authentication. The following versions of Hitachi Energy FOX61x are affected: FOX61x R18, vers:FOX61x/<=R17A (CVE-2024-3596, CVE-2024-3596) CVSS Vendor Equipment Vulnerabilities v3 9 Hitachi Energy Hitachi Energy FOX61x Improper Enforcement of Message Integrity During Transmission in a Communication Channel Background Critical Infrastructure Sectors: Critical Manufacturing Countries/Areas Deployed: Worldwide Company Headquarters Location: Switzerland Vulnerabilities Expand All + CVE-2024-3596 The RADIUS protocol under RFC 2865 is vulnerable to forgery attacks that allow a local attacker to modify any valid response (Access-Accept, Access-Reject, or Access-Challenge) into another response by exploiting a chosen-prefix collision attack on the MD5 Response Authenticator signature.. View CVE Details Affected Products Hitachi Energy FOX61x Vendor: Hitachi Energy Product Version: FOX61x version R18, FOX61x version R17A and earlier Product Status: known_affected Remediations Mitigation Enable the RADIUS Message-Authenticator option in both the FOX61x and RADIUS Server configurations. Refer to the Technical User Documentation at https://publisher.hitachienergy.com/preview?DocumentID=1KHW029042&LanguageCode=en&DocumentPartId=R18&Action=launch. Vendor fix Update to FOX61x R18, then enable the RADIUS Message-Authenticator option in both the FOX61x and RADIUS Server configurations. Refer to the Technical User Documentation at https://publisher.hitachienergy.com/preview?DocumentID=1KHW029042&LanguageCode=en&DocumentPartId=R18&Action=launch. Mitigation If the upgrade is not possible, apply general mitigation factors with segmentation of FOX management traffic to minimize the risk. Mitigation For more information, see the associated Hitachi Energy cybersecurity advisory 8DBD000225 Radius MD5 Vulnerability in Hitachi Energy FOX61x product at https://publisher.hitachienergy.com/preview?DocumentID=8DBD000225&LanguageCode=en or https://publisher.hitachienergy.com/preview?DocumentID=8DBD000225-CSAF&LanguageCode=en&DocumentPartId=&Action=Launch . Mitigation Hitachi Energy recommends implementing security practices and firewall configurations to help protect process control networks from external attacks. Such practices include ensuring that process control systems are physically protected from unauthorized access, have no direct Internet connections, and are separated from other networks by a firewall system that minimizes exposed ports, and any additional ports should be evaluated on a case-by-case basis. Process control systems should not be used for web browsing, instant messaging, or email. Portable computers and removable storage media should be thoroughly scanned for malware before being connected to a control system. Organizations should enforce proper password policies and procedures. Relevant CWE: CWE-924 Improper Enforcement of Message Integrity During Transmission in a Communication Channel Metrics CVSS Version Base Score Base Severity Vector String 3.1 9 CRITICAL CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:C/C:H/I:H/A:H Acknowledgments Hitachi Energy reported this vulnerability to CISA. Notice The information in this document is subject to change without notice and should not be construed as a commitment by Hitachi Energy. Hitachi Energy provides no warranty, express or implied, including warranties of merchantability and fitness for a particular purpose, for the information contained in this document, and assumes no responsibility for any errors that may appear in this document. In no event shall Hitachi Energy or any of its suppliers be liable for direct, indirect, special, incidental or consequential damages of any nature or kind arising from the use of this document, or from the use of any hardware or software described in this document, even if Hitachi Energy or its suppliers have been advised of the possibility of such damages. This document and parts hereof must not be reproduced or copied without written permission from Hitachi Energy and the contents hereof must not be imparted to a third party nor used for any unauthorized purpose. All rights to registrations and trademarks reside with their respective owners. Support For additional information and support please contact your product provider or Hitachi Energy service organization. For contact information, see https://www.hitachienergy.com/contact-us/ for Hitachi Energy contact-centers. General Mitigation Factors Recommended security practices and firewall configurations can help protect a process control network from attacks that originate from outside the network. Such practices include that process control systems are physically protected from direct access by unauthorized personnel, have no direct connections to the Internet, and are separated from other networks by means of a firewall system that has a minimal number of ports exposed, and others that have to be evaluated case by case. Process control systems should not be used for Internet surfing, instant messaging, or receiving e-mails. Portable computers and removable storage media should be carefully scanned for viruses before they are connected to a control system. Proper password policies and processes should be followed. Legal Notice and Terms of Use This product is provided subject to this Notification (https://www.cisa.gov/notification) and this Privacy & Use policy (https://www.cisa.gov/privacy-policy). Recommended Practices CISA recommends users take defensive measures to minimize the exploitation risk of these vulnerabilities. Minimize network exposure for all control system devices and/or systems, and ensure they are not accessible from the internet. Locate control system networks and remote devices behind firewalls and isolate them from business networks. When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most recent version available. Also recognize VPN is only as secure as its connected devices. CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures. CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies. CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets. Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies. Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents. Advisory Conversion Disclaimer This ICSA is a verbatim republication of Hitachi Energy PSIRT 8DBD000225 from a direct conversion of the vendor's Common Security Advisory Framework (CSAF) advisory. This is republished to CISA's website as a means of increasing visibility and is provided "as-is" for informational purposes only. CISA is not responsible for the editorial or technical accuracy of republished advisories and provides no warranties of any kind regarding any information contained within this advisory. Further, CISA does not endorse any commercial product or service. Please contact Hitachi Energy PSIRT directly for any questions regarding this advisory. Revision History Initial Release Date: 2026-01-27 Date Revision Summary 2026-01-27 1 Initial public release 2026-02-05 2 Initial CISA Republication of Hitachi Energy PSIRT 8DBD000225 advisory Legal Notice and Terms of Use
· CISA Cybersecurity Advisory

o6 Automation GmbH Open62541

View CSAF Summary Successful exploitation of this vulnerability could allow an attacker to cause a denial-of-service condition and memory corruption. The following versions of o6 Automation GmbH Open62541 are affected: Open62541 >=1.5-rc1|<1.5-rc2 (CVE-2026-1301) CVSS Vendor Equipment Vulnerabilities v3 5.7 o6 Automation GmbH o6 Automation GmbH Open62541 Out-of-bounds Write Background Critical Infrastructure…
Read full source summary
View CSAF Summary Successful exploitation of this vulnerability could allow an attacker to cause a denial-of-service condition and memory corruption. The following versions of o6 Automation GmbH Open62541 are affected: Open62541 >=1.5-rc1|<1.5-rc2 (CVE-2026-1301) CVSS Vendor Equipment Vulnerabilities v3 5.7 o6 Automation GmbH o6 Automation GmbH Open62541 Out-of-bounds Write Background Critical Infrastructure Sectors: Critical Manufacturing Countries/Areas Deployed: Worldwide Company Headquarters Location: Germany Vulnerabilities Expand All + CVE-2026-1301 In builds with PubSub and JSON enabled, a crafted JSON message can cause the decoder to write beyond a heap-allocated array before authentication, reliably crashing the process and corrupting memory. View CVE Details Affected Products o6 Automation GmbH Open62541 Vendor: o6 Automation GmbH Product Version: o6 Automation GmbH Open62541: >=1.5-rc1|<1.5-rc2 Product Status: known_affected Remediations Mitigation o6 Automation GmbH recommends users upgrade to the stable release of v1.5.0. Relevant CWE: CWE-787 Out-of-bounds Write Metrics CVSS Version Base Score Base Severity Vector String 3.1 5.7 MEDIUM CVSS:3.1/AV:N/AC:L/PR:L/UI:R/S:U/C:N/I:N/A:H Acknowledgments Andrew Fasano of NIST CAISI reported this vulnerability to CISA Legal Notice and Terms of Use This product is provided subject to this Notification (https://www.cisa.gov/notification) and this Privacy & Use policy (https://www.cisa.gov/privacy-policy). Recommended Practices CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability, such as: Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the Internet. Locate control system networks and remote devices behind firewalls and isolating them from business networks. When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as the connected devices. CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures. CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies. CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets. Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies. Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents. CISA also recommends users take the following measures to protect themselves from social engineering attacks: Do not click web links or open attachments in unsolicited email messages. Refer to Recognizing and Avoiding Email Scams for more information on avoiding email scams. Refer to Avoiding Social Engineering and Phishing Attacks for more information on social engineering attacks. No known public exploitation specifically targeting this vulnerability has been reported to CISA at this time. Revision History Initial Release Date: 2026-02-05 Date Revision Summary 2026-02-05 1 Initial Publication Legal Notice and Terms of Use
· CISA Cybersecurity Advisory

CISA Adds Two Known Exploited Vulnerabilities to Catalog

CISA has added two new vulnerabilities to its Known Exploited Vulnerabilities (KEV) Catalog, based on evidence of active exploitation. CVE-2025-11953 React Native Community CLI OS Command Injection Vulnerability CVE-2026-24423 SmarterTools SmarterMail Missing Authentication for Critical Function Vulnerability These types of vulnerabilities are frequent attack vectors for malicious cyber actors and pose significant…
Read full source summary
CISA has added two new vulnerabilities to its Known Exploited Vulnerabilities (KEV) Catalog, based on evidence of active exploitation. CVE-2025-11953 React Native Community CLI OS Command Injection Vulnerability CVE-2026-24423 SmarterTools SmarterMail Missing Authentication for Critical Function Vulnerability These types of vulnerabilities are frequent attack vectors for malicious cyber actors and pose significant risks to the federal enterprise. Binding Operational Directive (BOD) 22-01: Reducing the Significant Risk of Known Exploited Vulnerabilities established the KEV Catalog as a living list of known Common Vulnerabilities and Exposures (CVEs) that carry significant risk to the federal enterprise. BOD 22-01 requires Federal Civilian Executive Branch (FCEB) agencies to remediate identified vulnerabilities by the due date to protect FCEB networks against active threats. See the BOD 22-01 Fact Sheet for more information. Although BOD 22-01 only applies to FCEB agencies, CISA strongly urges all organizations to reduce their exposure to cyberattacks by prioritizing timely remediation of KEV Catalog vulnerabilities as part of their vulnerability management practice. CISA will continue to add vulnerabilities to the catalog that meet the specified criteria.
· CISA Cybersecurity Advisory

Hitachi Energy XMC20

View CSAF Summary Hitachi Energy is aware of a vulnerability that affects XMC20 product versions listed in this document. Successful exploitation of this vulnerability can lead to forgery attacks potentially causing impact on confidentiality, integrity and availability for the product. Please refer to the Recommended Immediate Actions for information about the mitigation/remediation. Note: This is applicable only if…
Read full source summary
View CSAF Summary Hitachi Energy is aware of a vulnerability that affects XMC20 product versions listed in this document. Successful exploitation of this vulnerability can lead to forgery attacks potentially causing impact on confidentiality, integrity and availability for the product. Please refer to the Recommended Immediate Actions for information about the mitigation/remediation. Note: This is applicable only if XMC20 devices are configured to use remote RADIUS authentication. The following versions of Hitachi Energy XMC20 are affected: XMC20 R18, vers:XMC20/<=R17A (CVE-2024-3596, CVE-2024-3596) CVSS Vendor Equipment Vulnerabilities v3 9 Hitachi Energy Hitachi Energy XMC20 Improper Enforcement of Message Integrity During Transmission in a Communication Channel Background Critical Infrastructure Sectors: Critical Manufacturing Countries/Areas Deployed: Worldwide Company Headquarters Location: Switzerland Vulnerabilities Expand All + CVE-2024-3596 The RADIUS protocol under RFC 2865 is susceptible to forgery attacks by a local attacker. An attacker can modify any valid response (Access-Accept, Access-Reject, or Access-Challenge) into another response using a chosen-prefix collision attack targeting the MD5 Response Authenticator signature. View CVE Details Affected Products Hitachi Energy XMC20 Vendor: Hitachi Energy Product Version: XMC20 version R18, XMC20 version R17A and earlier Product Status: known_affected Remediations Mitigation Enable the RADIUS Message-Authenticator option in both the XMC20 and RADIUS server configurations. Refer to the Technical User Documentation at https://publisher.hitachienergy.com/preview?DocumentID=1KHW029001&LanguageCode=en&DocumentPartId=R18&Action=launch. Vendor fix Update to XMC20 R18 and then enable the RADIUS Message-Authenticator option in both the XMC20 and RADIUS server configurations. Refer to the Technical User Documentation at https://publisher.hitachienergy.com/preview?DocumentID=1KHW029001&LanguageCode=en&DocumentPartId=R18&Action=launch. Mitigation If the upgrade is not possible, apply general mitigation factors with segmentation of FOX management traffic to minimize the risk. Mitigation For more information, see the associated Hitachi Energy cybersecurity advisory 8DBD000233 RADIUS MD5 Vulnerability in Hitachi Energy XMC20 product available in PDF format here https://publisher.hitachienergy.com/preview?DocumentID=8DBD000233&LanguageCode=en&DocumentPartId=&Action=launch or JSON format here https://publisher.hitachienergy.com/preview?DocumentID=8DBD000233-CSAF&LanguageCode=en&DocumentPartId=&Action=Launch. Mitigation Hitachi Energy recommends implementing security practices and firewall configurations to help protect process control networks from external attacks. Such practices include ensuring that process control systems are physically protected from unauthorized access, have no direct Internet connections, and are separated from other networks by a firewall system that minimizes exposed ports, and any additional ports should be evaluated on a case-by-case basis. Process control systems should not be used for web browsing, instant messaging, or email. Portable computers and removable storage media should be thoroughly scanned for malware before being connected to a control system. Organizations should enforce proper password policies and procedures. Relevant CWE: CWE-924 Improper Enforcement of Message Integrity During Transmission in a Communication Channel Metrics CVSS Version Base Score Base Severity Vector String 3.1 9 CRITICAL CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:C/C:H/I:H/A:H Acknowledgments Hitachi Energy reported this vulnerability to CISA. Notice The information in this document is subject to change without notice and should not be construed as a commitment by Hitachi Energy. Hitachi Energy provides no warranty, express or implied, including warranties of merchantability and fitness for a particular purpose, for the information contained in this document, and assumes no responsibility for any errors that may appear in this document. In no event shall Hitachi Energy or any of its suppliers be liable for direct, indirect, special, incidental or consequential damages of any nature or kind arising from the use of this document, or from the use of any hardware or software described in this document, even if Hitachi Energy or its suppliers have been advised of the possibility of such damages. This document and parts hereof must not be reproduced or copied without written permission from Hitachi Energy and the contents hereof must not be imparted to a third party nor used for any unauthorized purpose. All rights to registrations and trademarks reside with their respective owners. Support For additional information and support please contact your product provider or Hitachi Energy service organization. For contact information, see https://www.hitachienergy.com/contact-us/ for Hitachi Energy contact-centers. General Mitigation Factors Recommended security practices and firewall configurations can help protect a process control network from attacks that originate from outside the network. Such practices include that process control systems are physically protected from direct access by unauthorized personnel, have no direct connections to the Internet, and are separated from other networks by means of a firewall system that has a minimal number of ports exposed, and others that have to be evaluated case by case. Process control systems should not be used for Internet surfing, instant messaging, or receiving e-mails. Portable computers and removable storage media should be carefully scanned for viruses before they are connected to a control system. Proper password policies and processes should be followed. Legal Notice and Terms of Use This product is provided subject to this Notification (https://www.cisa.gov/notification) and this Privacy & Use policy (https://www.cisa.gov/privacy-policy). Recommended Practices CISA recommends users take defensive measures to minimize the exploitation risk of these vulnerabilities. Minimize network exposure for all control system devices and/or systems, and ensure they are not accessible from the internet. Locate control system networks and remote devices behind firewalls and isolate them from business networks. When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most recent version available. Also recognize VPN is only as secure as its connected devices. CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures. CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies. CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets. Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies. Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents. Advisory Conversion Disclaimer This ICSA is a verbatim republication of Hitachi Energy PSIRT 8DBD000233 from a direct conversion of the vendor's Common Security Advisory Framework (CSAF) advisory. This is republished to CISA's website as a means of increasing visibility and is provided "as-is" for informational purposes only. CISA is not responsible for the editorial or technical accuracy of republished advisories and provides no warranties of any kind regarding any information contained within this advisory. Further, CISA does not endorse any commercial product or service. Please contact Hitachi Energy PSIRT directly for any questions regarding this advisory. Revision History Initial Release Date: 2026-01-27 Date Revision Summary 2026-01-27 1 Initial public release 2026-02-05 2 Initial CISA Republication of Hitachi Energy PSIRT 8DBD000233 advisory Legal Notice and Terms of Use
· CISA Cybersecurity Advisory

Ilevia EVE X1 Server

View CSAF Summary Successful exploitation of these vulnerabilities could allow an attacker to execute arbitrary shell commands and the disclosure of sensitive system information. The following versions of Ilevia EVE X1 Server are affected: EVE X1 <=4.7.18.0 (CVE-2025-34185, CVE-2025-34184, CVE-2025-34183, CVE-2025-34186, CVE-2025-34187, CVE-2025-34517, CVE-2025-34518, CVE-2025-34512, CVE-2025-34513) CVSS Vendor…
Read full source summary
View CSAF Summary Successful exploitation of these vulnerabilities could allow an attacker to execute arbitrary shell commands and the disclosure of sensitive system information. The following versions of Ilevia EVE X1 Server are affected: EVE X1 <=4.7.18.0 (CVE-2025-34185, CVE-2025-34184, CVE-2025-34183, CVE-2025-34186, CVE-2025-34187, CVE-2025-34517, CVE-2025-34518, CVE-2025-34512, CVE-2025-34513) CVSS Vendor Equipment Vulnerabilities v3 9.8 Ilevia Ilevia EVE X1 Server Improper Limitation of a Pathname to a Restricted Directory ('Path Traversal'), Improper Neutralization of Special Elements used in an OS Command ('OS Command Injection'), Insertion of Sensitive Information into Log File, Improper Neutralization of Input During Web Page Generation ('Cross-site Scripting') Background Critical Infrastructure Sectors: Critical Manufacturing Countries/Areas Deployed: Worldwide Company Headquarters Location: Italy Vulnerabilities Expand All + CVE-2025-34185 Ilevia EVE X1 Server contains a pre-authentication file disclosure vulnerability via the 'db_log' POST parameter. Remote attackers can retrieve arbitrary files from the server, exposing sensitive system information and credentials. View CVE Details Affected Products Ilevia EVE X1 Server Vendor: Ilevia Product Version: Ilevia EVE X1: <=4.7.18.0 Product Status: known_affected Remediations Mitigation Ilevia recommends that users perform the following mitigation steps: Update to the newest version of Ilevia Manager at https://www.ilevia.com/downloads/. Verify port 8080 is closed on all devices and routers and enable access only through the secure option provided in the updated Ilevia Manager. Change all default passwords on active systems to strong, unique credentials to prevent unauthorized access and automated attacks. Review firewall configurations to confirm that internal protections are functioning as intended and external exposure is minimized. Monitor for unauthorized access attempts and apply network segmentation where possible to reduce attack surfaces. Relevant CWE: CWE-22 Improper Limitation of a Pathname to a Restricted Directory ('Path Traversal') Metrics CVSS Version Base Score Base Severity Vector String 3.1 7.5 HIGH CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N CVE-2025-34184 Ilevia EVE X1 Server contains an unauthenticated OS command injection vulnerability in the /ajax/php/login.php script. Remote attackers can execute arbitrary system commands by injecting payloads into the 'passwd' HTTP POST parameter, leading to full system compromise or denial of service. View CVE Details Affected Products Ilevia EVE X1 Server Vendor: Ilevia Product Version: Ilevia EVE X1: <=4.7.18.0 Product Status: known_affected Remediations Mitigation Ilevia recommends that users perform the following mitigation steps: Update to the newest version of Ilevia Manager at https://www.ilevia.com/downloads/. Verify port 8080 is closed on all devices and routers and enable access only through the secure option provided in the updated Ilevia Manager. Change all default passwords on active systems to strong, unique credentials to prevent unauthorized access and automated attacks. Review firewall configurations to confirm that internal protections are functioning as intended and external exposure is minimized. Monitor for unauthorized access attempts and apply network segmentation where possible to reduce attack surfaces. Relevant CWE: CWE-78 Improper Neutralization of Special Elements used in an OS Command ('OS Command Injection') Metrics CVSS Version Base Score Base Severity Vector String 3.1 9.8 CRITICAL CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H CVE-2025-34183 Ilevia EVE X1 Server contains a vulnerability in its server-side logging mechanism that allows unauthenticated remote attackers to retrieve plaintext credentials from exposed .log files. This flaw enables full authentication bypass and system compromise through credential reuse. View CVE Details Affected Products Ilevia EVE X1 Server Vendor: Ilevia Product Version: Ilevia EVE X1: <=4.7.18.0 Product Status: known_affected Remediations Mitigation Ilevia recommends that users perform the following mitigation steps: Update to the newest version of Ilevia Manager at https://www.ilevia.com/downloads/. Verify port 8080 is closed on all devices and routers and enable access only through the secure option provided in the updated Ilevia Manager. Change all default passwords on active systems to strong, unique credentials to prevent unauthorized access and automated attacks. Review firewall configurations to confirm that internal protections are functioning as intended and external exposure is minimized. Monitor for unauthorized access attempts and apply network segmentation where possible to reduce attack surfaces. Relevant CWE: CWE-532 Insertion of Sensitive Information into Log File Metrics CVSS Version Base Score Base Severity Vector String 3.1 9.8 CRITICAL CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H CVE-2025-34186 Ilevia EVE X1/X5 Server contains a vulnerability in its authentication mechanism. Unsanitized input is passed to a system() call for authentication, allowing attackers to inject special characters and manipulate command parsing. Due to the binary's interpretation of non-zero exit codes as successful authentication, remote attackers can bypass authentication and gain full access to the system. View CVE Details Affected Products Ilevia EVE X1 Server Vendor: Ilevia Product Version: Ilevia EVE X1: <=4.7.18.0 Product Status: known_affected Remediations Mitigation Ilevia recommends that users perform the following mitigation steps: Update to the newest version of Ilevia Manager at https://www.ilevia.com/downloads/. Verify port 8080 is closed on all devices and routers and enable access only through the secure option provided in the updated Ilevia Manager. Change all default passwords on active systems to strong, unique credentials to prevent unauthorized access and automated attacks. Review firewall configurations to confirm that internal protections are functioning as intended and external exposure is minimized. Monitor for unauthorized access attempts and apply network segmentation where possible to reduce attack surfaces. Relevant CWE: CWE-78 Improper Neutralization of Special Elements used in an OS Command ('OS Command Injection') Metrics CVSS Version Base Score Base Severity Vector String 3.1 9.8 CRITICAL CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H CVE-2025-34187 Ilevia EVE X1/X5 Server contains a misconfiguration in the sudoers file that allows passwordless execution of certain Bash scripts. If these scripts are writable by web-facing users or accessible via command injection, attackers can replace them with malicious payloads. Execution with sudo grants full root access, resulting in remote privilege escalation and potential system compromise. View CVE Details Affected Products Ilevia EVE X1 Server Vendor: Ilevia Product Version: Ilevia EVE X1: <=4.7.18.0 Product Status: known_affected Remediations Mitigation Ilevia recommends that users perform the following mitigation steps: Update to the newest version of Ilevia Manager at https://www.ilevia.com/downloads/. Verify port 8080 is closed on all devices and routers and enable access only through the secure option provided in the updated Ilevia Manager. Change all default passwords on active systems to strong, unique credentials to prevent unauthorized access and automated attacks. Review firewall configurations to confirm that internal protections are functioning as intended and external exposure is minimized. Monitor for unauthorized access attempts and apply network segmentation where possible to reduce attack surfaces. Relevant CWE: CWE-78 Improper Neutralization of Special Elements used in an OS Command ('OS Command Injection') Metrics CVSS Version Base Score Base Severity Vector String 3.1 9.8 CRITICAL CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H CVE-2025-34517 Ilevia EVE X1 Server firmware contains an absolute path traversal vulnerability in get_file_content.php that allows an attacker to read arbitrary files. Ilevia has declined to service this vulnerability, and recommends that customers not expose port 8080 to the internet. View CVE Details Affected Products Ilevia EVE X1 Server Vendor: Ilevia Product Version: Ilevia EVE X1: <=4.7.18.0 Product Status: known_affected Remediations Mitigation Ilevia recommends that users perform the following mitigation steps: Update to the newest version of Ilevia Manager at https://www.ilevia.com/downloads/. Verify port 8080 is closed on all devices and routers and enable access only through the secure option provided in the updated Ilevia Manager. Change all default passwords on active systems to strong, unique credentials to prevent unauthorized access and automated attacks. Review firewall configurations to confirm that internal protections are functioning as intended and external exposure is minimized. Monitor for unauthorized access attempts and apply network segmentation where possible to reduce attack surfaces. Relevant CWE: CWE-22 Improper Limitation of a Pathname to a Restricted Directory ('Path Traversal') Metrics CVSS Version Base Score Base Severity Vector String 3.1 7.5 HIGH CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N CVE-2025-34518 Ilevia EVE X1 Server firmware contains a relative path traversal vulnerability in get_file_content.php that allows an attacker to read arbitrary files. Ilevia has declined to service this vulnerability, and recommends that customers not expose port 8080 to the internet. View CVE Details Affected Products Ilevia EVE X1 Server Vendor: Ilevia Product Version: Ilevia EVE X1: <=4.7.18.0 Product Status: known_affected Remediations Mitigation Ilevia recommends that users perform the following mitigation steps: Update to the newest version of Ilevia Manager at https://www.ilevia.com/downloads/. Verify port 8080 is closed on all devices and routers and enable access only through the secure option provided in the updated Ilevia Manager. Change all default passwords on active systems to strong, unique credentials to prevent unauthorized access and automated attacks. Review firewall configurations to confirm that internal protections are functioning as intended and external exposure is minimized. Monitor for unauthorized access attempts and apply network segmentation where possible to reduce attack surfaces. Relevant CWE: CWE-22 Improper Limitation of a Pathname to a Restricted Directory ('Path Traversal') Metrics CVSS Version Base Score Base Severity Vector String 3.1 7.5 HIGH CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N CVE-2025-34512 Ilevia EVE X1 Server firmware contains a reflected cross-site scripting (XSS) vulnerability in index.php that allows an unauthenticated attacker to execute arbitrary code. Ilevia has declined to service this vulnerability, and recommends that customers not expose port 8080 to the internet. View CVE Details Affected Products Ilevia EVE X1 Server Vendor: Ilevia Product Version: Ilevia EVE X1: <=4.7.18.0 Product Status: known_affected Remediations Mitigation Ilevia recommends that users perform the following mitigation steps: Update to the newest version of Ilevia Manager at https://www.ilevia.com/downloads/. Verify port 8080 is closed on all devices and routers and enable access only through the secure option provided in the updated Ilevia Manager. Change all default passwords on active systems to strong, unique credentials to prevent unauthorized access and automated attacks. Review firewall configurations to confirm that internal protections are functioning as intended and external exposure is minimized. Monitor for unauthorized access attempts and apply network segmentation where possible to reduce attack surfaces. Relevant CWE: CWE-79 Improper Neutralization of Input During Web Page Generation ('Cross-site Scripting') Metrics CVSS Version Base Score Base Severity Vector String 3.1 5.4 MEDIUM CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:U/C:L/I:L/A:N CVE-2025-34513 Ilevia EVE X1 Server firmware contains an OS command injection vulnerability in mbus_build_from_csv.php that allows an unauthenticated attacker to execute arbitrary code. Ilevia has declined to service this vulnerability, and recommends that customers not expose port 8080 to the internet. View CVE Details Affected Products Ilevia EVE X1 Server Vendor: Ilevia Product Version: Ilevia EVE X1: <=4.7.18.0 Product Status: known_affected Remediations Mitigation Ilevia recommends that users perform the following mitigation steps: Update to the newest version of Ilevia Manager at https://www.ilevia.com/downloads/. Verify port 8080 is closed on all devices and routers and enable access only through the secure option provided in the updated Ilevia Manager. Change all default passwords on active systems to strong, unique credentials to prevent unauthorized access and automated attacks. Review firewall configurations to confirm that internal protections are functioning as intended and external exposure is minimized. Monitor for unauthorized access attempts and apply network segmentation where possible to reduce attack surfaces. Relevant CWE: CWE-78 Improper Neutralization of Special Elements used in an OS Command ('OS Command Injection') Metrics CVSS Version Base Score Base Severity Vector String 3.1 9.8 CRITICAL CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H Acknowledgments Gjoko Krstic of Zero Science Lab reported these vulnerabilities to CISA Legal Notice and Terms of Use This product is provided subject to this Notification (https://www.cisa.gov/notification) and this Privacy & Use policy (https://www.cisa.gov/privacy-policy). Recommended Practices CISA recommends users take defensive measures to minimize the risk of exploitation of these vulnerabilities, such as: Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet. Locate control system networks and remote devices behind firewalls and isolating them from business networks. When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as the connected devices. CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures. CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies. CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets. Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies. Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents. CISA also recommends users take the following measures to protect themselves from social engineering attacks: Do not click web links or open attachments in unsolicited email messages. Refer to Recognizing and Avoiding Email Scams for more information on avoiding email scams. Refer to Avoiding Social Engineering and Phishing Attacks for more information on social engineering attacks. No known public exploitation specifically targeting these vulnerabilities has been reported to CISA at this time. Revision History Initial Release Date: 2026-02-05 Date Revision Summary 2026-02-05 1 Initial Publication Legal Notice and Terms of Use
· CISA Cybersecurity Advisory

Synectix LAN 232 TRIO

View CSAF Summary Successful exploitation of this vulnerability could result in an unauthenticated attacker modifying critical device settings or factory resetting the device. The following versions of Synectix LAN 232 TRIO are affected: LAN 232 TRIO vers:all/* (CVE-2026-1633) CVSS Vendor Equipment Vulnerabilities v3 10 Synectix Synectix LAN 232 TRIO Missing Authentication for Critical Function Background Critical…
Read full source summary
View CSAF Summary Successful exploitation of this vulnerability could result in an unauthenticated attacker modifying critical device settings or factory resetting the device. The following versions of Synectix LAN 232 TRIO are affected: LAN 232 TRIO vers:all/* (CVE-2026-1633) CVSS Vendor Equipment Vulnerabilities v3 10 Synectix Synectix LAN 232 TRIO Missing Authentication for Critical Function Background Critical Infrastructure Sectors: Critical Manufacturing, Emergency Services, Energy, Information Technology, Transportation Systems, Water and Wastewater Countries/Areas Deployed: Worldwide Company Headquarters Location: United States Vulnerabilities Expand All + CVE-2026-1633 The Synectix LAN 232 TRIO 3-Port serial to ethernet adapter exposes its web management interface without requiring authentication, allowing unauthenticated users to modify critical device settings or factory reset the device. View CVE Details Affected Products Synectix LAN 232 TRIO Vendor: Synectix Product Version: Synectix LAN 232 TRIO: vers:all/* Product Status: known_affected Remediations Mitigation The affected products should be considered end-of-life, as Synectix is no longer in business and therefore firmware fixes, mitigations and updates will be unavailable. Relevant CWE: CWE-306 Missing Authentication for Critical Function Metrics CVSS Version Base Score Base Severity Vector String 3.1 10 CRITICAL CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:H Acknowledgments Souvik Kandar of MicroSec (microsec.io) reported this vulnerability to CISA Legal Notice and Terms of Use This product is provided subject to this Notification (https://www.cisa.gov/notification) and this Privacy & Use policy (https://www.cisa.gov/privacy-policy). Recommended Practices CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability, such as: Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet. Locate control system networks and remote devices behind firewalls and isolating them from business networks. When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as the connected devices. CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures. CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies. CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets. Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies. Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents. No known public exploitation specifically targeting this vulnerability has been reported to CISA at this time. Revision History Initial Release Date: 2026-02-03 Date Revision Summary 2026-02-03 1 Initial Publication Legal Notice and Terms of Use
· CISA Cybersecurity Advisory

RISS SRL MOMA Seismic Station

View CSAF Summary Successful exploitation of this vulnerability could result in an unauthenticated attacker creating a denial-of-service condition. The following versions of RISS SRL MOMA Seismic Station are affected: MOMA Seismic Station <=v2.4.2520 (CVE-2026-1632) CVSS Vendor Equipment Vulnerabilities v3 9.1 RISS SRL RISS SRL MOMA Seismic Station Missing Authentication for Critical Function Background Critical…
Read full source summary
View CSAF Summary Successful exploitation of this vulnerability could result in an unauthenticated attacker creating a denial-of-service condition. The following versions of RISS SRL MOMA Seismic Station are affected: MOMA Seismic Station <=v2.4.2520 (CVE-2026-1632) CVSS Vendor Equipment Vulnerabilities v3 9.1 RISS SRL RISS SRL MOMA Seismic Station Missing Authentication for Critical Function Background Critical Infrastructure Sectors: Critical Manufacturing, Dams, Energy, Water and Wastewater, Transportation Systems Countries/Areas Deployed: Worldwide Company Headquarters Location: Italy Vulnerabilities Expand All + CVE-2026-1632 MOMA Seismic Station Version v2.4.2520 and prior exposes its web management interface without requiring authentication, which could allow an unauthenticated attacker to modify configuration settings, acquire device data or remotely reset the device. View CVE Details Affected Products RISS SRL MOMA Seismic Station Vendor: RISS SRL Product Version: RISS SRL MOMA Seismic Station: <=v2.4.2520 Product Status: known_affected Remediations Vendor fix RISS SRL did not respond to CISA's request for coordination. Users of RISS MOMA Seismic Station are encouraged to contact RISS SRL (info@riss-srl.com) for more information. Relevant CWE: CWE-306 Missing Authentication for Critical Function Metrics CVSS Version Base Score Base Severity Vector String 3.1 9.1 CRITICAL CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:N Acknowledgments Souvik Kandar reported this vulnerability to CISA Legal Notice and Terms of Use This product is provided subject to this Notification (https://www.cisa.gov/notification) and this Privacy & Use policy (https://www.cisa.gov/privacy-policy). Recommended Practices CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability, such as: Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet. Locate control system networks and remote devices behind firewalls and isolating them from business networks. When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as the connected devices. CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures. CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies. CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets. Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies. Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents. No known public exploitation specifically targeting this vulnerability has been reported to CISA at this time. Revision History Initial Release Date: 2026-02-03 Date Revision Summary 2026-02-03 1 Initial Publication Legal Notice and Terms of Use
· CISA Cybersecurity Advisory

Mitsubishi Electric FREQSHIP-mini for Windows

View CSAF Summary Successful exploitation of this vulnerability could allow an attacker to gain unauthorized access to, modify, delete, or destroy information stored on the system where the affected product is installed, or cause a denial-of-service condition on the affected system. The following versions of Mitsubishi Electric FREQSHIP-mini for Windows are affected: FREQSHIP-mini for Windows >=8.0.0|<=8.0.2…
Read full source summary
View CSAF Summary Successful exploitation of this vulnerability could allow an attacker to gain unauthorized access to, modify, delete, or destroy information stored on the system where the affected product is installed, or cause a denial-of-service condition on the affected system. The following versions of Mitsubishi Electric FREQSHIP-mini for Windows are affected: FREQSHIP-mini for Windows >=8.0.0|<=8.0.2 (CVE-2025-10314) CVSS Vendor Equipment Vulnerabilities v3 8.8 Mitsubishi Electric Mitsubishi Electric FREQSHIP-mini for Windows Incorrect Default Permissions Background Critical Infrastructure Sectors: Critical Manufacturing, Energy, Information Technology, Healthcare and Public Health, Government Services and Facilities Countries/Areas Deployed: Japan Company Headquarters Location: Japan Vulnerabilities Expand All + CVE-2025-10314 A malicious code execution vulnerability exists in Mitsubishi's small-capacity UPS shutdown software, FREQSHIP-mini for Windows, due to incorrect default permissions. A local attacker may be able to execute arbitrary code with system privileges by replacing service executable or DLL files in the installation directory with specially crafted files. View CVE Details Affected Products Mitsubishi Electric FREQSHIP-mini for Windows Vendor: Mitsubishi Electric Product Version: Mitsubishi Electric FREQSHIP-mini for Windows: >=8.0.0|<=8.0.2 Product Status: known_affected Remediations Vendor fix The vulnerability has been addressed in FREQSHIP-mini for Windows version 8.1.0 or later. Download and install the updated version from the Mitsubishi Electric download site at https://www.mitsubishielectric.co.jp/fa/download/index.html . Mitigation Mitsubishi Electric recommends that customers take the following mitigation measures to minimize the risk of this vulnerability being exploited: Use the PCs with the affected product installed only within a LAN, and block remote logins from untrusted networks, hosts, and non-administrator users. Block unauthorized access by using a firewall or virtual private network (VPN), etc., and allow remote login only for administrators when connecting the PCs with the affected product installed to the internet. Restrict physical access to the PC and its connected network to prevent unauthorized access. Do not click on links or open attachments in emails from untrusted sources. Install and regularly update antivirus software. Mitigation Mitsubishi Electric Corporation recommends users contact their local Mitsubishi Electric representative at https://www.mitsubishielectric.co.jp/fa/support/purchase/index.html with questions. Mitigation For additional details, refer to Mitsubishi Electric's security advisory at https://www.mitsubishielectric.com/en/psirt/vulnerability/pdf/2025-019_en.pdf . Relevant CWE: CWE-276 Incorrect Default Permissions Metrics CVSS Version Base Score Base Severity Vector String 3.1 8.8 HIGH CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:C/C:H/I:H/A:H Acknowledgments Kazuma Matsumoto of GMO Cybersecurity by IERAE, Inc. reported this vulnerability to Mitsubishi Electric Legal Notice and Terms of Use This product is provided subject to this Notification (https://www.cisa.gov/notification) and this Privacy & Use policy (https://www.cisa.gov/privacy-policy). Recommended Practices CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability. CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures. CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies. CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets. Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies. Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents. CISA also recommends users take the following measures to protect themselves from social engineering attacks: Do not click web links or open attachments in unsolicited email messages. Refer to Recognizing and Avoiding Email Scams for more information on avoiding email scams. Refer to Avoiding Social Engineering and Phishing Attacks for more information on social engineering attacks. No known public exploitation specifically targeting this vulnerability has been reported to CISA at this time. This vulnerability is not exploitable remotely. Revision History Initial Release Date: 2026-02-03 Date Revision Summary 2026-02-03 1 Initial Republication of Mitsubishi Electric 2025-019. Legal Notice and Terms of Use
· CISA Cybersecurity Advisory

Avation Light Engine Pro

View CSAF Summary Successful exploitation of this vulnerability could allow an attacker to take full control of the device. The following versions of Avation Light Engine Pro are affected: Light Engine Pro vers:all/* (CVE-2026-1341) CVSS Vendor Equipment Vulnerabilities v3 9.8 Avation Avation Light Engine Pro Missing Authentication for Critical Function Background Critical Infrastructure Sectors: Commercial…
Read full source summary
View CSAF Summary Successful exploitation of this vulnerability could allow an attacker to take full control of the device. The following versions of Avation Light Engine Pro are affected: Light Engine Pro vers:all/* (CVE-2026-1341) CVSS Vendor Equipment Vulnerabilities v3 9.8 Avation Avation Light Engine Pro Missing Authentication for Critical Function Background Critical Infrastructure Sectors: Commercial Facilities Countries/Areas Deployed: Worldwide Company Headquarters Location: Australia Vulnerabilities Expand All + CVE-2026-1341 Avation Light Engine Pro exposes its configuration and control interface without any authentication or access control. View CVE Details Affected Products Avation Light Engine Pro Vendor: Avation Product Version: Avation Light Engine Pro: vers:all/* Product Status: known_affected Remediations Vendor fix Avation has not responded to CISA's request to coordinate. Users of Avation Light Engine Pro are encouraged to contact Avation for more information. Relevant CWE: CWE-306 Missing Authentication for Critical Function Metrics CVSS Version Base Score Base Severity Vector String 3.1 9.8 CRITICAL CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H Acknowledgments Souvik Kandar reported this vulnerability to CISA Legal Notice and Terms of Use This product is provided subject to this Notification (https://www.cisa.gov/notification) and this Privacy & Use policy (https://www.cisa.gov/privacy-policy). Recommended Practices CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability, such as: Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet. Locate control system networks and remote devices behind firewalls and isolating them from business networks. When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as the connected devices. CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures. CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies. CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets. Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies. Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents. No known public exploitation specifically targeting this vulnerability has been reported to CISA at this time. Revision History Initial Release Date: 2026-02-03 Date Revision Summary 2026-02-03 1 Initial Publication Legal Notice and Terms of Use
· CISA Cybersecurity Advisory

CISA Adds Four Known Exploited Vulnerabilities to Catalog

CISA has added four new vulnerabilities to its Known Exploited Vulnerabilities (KEV) Catalog, based on evidence of active exploitation. CVE-2019-19006 Sangoma FreePBX Improper Authentication Vulnerability CVE-2021-39935 GitLab Community and Enterprise Editions Server-Side Request Forgery (SSRF) Vulnerability CVE-2025-40551 SolarWinds Web Help Desk Deserialization of Untrusted Data Vulnerability CVE-2025-64328…
Read full source summary
CISA has added four new vulnerabilities to its Known Exploited Vulnerabilities (KEV) Catalog, based on evidence of active exploitation. CVE-2019-19006 Sangoma FreePBX Improper Authentication Vulnerability CVE-2021-39935 GitLab Community and Enterprise Editions Server-Side Request Forgery (SSRF) Vulnerability CVE-2025-40551 SolarWinds Web Help Desk Deserialization of Untrusted Data Vulnerability CVE-2025-64328 Sangoma FreePBX OS Command Injection Vulnerability These types of vulnerabilities are frequent attack vectors for malicious cyber actors and pose significant risks to the federal enterprise. Binding Operational Directive (BOD) 22-01: Reducing the Significant Risk of Known Exploited Vulnerabilities established the KEV Catalog as a living list of known Common Vulnerabilities and Exposures (CVEs) that carry significant risk to the federal enterprise. BOD 22-01 requires Federal Civilian Executive Branch (FCEB) agencies to remediate identified vulnerabilities by the due date to protect FCEB networks against active threats. See the BOD 22-01 Fact Sheet for more information. Although BOD 22-01 only applies to FCEB agencies, CISA strongly urges all organizations to reduce their exposure to cyberattacks by prioritizing timely remediation of KEV Catalog vulnerabilities as part of their vulnerability management practice. CISA will continue to add vulnerabilities to the catalog that meet the specified criteria.
· CISA Cybersecurity Advisory

CISA Adds One Known Exploited Vulnerability to Catalog

CISA has added one new vulnerability to its Known Exploited Vulnerabilities (KEV) Catalog, based on evidence of active exploitation. CVE-2026-1281 Ivanti Endpoint Manager Mobile (EPMM) Code Injection Vulnerability This type of vulnerability is a frequent attack vector for malicious cyber actors and poses significant risks to the federal enterprise. Binding Operational Directive (BOD) 22-01: Reducing the Significant…
Read full source summary
CISA has added one new vulnerability to its Known Exploited Vulnerabilities (KEV) Catalog, based on evidence of active exploitation. CVE-2026-1281 Ivanti Endpoint Manager Mobile (EPMM) Code Injection Vulnerability This type of vulnerability is a frequent attack vector for malicious cyber actors and poses significant risks to the federal enterprise. Binding Operational Directive (BOD) 22-01: Reducing the Significant Risk of Known Exploited Vulnerabilities established the KEV Catalog as a living list of known Common Vulnerabilities and Exposures (CVEs) that carry significant risk to the federal enterprise. BOD 22-01 requires Federal Civilian Executive Branch (FCEB) agencies to remediate identified vulnerabilities by the due date to protect FCEB networks against active threats. See the BOD 22-01 Fact Sheet for more information. Although BOD 22-01 only applies to FCEB agencies, CISA strongly urges all organizations to reduce their exposure to cyberattacks by prioritizing timely remediation of KEV Catalog vulnerabilities as part of their vulnerability management practice. CISA will continue to add vulnerabilities to the catalog that meet the specified criteria.
· CISA Cybersecurity Advisory

Rockwell Automation ControlLogix

View CSAF Summary Successful exploitation of this vulnerability could allow an attacker to cause a denial-of-service condition. The following versions of Rockwell Automation ControlLogix are affected: ControlLogix Redundancy Enhanced Module Catalog 1756-RM2 Firmware vers:all/* (CVE-2025-14027) ControlLogix Redundancy Enhanced Module Catalog 1756-RM2XT Firmware vers:all/* (CVE-2025-14027) CVSS Vendor Equipment…
Read full source summary
View CSAF Summary Successful exploitation of this vulnerability could allow an attacker to cause a denial-of-service condition. The following versions of Rockwell Automation ControlLogix are affected: ControlLogix Redundancy Enhanced Module Catalog 1756-RM2 Firmware vers:all/* (CVE-2025-14027) ControlLogix Redundancy Enhanced Module Catalog 1756-RM2XT Firmware vers:all/* (CVE-2025-14027) CVSS Vendor Equipment Vulnerabilities v3 7.5 Rockwell Automation Rockwell Automation ControlLogix Missing Release of Memory after Effective Lifetime Background Critical Infrastructure Sectors: Chemical, Energy, Critical Manufacturing, Food and Agriculture, Transportation Systems, Water and Wastewater Countries/Areas Deployed: Worldwide Company Headquarters Location: United States Vulnerabilities Expand All + CVE-2025-14027 Multiple denial-of-service issues exist in 1756-RM2 and 1756-RM2XT firmware (ControlLogix Redundancy Enhanced Modules). These issues can be triggered through various crafted inputs, including malformed Class 3 messages, memory leak conditions, and other resource exhaustion scenarios. Exploitation may cause the device to become unresponsive and, in some cases, result in a major nonrecoverable fault. Recovery may require a restart. View CVE Details Affected Products Rockwell Automation ControlLogix Vendor: Rockwell Automation Product Version: Rockwell Automation ControlLogix Redundancy Enhanced Module Catalog 1756-RM2 Firmware: vers:all/*, Rockwell Automation ControlLogix Redundancy Enhanced Module Catalog 1756-RM2XT Firmware: vers:all/* Product Status: known_affected Remediations Mitigation Rockwell Automation recommends that users upgrade from the 1756-RM2 to 1756-RM3. Mitigation If users are unable to upgrade to the 1756-RM3, security best practices should be applied. Mitigation See Rockwell Automation's SD1769 advisory for more information. Relevant CWE: CWE-401 Missing Release of Memory after Effective Lifetime Metrics CVSS Version Base Score Base Severity Vector String 3.1 7.5 HIGH CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H Acknowledgments Rockwell Automation reported this vulnerability to CISA Legal Notice and Terms of Use This product is provided subject to this Notification (https://www.cisa.gov/notification) and this Privacy & Use policy (https://www.cisa.gov/privacy-policy). Recommended Practices CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability, such as: Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet. Locate control system networks and remote devices behind firewalls and isolating them from business networks. When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as the connected devices. CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures. CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies. CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets. Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies. Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents. No known public exploitation specifically targeting this vulnerability has been reported to CISA at this time. Revision History Initial Release Date: 2026-01-29 Date Revision Summary 2026-01-29 1 Initial Republication of Rockwell Automation advisory SD1769 Legal Notice and Terms of Use
· CISA Cybersecurity Advisory

Rockwell Automation ArmorStart LT

View CSAF Summary Successful exploitation of these vulnerabilities could allow an attacker to cause a denial-of-service condition. The following versions of Rockwell Automation ArmorStart LT are affected: ArmorStart LT 290D <=V2.002 (CVE-2025-9464, CVE-2025-9465, CVE-2025-9466, CVE-2025-9278, CVE-2025-9279, CVE-2025-9280, CVE-2025-9281, CVE-2025-9282, CVE-2025-9283) ArmorStart LT 291D <=V2.002 (CVE-2025-9464,…
Read full source summary
View CSAF Summary Successful exploitation of these vulnerabilities could allow an attacker to cause a denial-of-service condition. The following versions of Rockwell Automation ArmorStart LT are affected: ArmorStart LT 290D <=V2.002 (CVE-2025-9464, CVE-2025-9465, CVE-2025-9466, CVE-2025-9278, CVE-2025-9279, CVE-2025-9280, CVE-2025-9281, CVE-2025-9282, CVE-2025-9283) ArmorStart LT 291D <=V2.002 (CVE-2025-9464, CVE-2025-9465, CVE-2025-9466, CVE-2025-9278, CVE-2025-9279, CVE-2025-9280, CVE-2025-9281, CVE-2025-9282, CVE-2025-9283) ArmorStart LT 294D <=V2.002 (CVE-2025-9464, CVE-2025-9465, CVE-2025-9466, CVE-2025-9278, CVE-2025-9279, CVE-2025-9280, CVE-2025-9281, CVE-2025-9282, CVE-2025-9283) CVSS Vendor Equipment Vulnerabilities v3 7.5 Rockwell Automation Rockwell Automation ArmorStart LT Uncontrolled Resource Consumption Background Critical Infrastructure Sectors: Critical Manufacturing Countries/Areas Deployed: Worldwide Company Headquarters Location: United States Vulnerabilities Expand All + CVE-2025-9464 A security issue exists within ArmorStart® LT that can result in a denial-of-service condition. This vulnerability is triggered during fuzzing of multiple CIP classes, which causes the CIP port to become unresponsive. View CVE Details Affected Products Rockwell Automation ArmorStart LT Vendor: Rockwell Automation Product Version: Rockwell Automation ArmorStart LT 290D: <=V2.002, Rockwell Automation ArmorStart LT 291D: <=V2.002, Rockwell Automation ArmorStart LT 294D: <=V2.002 Product Status: known_affected Remediations Mitigation There is no patch or upgrade at this time. Rockwell Automation recommends users apply security best practices to mitigate the risk of these vulnerabilities. Mitigation See Rockwell Automation's SD1768 advisory for more information. Relevant CWE: CWE-400 Uncontrolled Resource Consumption Metrics CVSS Version Base Score Base Severity Vector String 3.1 7.5 HIGH CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H CVE-2025-9465 A security issue exists within ArmorStart® LT that can result in a denial-of-service condition. During execution of the Achilles Comprehensive grammar tests, the device reboots unexpectedly, causing the Link State Monitor to go down for several seconds. View CVE Details Affected Products Rockwell Automation ArmorStart LT Vendor: Rockwell Automation Product Version: Rockwell Automation ArmorStart LT 290D: <=V2.002, Rockwell Automation ArmorStart LT 291D: <=V2.002, Rockwell Automation ArmorStart LT 294D: <=V2.002 Product Status: known_affected Remediations Mitigation There is no patch or upgrade at this time. Rockwell Automation recommends users apply security best practices to mitigate the risk of these vulnerabilities. Mitigation See Rockwell Automation's SD1768 advisory for more information. Relevant CWE: CWE-400 Uncontrolled Resource Consumption Metrics CVSS Version Base Score Base Severity Vector String 3.1 7.5 HIGH CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H CVE-2025-9466 A security issue exists within ArmorStart® LT that can result in a denial-of-service condition. During execution of the Achilles EtherNet/IP and CIP grammar tests, the device reboots unexpectedly, causing the Link State Monitor to go down for several seconds. View CVE Details Affected Products Rockwell Automation ArmorStart LT Vendor: Rockwell Automation Product Version: Rockwell Automation ArmorStart LT 290D: <=V2.002, Rockwell Automation ArmorStart LT 291D: <=V2.002, Rockwell Automation ArmorStart LT 294D: <=V2.002 Product Status: known_affected Remediations Mitigation There is no patch or upgrade at this time. Rockwell Automation recommends users apply security best practices to mitigate the risk of these vulnerabilities. Mitigation See Rockwell Automation's SD1768 advisory for more information. Relevant CWE: CWE-400 Uncontrolled Resource Consumption Metrics CVSS Version Base Score Base Severity Vector String 3.1 7.5 HIGH CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H CVE-2025-9278 A security issue exists within ArmorStart® LT that can result in a denial-of-service condition. After running a Burp Suite active scan, the device loses ICMP connectivity, causing the web application to become inaccessible. View CVE Details Affected Products Rockwell Automation ArmorStart LT Vendor: Rockwell Automation Product Version: Rockwell Automation ArmorStart LT 290D: <=V2.002, Rockwell Automation ArmorStart LT 291D: <=V2.002, Rockwell Automation ArmorStart LT 294D: <=V2.002 Product Status: known_affected Remediations Mitigation There is no patch or upgrade at this time. Rockwell Automation recommends users apply security best practices to mitigate the risk of these vulnerabilities. Mitigation See Rockwell Automation's SD1768 advisory for more information. Relevant CWE: CWE-400 Uncontrolled Resource Consumption Metrics CVSS Version Base Score Base Severity Vector String 3.1 7.5 HIGH CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H CVE-2025-9279 A security issue exists within ArmorStart® LT that can result in a denial-of-service condition. During execution of the Achilles EtherNet/IP Step Limit Storm tests, the device reboots unexpectedly, causing the Link State Monitor to go down for several seconds. View CVE Details Affected Products Rockwell Automation ArmorStart LT Vendor: Rockwell Automation Product Version: Rockwell Automation ArmorStart LT 290D: <=V2.002, Rockwell Automation ArmorStart LT 291D: <=V2.002, Rockwell Automation ArmorStart LT 294D: <=V2.002 Product Status: known_affected Remediations Mitigation There is no patch or upgrade at this time. Rockwell Automation recommends users apply security best practices to mitigate the risk of these vulnerabilities. Mitigation See Rockwell Automation's SD1768 advisory for more information. Relevant CWE: CWE-400 Uncontrolled Resource Consumption Metrics CVSS Version Base Score Base Severity Vector String 3.1 7.5 HIGH CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H CVE-2025-9280 A security issue exists within ArmorStart® LT that can result in a denial-of-service condition. Fuzzing performed using Defensics causes the device to become unresponsive, requiring a reboot. View CVE Details Affected Products Rockwell Automation ArmorStart LT Vendor: Rockwell Automation Product Version: Rockwell Automation ArmorStart LT 290D: <=V2.002, Rockwell Automation ArmorStart LT 291D: <=V2.002, Rockwell Automation ArmorStart LT 294D: <=V2.002 Product Status: known_affected Remediations Mitigation There is no patch or upgrade at this time. Rockwell Automation recommends users apply security best practices to mitigate the risk of these vulnerabilities. Mitigation See Rockwell Automation's SD1768 advisory for more information. Relevant CWE: CWE-400 Uncontrolled Resource Consumption Metrics CVSS Version Base Score Base Severity Vector String 3.1 7.5 HIGH CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H CVE-2025-9281 A security issue exists within ArmorStart® LT that can result in a denial-of-service condition. During execution of the Achilles Comprehensive step limit storm tests, the device reboots unexpectedly, causing the Link State Monitor to go down for several seconds. View CVE Details Affected Products Rockwell Automation ArmorStart LT Vendor: Rockwell Automation Product Version: Rockwell Automation ArmorStart LT 290D: <=V2.002, Rockwell Automation ArmorStart LT 291D: <=V2.002, Rockwell Automation ArmorStart LT 294D: <=V2.002 Product Status: known_affected Remediations Mitigation There is no patch or upgrade at this time. Rockwell Automation recommends users apply security best practices to mitigate the risk of these vulnerabilities. Mitigation See Rockwell Automation's SD1768 advisory for more information. Relevant CWE: CWE-400 Uncontrolled Resource Consumption Metrics CVSS Version Base Score Base Severity Vector String 3.1 7.5 HIGH CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H CVE-2025-9282 A security issue exists within ArmorStart® LT that can result in a denial-of-service condition. During execution of the Achilles Comprehensive limited storm tests, the device reboots unexpectedly, causing the Link State Monitor to go down for several seconds. View CVE Details Affected Products Rockwell Automation ArmorStart LT Vendor: Rockwell Automation Product Version: Rockwell Automation ArmorStart LT 290D: <=V2.002, Rockwell Automation ArmorStart LT 291D: <=V2.002, Rockwell Automation ArmorStart LT 294D: <=V2.002 Product Status: known_affected Remediations Mitigation There is no patch or upgrade at this time. Rockwell Automation recommends users apply security best practices to mitigate the risk of these vulnerabilities. Mitigation See Rockwell Automation's SD1768 advisory for more information. Relevant CWE: CWE-400 Uncontrolled Resource Consumption Metrics CVSS Version Base Score Base Severity Vector String 3.1 7.5 HIGH CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H CVE-2025-9283 A security issue exists within ArmorStart® LT that can result in a denial-of-service condition. During execution of the Achilles EtherNet/IP Step Limits Storms tests, the device reboots unexpectedly, causing the Link State Monitor to go down for several seconds. View CVE Details Affected Products Rockwell Automation ArmorStart LT Vendor: Rockwell Automation Product Version: Rockwell Automation ArmorStart LT 290D: <=V2.002, Rockwell Automation ArmorStart LT 291D: <=V2.002, Rockwell Automation ArmorStart LT 294D: <=V2.002 Product Status: known_affected Remediations Mitigation There is no patch or upgrade at this time. Rockwell Automation recommends users apply security best practices to mitigate the risk of these vulnerabilities. Mitigation See Rockwell Automation's SD1768 advisory for more information. Relevant CWE: CWE-400 Uncontrolled Resource Consumption Metrics CVSS Version Base Score Base Severity Vector String 3.1 7.5 HIGH CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H Acknowledgments Rockwell Automation reported these vulnerabilties to CISA Legal Notice and Terms of Use This product is provided subject to this Notification (https://www.cisa.gov/notification) and this Privacy & Use policy (https://www.cisa.gov/privacy-policy). Recommended Practices CISA recommends users take defensive measures to minimize the risk of exploitation of these vulnerabilities, such as: Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet. Locate control system networks and remote devices behind firewalls and isolating them from business networks. When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as the connected devices. CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures. CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies. CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets. Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies. Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents. No known public exploitation specifically targeting these vulnerabilities has been reported to CISA at this time. Revision History Initial Release Date: 2026-01-29 Date Revision Summary 2026-01-29 1 Initial Republication of Rockwell Automation advisory SD1768 Legal Notice and Terms of Use
· CISA Cybersecurity Advisory

KiloView Encoder Series (Update A)

View CSAF Summary Successful exploitation of this vulnerability could allow an unauthenticated attacker to create or delete administrator accounts, granting full administrative control. The following versions of KiloView Encoder Series are affected: Encoder Series E1 hardware Version 1.4 4.7.2516 (CVE-2026-1453) Encoder Series E1 hardware Version 1.6.20…
Read full source summary
View CSAF Summary Successful exploitation of this vulnerability could allow an unauthenticated attacker to create or delete administrator accounts, granting full administrative control. The following versions of KiloView Encoder Series are affected: Encoder Series E1 hardware Version 1.4 4.7.2516 (CVE-2026-1453) Encoder Series E1 hardware Version 1.6.20 4.7.2511|4.8.2523|4.8.2611|4.6.2400|4.7.2512|4.8.2561|4.8.2554|4.3.2029|4.8.2555|4.6.2408 (CVE-2026-1453) Encoder Series E1-s hardware Version 1.4 4.7.2516|4.8.2519|4.8.2525|4.8.2611|4.8.2561|4.8.2554|4.8.2523 (CVE-2026-1453) Encoder Series E2 hardware Version 1.7.20 4.8.2611|4.8.2561 (CVE-2026-1453) Encoder Series E2 hardware Version 1.8.20 4.8.2523|4.8.2611|4.8.2554 (CVE-2026-1453) Encoder Series G1 hardware Version 1.6.20 4.8.2561 (CVE-2026-1453) Encoder Series P1 hardware Version 1.3.20 4.8.2633|4.8.2608 (CVE-2026-1453) Encoder Series P2 hardware Version 1.8.20 4.8.2633 (CVE-2026-1453) Encoder Series RE1 hardware Version 2.0.00 4.7.2513 (CVE-2026-1453) Encoder Series RE1 hardware Version 3.0.00 4.8.2519|4.8.2561|4.8.2611|4.8.2525 (CVE-2026-1453) CVSS Vendor Equipment Vulnerabilities v3 9.8 KiloView KiloView Encoder Series Missing Authentication for Critical Function Background Critical Infrastructure Sectors: Communications, Information Technology Countries/Areas Deployed: Worldwide Company Headquarters Location: China Vulnerabilities Expand All + CVE-2026-1453 A missing authentication for critical function vulnerability in KiloView Encoder Series could allow an unauthenticated attacker to create or delete administrator accounts. This vulnerability can grant the attacker full administrative control over the product. View CVE Details Affected Products KiloView Encoder Series Vendor: KiloView Product Version: KiloView Encoder Series E1 hardware Version 1.4: 4.7.2516, KiloView Encoder Series E1 hardware Version 1.6.20: 4.7.2511|4.8.2523|4.8.2611|4.6.2400|4.7.2512|4.8.2561|4.8.2554|4.3.2029|4.8.2555|4.6.2408, KiloView Encoder Series E1-s hardware Version 1.4: 4.7.2516|4.8.2519|4.8.2525|4.8.2611|4.8.2561|4.8.2554|4.8.2523, KiloView Encoder Series E2 hardware Version 1.7.20: 4.8.2611|4.8.2561, KiloView Encoder Series E2 hardware Version 1.8.20: 4.8.2523|4.8.2611|4.8.2554, KiloView Encoder Series G1 hardware Version 1.6.20: 4.8.2561, KiloView Encoder Series P1 hardware Version 1.3.20: 4.8.2633|4.8.2608, KiloView Encoder Series P2 hardware Version 1.8.20: 4.8.2633, KiloView Encoder Series RE1 hardware Version 2.0.00: 4.7.2513, KiloView Encoder Series RE1 hardware Version 3.0.00: 4.8.2519|4.8.2561|4.8.2611|4.8.2525 Product Status: known_affected Remediations Mitigation KiloView states that these specific hardware versions are end-of-life; therefore, no patches will be released due to hardware limitations. KiloView recommends that users implement mitigation measures such as network isolation or upgrade to newer hardware generations. Mitigation Users of affected versions of KiloView Encoder Series are invited to contact KiloView customer support at https://www.kiloview.com/contact/ for additional information. Relevant CWE: CWE-306 Missing Authentication for Critical Function Metrics CVSS Version Base Score Base Severity Vector String 3.1 9.8 CRITICAL CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H Acknowledgments Muhammad Ammar (0xam225) reported this vulnerability to CISA Legal Notice and Terms of Use This product is provided subject to this Notification (https://www.cisa.gov/notification) and this Privacy & Use policy (https://www.cisa.gov/privacy-policy). Recommended Practices CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability, such as: Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the Internet. Locate control system networks and remote devices behind firewalls and isolating them from business networks. When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as the connected devices. CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures. CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies. CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets. Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies. Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents. CISA also recommends users take the following measures to protect themselves from social engineering attacks: Do not click web links or open attachments in unsolicited email messages. Refer to Recognizing and Avoiding Email Scams for more information on avoiding email scams. Refer to Avoiding Social Engineering and Phishing Attacks for more information on social engineering attacks. No known public exploitation specifically targeting this vulnerability has been reported to CISA at this time. Revision History Initial Release Date: 2026-01-29 Date Revision Summary 2026-01-29 1 Initial Publication 2026-02-05 2 Update A - Affected products are end-of-life Legal Notice and Terms of Use
· CISA Cybersecurity Advisory

Fortinet Releases Guidance to Address Ongoing Exploitation of Authentication Bypass Vulnerability CVE-2026-24858

Newly disclosed vulnerability Common Vulnerabilities and Exposures (CVE)-2026-24858 [Common Weakness Enumeration (CWE)-288: Authentication Bypass Using an Alternate Path or Channel] allows malicious actors with a FortiCloud account and a registered device to log in to separate devices registered to other users in FortiOS, FortiManager, FortiWeb, FortiProxy, and FortiAnalyzer, if FortiCloud single sign on (SSO) is…
Read full source summary
Newly disclosed vulnerability Common Vulnerabilities and Exposures (CVE)-2026-24858 [Common Weakness Enumeration (CWE)-288: Authentication Bypass Using an Alternate Path or Channel] allows malicious actors with a FortiCloud account and a registered device to log in to separate devices registered to other users in FortiOS, FortiManager, FortiWeb, FortiProxy, and FortiAnalyzer, if FortiCloud single sign on (SSO) is enabled on devices.1 Users are vulnerable to CVE-2026-24858 even if they updated Fortinet devices to address previously disclosed FortiCloud SSO bypass vulnerabilities CVE-2025-59718 and CVE-2025-59719 [CWE-347: Improper Verification of Cryptographic Signature].2 CVE-2025-59718 and CVE-2025-59719 affect FortiOS, FortiWeb, FortiProxy, and FortiSwitch Manager, and allow malicious actors to bypass the SSO login authentication via a crafted Security Assertion Markup Language (SAML) message.3 On Fortinet devices that had been fully upgraded to the latest release addressing CVE-2025-59718 and CVE-2025-59719 at the time of CVE-2026-24858 exploitation, Fortinet observed the following malicious activity: Unauthorized firewall configuration changes on FortiGate devices. Unauthorized creation of accounts. Unauthorized configuration changes of virtual private networks (VPNs) to grant access to new accounts.4 According to Fortinet, on Jan. 26, 2026, Fortinet disabled all FortiCloud SSO authentication to mitigate CVE-2026-24858, then reinstated the service on Jan. 27, 2026, with changes to prevent exploitation of vulnerable devices. CISA added CVE-2026-24858 to its Known Exploited Vulnerabilities (KEV) Catalog on Jan. 27, 2026. CISA urges users to check for indicators of compromise on all internet-accessible Fortinet products affected by this vulnerability and immediately apply updates as soon as they are available using Fortinet’s instructions: Administrative FortiCloud SSO authentication bypass Analysis of Single Sign-On Abuse on FortiOS Disclaimer The information in this report is being provided “as is” for informational purposes only. CISA does not endorse any commercial entity, product, company, or service, including any entities, products, or services linked within this document. Any reference to specific commercial entities, products, processes, or services by service mark, trademark, manufacturer, or otherwise, does not constitute or imply endorsement, recommendation, or favoring by CISA. Notes Fortinet, “Administrative FortiCloud SSO Authentication Bypass,” FortiGuard Labs, last modified January 27, 2026, https://fortiguard.fortinet.com/psirt/FG-IR-26-060. Fortinet, “Multiple Fortinet Products’ FortiCloud SSO Login Authentication Bypass,” FortiGuard Labs, last modified December 9, 2025, https://fortiguard.fortinet.com/psirt/FG-IR-25-647. Carl Windsor, “Analysis of Single Sign-On Abuse on FortiOS,” PSIRT Blogs (blog), Fortinet, last modified January 22, 2026, https://www.fortinet.com/blog/psirt-blogs/analysis-of-sso-abuse-on-fortios. Arctic Wolf Labs, “Arctic Wolf Observes Malicious Configuration Changes on Fortinet FortiGate Devices via SSO Accounts,” Arctic Wolf Blog (blog), Arctic Wolf, last modified January 21, 2026, https://arcticwolf.com/resources/blog/arctic-wolf-observes-malicious-configuration-changes-fortinet-fortigate-devices-via-sso-accounts/.
· CISA Cybersecurity Advisory

Festo Didactic SE MES PC

View CSAF Summary MES PCs shipped with Windows 10 come pre-installed with XAMPP. XAMPP is a bundle of third-party open-source applications including the Apache HTTP Server, the MariaDB database and more. From time to time, vulnerabilities in these applications are discovered. These are fixed in newer versions of XAMPP by updating the bundled applications. MES PCs shipped with Windows 10 include a copy of XAMPP which…
Read full source summary
View CSAF Summary MES PCs shipped with Windows 10 come pre-installed with XAMPP. XAMPP is a bundle of third-party open-source applications including the Apache HTTP Server, the MariaDB database and more. From time to time, vulnerabilities in these applications are discovered. These are fixed in newer versions of XAMPP by updating the bundled applications. MES PCs shipped with Windows 10 include a copy of XAMPP which contains around 140 such vulnerabilities listed in this advisory. They can be fixed by replacing XAMPP with Festo Didactic's Factory Control Panel application. The following versions of Festo Didactic SE MES PC are affected: MES PC (CVE-2019-11036, CVE-2023-25727, CVE-2021-2011, CVE-2022-32083, CVE-2021-46668, CVE-2018-19518, CVE-2021-2194, CVE-2019-11049, CVE-2022-31626, CVE-2022-32084, CVE-2022-32088, CVE-2022-27377, CVE-2020-2922, CVE-2019-9638, CVE-2019-11044, CVE-2020-7068, CVE-2020-7069, CVE-2015-2301, CVE-2023-0568, CVE-2022-27458, CVE-2021-21706, CVE-2022-27452, CVE-2020-7071, CVE-2022-27387, CVE-2022-27376, CVE-2019-11043, CVE-2021-2032, CVE-2021-2007, CVE-2019-11045, CVE-2022-27445, CVE-2022-27457, CVE-2022-27384, CVE-2022-23808, CVE-2023-0567, CVE-2019-9025, CVE-2022-27379, CVE-2019-9637, CVE-2021-27928, CVE-2021-21703, CVE-2020-2760, CVE-2021-2166, CVE-2015-2787, CVE-2022-23807, CVE-2020-2752, CVE-2021-46666, CVE-2020-2814, CVE-2020-7065, CVE-2021-21705, CVE-2020-7062, CVE-2019-11039, CVE-2019-11035, CVE-2022-27447, CVE-2019-11046, CVE-2022-27446, CVE-2022-27386, CVE-2019-9639, CVE-2019-11042, CVE-2022-27385, CVE-2020-7059, CVE-2020-7070, CVE-2022-32091, CVE-2015-2348, CVE-2019-9020, CVE-2021-35604, CVE-2022-27444, CVE-2018-14883, CVE-2014-9705, CVE-2020-7064, CVE-2022-27382, CVE-2020-7063, CVE-2021-2372, CVE-2019-9021, CVE-2018-14851, CVE-2022-27448, CVE-2021-46663, CVE-2021-2180, CVE-2014-9709, CVE-2023-25690, CVE-2022-32082, CVE-2022-31629, CVE-2019-9022, CVE-2016-3078, CVE-2023-0662, CVE-2021-2022, CVE-2022-32089, CVE-2019-11048, CVE-2021-46669, CVE-2019-11047, CVE-2022-27383, CVE-2021-46667, CVE-2022-32087, CVE-2022-36760, CVE-2020-7060, CVE-2018-17082, CVE-2019-9640, CVE-2021-46661, CVE-2019-11034, CVE-2022-27456, CVE-2020-7061, CVE-2022-27455, CVE-2021-2144, CVE-2021-2154, CVE-2022-21595, CVE-2019-11040, CVE-2021-2389, CVE-2023-27522, CVE-2020-2812, CVE-2021-46665, CVE-2022-32086, CVE-2022-32085, CVE-2021-21704, CVE-2020-7066, CVE-2022-31628, CVE-2021-46662, CVE-2016-5385, CVE-2022-37436, CVE-2013-6501, CVE-2021-21702, CVE-2019-9024, CVE-2019-9023, CVE-2022-27449, CVE-2021-46664, CVE-2019-11050, CVE-2021-21708, CVE-2022-31625, CVE-2022-32081, CVE-2022-27378, CVE-2006-20001, CVE-2018-19935, CVE-2022-4900, CVE-2018-12882, CVE-2019-9641, CVE-2022-27380, CVE-2022-27381, CVE-2021-21707, CVE-2022-27451, CVE-2020-2780, CVE-2019-11041, CVE-2021-2174) CVSS Vendor Equipment Vulnerabilities v3 9.8 Festo Didactic SE Festo Didactic SE MES PC Buffer Over-read, Improper Neutralization of Input During Web Page Generation ('Cross-site Scripting'), Improper Input Validation, Improper Handling of Values, Uncontrolled Resource Consumption, Improper Neutralization of Argument Delimiters in a Command ('Argument Injection'), Double Free, Buffer Copy without Checking Size of Input ('Classic Buffer Overflow'), Use After Free, Exposure of Sensitive Information to an Unauthorized Actor, Out-of-bounds Read, Improper Null Termination, Incorrect Calculation of Buffer Size, Path Traversal: '../filedir', Reachable Assertion, Improper Neutralization of Special Elements used in an SQL Command ('SQL Injection'), Use of Password Hash With Insufficient Computational Effort, Out-of-bounds Write, Incorrect Privilege Assignment, Improper Control of Generation of Code ('Code Injection'), Improper Authentication, Stack-based Buffer Overflow, NULL Pointer Dereference, Missing Initialization of Resource, Null Byte Interaction Error (Poison Null Byte), Improper Restriction of Operations within the Bounds of a Memory Buffer, Improper Preservation of Permissions, Inconsistent Interpretation of HTTP Requests ('HTTP Request/Response Smuggling'), Integer Overflow or Wraparound, Uncontrolled Recursion, URL Redirection to Untrusted Site ('Open Redirect'), Improper Neutralization of CRLF Sequences in HTTP Headers ('HTTP Request/Response Splitting'), Improper Neutralization of Special Elements in Output Used by a Downstream Component ('Injection'), Free of Memory not on the Heap, Use of Uninitialized Resource, Improper Handling of Invalid Use of Special Elements, Improper Use of Validation Framework Background Critical Infrastructure Sectors: Commercial Facilities, Communications, Critical Manufacturing, Energy Countries/Areas Deployed: Worldwide Company Headquarters Location: Germany Vulnerabilities Expand All + CVE-2019-11036 When processing certain files, PHP EXIF extension in versions 7.1.x below 7.1.29, 7.2.x below 7.2.18 and 7.3.x below 7.3.5 can be caused to read past allocated buffer in exif_process_IFD_TAG function. This may lead to information disclosure or crash. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-126 Buffer Over-read Metrics CVSS Version Base Score Base Severity Vector String 3.1 9.1 CRITICAL CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:H CVE-2023-25727 In phpMyAdmin before 4.9.11 and 5.x before 5.2.1, an authenticated user can trigger XSS by uploading a crafted .sql file through the drag-and-drop interface. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-79 Improper Neutralization of Input During Web Page Generation ('Cross-site Scripting') Metrics CVSS Version Base Score Base Severity Vector String 3.1 5.4 MEDIUM CVSS:3.1/AV:N/AC:L/PR:L/UI:R/S:C/C:L/I:L/A:N CVE-2021-2011 Vulnerability in the MySQL Client product of Oracle MySQL (component: C API). Supported versions that are affected are 5.7.32 and prior and 8.0.22 and prior. Difficult to exploit vulnerability allows unauthenticated attacker with network access via multiple protocols to compromise MySQL Client. Successful attacks of this vulnerability can result in unauthorized ability to cause a hang or frequently repeatable crash (complete DOS) of MySQL Client. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-20 Improper Input Validation Metrics CVSS Version Base Score Base Severity Vector String 3.1 5.9 MEDIUM CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:N/I:N/A:H CVE-2022-32083 MariaDB v10.2 to v10.6.1 was discovered to contain a segmentation fault via the component Item_subselect::init_expr_cache_tracker. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-229 Improper Handling of Values Metrics CVSS Version Base Score Base Severity Vector String 3.1 7.5 HIGH CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H CVE-2021-46668 MariaDB through 10.5.9 allows an application crash via certain long SELECT DISTINCT statements that improperly interact with storage-engine resource limitations for temporary data structures. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-400 Uncontrolled Resource Consumption Metrics CVSS Version Base Score Base Severity Vector String 3.1 5.5 MEDIUM CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H CVE-2018-19518 University of Washington IMAP Toolkit 2007f on UNIX, as used in imap_open() in PHP and other products, launches an rsh command (by means of the imap_rimap function in c-client/imap4r1.c and the tcp_aopen function in osdep/unix/tcp_unix.c) without preventing argument injection, which might allow remote attackers to execute arbitrary OS commands if the IMAP server name is untrusted input (e.g., entered by a user of a web application) and if rsh has been replaced by a program with different argument semantics. For example, if rsh is a link to ssh (as seen on Debian and Ubuntu systems), then the attack can use an IMAP server name containing a "-oProxyCommand" argument. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-88 Improper Neutralization of Argument Delimiters in a Command ('Argument Injection') Metrics CVSS Version Base Score Base Severity Vector String 3.1 7.5 HIGH CVSS:3.1/AV:N/AC:H/PR:L/UI:N/S:U/C:H/I:H/A:H CVE-2021-2194 Vulnerability in the MySQL Server product of Oracle MySQL (component: InnoDB). Supported versions that are affected are 5.7.33 and prior and 8.0.23 and prior. Easily exploitable vulnerability allows high privileged attacker with network access via multiple protocols to compromise MySQL Server. Successful attacks of this vulnerability can result in unauthorized ability to cause a hang or frequently repeatable crash (complete DOS) of MySQL Server. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-20 Improper Input Validation Metrics CVSS Version Base Score Base Severity Vector String 3.1 4.9 MEDIUM CVSS:3.1/AV:N/AC:L/PR:H/UI:N/S:U/C:N/I:N/A:H CVE-2019-11049 In PHP versions 7.3.x below 7.3.13 and 7.4.0 on Windows, when supplying custom headers to mail() function, due to mistake introduced in commit 78f4b4a2dcf92ddbccea1bb95f8390a18ac3342e, if the header is supplied in lowercase, this can result in double-freeing certain memory locations. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-415 Double Free Metrics CVSS Version Base Score Base Severity Vector String 3.1 9.8 CRITICAL CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H CVE-2022-31626 In PHP versions 7.4.x below 7.4.30, 8.0.x below 8.0.20, and 8.1.x below 8.1.7, when pdo_mysql extension with mysqlnd driver, if the third party is allowed to supply host to connect to and the password for the connection, password of excessive length can trigger a buffer overflow in PHP, which can lead to a remote code execution vulnerability. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-120 Buffer Copy without Checking Size of Input ('Classic Buffer Overflow') Metrics CVSS Version Base Score Base Severity Vector String 3.1 8.8 HIGH CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H CVE-2022-32084 MariaDB v10.2 to v10.7 was discovered to contain a segmentation fault via the component sub_select. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-229 Improper Handling of Values Metrics CVSS Version Base Score Base Severity Vector String 3.1 7.5 HIGH CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H CVE-2022-32088 MariaDB v10.2 to v10.7 was discovered to contain a segmentation fault via the component Exec_time_tracker::get_loops/Filesort_tracker::report_use/filesort. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-229 Improper Handling of Values Metrics CVSS Version Base Score Base Severity Vector String 3.1 7.5 HIGH CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H CVE-2022-27377 MariaDB Server v10.6.3 and below was discovered to contain an use-after-free in the component Item_func_in::cleanup(), which is exploited via specially crafted SQL statements. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-416 Use After Free Metrics CVSS Version Base Score Base Severity Vector String 3.1 7.5 HIGH CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H CVE-2020-2922 Vulnerability in the MySQL Client product of Oracle MySQL (component: C API). Supported versions that are affected are 5.6.47 and prior, 5.7.29 and prior and 8.0.18 and prior. Difficult to exploit vulnerability allows unauthenticated attacker with network access via multiple protocols to compromise MySQL Client. Successful attacks of this vulnerability can result in unauthorized read access to a subset of MySQL Client accessible data. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-200 Exposure of Sensitive Information to an Unauthorized Actor Metrics CVSS Version Base Score Base Severity Vector String 3.1 3.7 LOW CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:L/I:N/A:N CVE-2019-9638 An issue was discovered in the EXIF component in PHP before 7.1.27, 7.2.x before 7.2.16, and 7.3.x before 7.3.3. There is an uninitialized read in exif_process_IFD_in_MAKERNOTE because of mishandling the maker_note->offset relationship to value_len. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-125 Out-of-bounds Read Metrics CVSS Version Base Score Base Severity Vector String 3.1 7.5 HIGH CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N CVE-2019-11044 In PHP versions 7.2.x below 7.2.26, 7.3.x below 7.3.13 and 7.4.0 on Windows, PHP link() function accepts filenames with embedded \0 byte and treats them as terminating at that byte. This could lead to security vulnerabilities, e.g. in applications checking paths that the code is allowed to access. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-170 Improper Null Termination Metrics CVSS Version Base Score Base Severity Vector String 3.1 7.5 HIGH CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N CVE-2020-7068 In PHP versions 7.2.x below 7.2.33, 7.3.x below 7.3.21 and 7.4.x below 7.4.9, while processing PHAR files using phar extension, phar_parse_zipfile could be tricked into accessing freed memory, which could lead to a crash or information disclosure. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-416 Use After Free Metrics CVSS Version Base Score Base Severity Vector String 3.1 3.6 LOW CVSS:3.1/AV:L/AC:H/PR:L/UI:N/S:U/C:L/I:N/A:L CVE-2020-7069 In PHP versions 7.2.x below 7.2.34, 7.3.x below 7.3.23 and 7.4.x below 7.4.11, when AES-CCM mode is used with openssl_encrypt() function with 12 bytes IV, only first 7 bytes of the IV is actually used. This can lead to both decreased security and incorrect encryption data. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-20 Improper Input Validation Metrics CVSS Version Base Score Base Severity Vector String 3.1 6.5 MEDIUM CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:L/A:N CVE-2015-2301 Use-after-free vulnerability in the phar_rename_archive function in phar_object.c in PHP before 5.5.22 and 5.6.x before 5.6.6 allows remote attackers to cause a denial of service or possibly have unspecified other impact via vectors that trigger an attempted renaming of a Phar archive to the name of an existing file. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-416 Use After Free Metrics CVSS Version Base Score Base Severity Vector String 3.0 9.8 CRITICAL CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H CVE-2023-0568 In PHP 8.0.X before 8.0.28, 8.1.X before 8.1.16 and 8.2.X before 8.2.3, core path resolution function allocate buffer one byte too small. When resolving paths with lengths close to system MAXPATHLEN setting, this may lead to the byte after the allocated buffer being overwritten with NUL value, which might lead to unauthorized data access or modification. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-131 Incorrect Calculation of Buffer Size Metrics CVSS Version Base Score Base Severity Vector String 3.1 8.1 HIGH CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:H/I:H/A:H CVE-2022-27458 MariaDB Server v10.6.3 and below was discovered to contain an use-after-free in the component Binary_string::free_buffer() at /sql/sql_string.h. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-416 Use After Free Metrics CVSS Version Base Score Base Severity Vector String 3.1 7.5 HIGH CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H CVE-2021-21706 In PHP versions 7.3.x below 7.3.31, 7.4.x below 7.4.24 and 8.0.x below 8.0.11, in Microsoft Windows environment, ZipArchive::extractTo may be tricked into writing a file outside target directory when extracting a ZIP file, thus potentially causing files to be created or overwritten, subject to OS permissions. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-24 Path Traversal: '../filedir' Metrics CVSS Version Base Score Base Severity Vector String 3.1 6.5 MEDIUM CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:U/C:N/I:H/A:N CVE-2022-27452 MariaDB Server v10.9 and below was discovered to contain a segmentation fault via the component sql/item_cmpfunc.cc. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-617 Reachable Assertion Metrics CVSS Version Base Score Base Severity Vector String 3.1 7.5 HIGH CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H CVE-2020-7071 In PHP versions 7.3.x below 7.3.26, 7.4.x below 7.4.14 and 8.0.0, when validating URL with functions like filter_var($url, FILTER_VALIDATE_URL), PHP will accept an URL with invalid password as valid URL. This may lead to functions that rely on URL being valid to mis-parse the URL and produce wrong data as components of the URL. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-20 Improper Input Validation Metrics CVSS Version Base Score Base Severity Vector String 3.1 5.3 MEDIUM CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:L/A:N CVE-2022-27387 MariaDB Server v10.7 and below was discovered to contain a global buffer overflow in the component decimal_bin_size, which is exploited via specially crafted SQL statements. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-120 Buffer Copy without Checking Size of Input ('Classic Buffer Overflow') Metrics CVSS Version Base Score Base Severity Vector String 3.1 7.5 HIGH CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H CVE-2022-27376 MariaDB Server v10.6.5 and below was discovered to contain an use-after-free in the component Item_args::walk_arg, which is exploited via specially crafted SQL statements. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-416 Use After Free Metrics CVSS Version Base Score Base Severity Vector String 3.1 7.5 HIGH CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H CVE-2019-11043 In PHP versions 7.1.x below 7.1.33, 7.2.x below 7.2.24 and 7.3.x below 7.3.11 in certain configurations of FPM setup it is possible to cause FPM module to write past allocated buffers into the space reserved for FCGI protocol data, thus opening the possibility of remote code execution. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-120 Buffer Copy without Checking Size of Input ('Classic Buffer Overflow') Metrics CVSS Version Base Score Base Severity Vector String 3.1 9.8 CRITICAL CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H CVE-2021-2032 Vulnerability in the MySQL Server product of Oracle MySQL (component: Information Schema). Supported versions that are affected are 5.7.32 and prior and 8.0.22 and prior. Easily exploitable vulnerability allows low privileged attacker with network access via multiple protocols to compromise MySQL Server. Successful attacks of this vulnerability can result in unauthorized read access to a subset of MySQL Server accessible data. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-20 Improper Input Validation Metrics CVSS Version Base Score Base Severity Vector String 3.1 4.3 MEDIUM CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:L/I:N/A:N CVE-2021-2007 Vulnerability in the MySQL Client product of Oracle MySQL (component: C API). Supported versions that are affected are 5.6.47 and prior, 5.7.29 and prior and 8.0.19 and prior. Difficult to exploit vulnerability allows unauthenticated attacker with network access via multiple protocols to compromise MySQL Client. Successful attacks of this vulnerability can result in unauthorized read access to a subset of MySQL Client accessible data. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-20 Improper Input Validation Metrics CVSS Version Base Score Base Severity Vector String 3.1 3.7 LOW CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:L/I:N/A:N CVE-2019-11045 In PHP versions 7.2.x below 7.2.26, 7.3.x below 7.3.13 and 7.4.0, PHP DirectoryIterator class accepts filenames with embedded \0 byte and treats them as terminating at that byte. This could lead to security vulnerabilities, e.g. in applications checking paths that the code is allowed to access. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-170 Improper Null Termination Metrics CVSS Version Base Score Base Severity Vector String 3.1 5.9 MEDIUM CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:H/I:N/A:N CVE-2022-27445 MariaDB Server v10.9 and below was discovered to contain a segmentation fault via the component sql/sql_window.cc. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-20 Improper Input Validation Metrics CVSS Version Base Score Base Severity Vector String 3.1 7.5 HIGH CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H CVE-2022-27457 MariaDB Server v10.6.3 and below was discovered to contain an use-after-free in the component my_mb_wc_latin1 at /strings/ctype-latin1.c. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-416 Use After Free Metrics CVSS Version Base Score Base Severity Vector String 3.1 7.5 HIGH CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H CVE-2022-27384 An issue in the component Item_subselect::init_expr_cache_tracker of MariaDB Server v10.6 and below was discovered to allow attackers to cause a Denial of Service (DoS) via specially crafted SQL statements. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-89 Improper Neutralization of Special Elements used in an SQL Command ('SQL Injection') Metrics CVSS Version Base Score Base Severity Vector String 3.1 7.5 HIGH CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H CVE-2022-23808 An issue was discovered in phpMyAdmin 5.1 before 5.1.2. An attacker can inject malicious code into aspects of the setup script, which can allow XSS or HTML injection. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-79 Improper Neutralization of Input During Web Page Generation ('Cross-site Scripting') Metrics CVSS Version Base Score Base Severity Vector String 3.1 6.1 MEDIUM CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:C/C:L/I:L/A:N CVE-2023-0567 In PHP 8.0.X before 8.0.28, 8.1.X before 8.1.16 and 8.2.X before 8.2.3, password_verify() function may accept some invalid Blowfish hashes as valid. If such invalid hash ever ends up in the password database, it may lead to an application allowing any password for this entry as valid. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-916 Use of Password Hash With Insufficient Computational Effort Metrics CVSS Version Base Score Base Severity Vector String 3.1 6.2 MEDIUM CVSS:3.1/AV:L/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:N CVE-2019-9025 An issue was discovered in PHP 7.3.x before 7.3.1. An invalid multibyte string supplied as an argument to the mb_split() function in ext/mbstring/php_mbregex.c can cause PHP to execute memcpy() with a negative argument, which could read and write past buffers allocated for the data. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-787 Out-of-bounds Write Metrics CVSS Version Base Score Base Severity Vector String 3.0 9.8 CRITICAL CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H CVE-2022-27379 An issue in the component Arg_comparator::compare_real_fixed of MariaDB Server v10.6.2 and below was discovered to allow attackers to cause a Denial of Service (DoS) via specially crafted SQL statements. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-89 Improper Neutralization of Special Elements used in an SQL Command ('SQL Injection') Metrics CVSS Version Base Score Base Severity Vector String 3.1 7.5 HIGH CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H CVE-2019-9637 An issue was discovered in PHP before 7.1.27, 7.2.x before 7.2.16, and 7.3.x before 7.3.3. Due to the way rename() across filesystems is implemented, it is possible that file being renamed is briefly available with wrong permissions while the rename is ongoing, thus enabling unauthorized users to access the data. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-266 Incorrect Privilege Assignment Metrics CVSS Version Base Score Base Severity Vector String 3.0 7.5 HIGH CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N CVE-2021-27928 A remote code execution issue was discovered in MariaDB 10.2 before 10.2.37, 10.3 before 10.3.28, 10.4 before 10.4.18, and 10.5 before 10.5.9; Percona Server through 2021-03-03; and the wsrep patch through 2021-03-03 for MySQL. An untrusted search path leads to eval injection, in which a database SUPER user can execute OS commands after modifying wsrep_provider and wsrep_notify_cmd. NOTE: this does not affect an Oracle product. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-94 Improper Control of Generation of Code ('Code Injection') Metrics CVSS Version Base Score Base Severity Vector String 3.1 7.2 HIGH CVSS:3.1/AV:N/AC:L/PR:H/UI:N/S:U/C:H/I:H/A:H CVE-2021-21703 In PHP versions 7.3.x up to and including 7.3.31, 7.4.x below 7.4.25 and 8.0.x below 8.0.12, when running PHP FPM SAPI with main FPM daemon process running as root and child worker processes running as lower-privileged users, it is possible for the child processes to access memory shared with the main process and write to it, modifying it in a way that would cause the root process to conduct invalid memory reads and writes, which can be used to escalate privileges from local unprivileged user to the root user. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-787 Out-of-bounds Write Metrics CVSS Version Base Score Base Severity Vector String 3.1 7 HIGH CVSS:3.1/AV:L/AC:H/PR:L/UI:N/S:U/C:H/I:H/A:H CVE-2020-2760 Vulnerability in the MySQL Server product of Oracle MySQL (component: InnoDB). Supported versions that are affected are 5.7.29 and prior and 8.0.19 and prior. Easily exploitable vulnerability allows high privileged attacker with network access via multiple protocols to compromise MySQL Server. Successful attacks of this vulnerability can result in unauthorized ability to cause a hang or frequently repeatable crash (complete DOS) of MySQL Server as well as unauthorized update, insert or delete access to some of MySQL Server accessible data. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-20 Improper Input Validation Metrics CVSS Version Base Score Base Severity Vector String 3.1 5.5 MEDIUM CVSS:3.1/AV:N/AC:L/PR:H/UI:N/S:U/C:N/I:L/A:H CVE-2021-2166 Vulnerability in the MySQL Server product of Oracle MySQL (component: Server: DML). Supported versions that are affected are 5.7.33 and prior and 8.0.23 and prior. Easily exploitable vulnerability allows high privileged attacker with network access via multiple protocols to compromise MySQL Server. Successful attacks of this vulnerability can result in unauthorized ability to cause a hang or frequently repeatable crash (complete DOS) of MySQL Server. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-20 Improper Input Validation Metrics CVSS Version Base Score Base Severity Vector String 3.1 4.9 MEDIUM CVSS:3.1/AV:N/AC:L/PR:H/UI:N/S:U/C:N/I:N/A:H CVE-2015-2787 Use-after-free vulnerability in the process_nested_data function in ext/standard/var_unserializer.re in PHP before 5.4.39, 5.5.x before 5.5.23, and 5.6.x before 5.6.7 allows remote attackers to execute arbitrary code via a crafted unserialize call that leverages use of the unset function within an __wakeup function, a related issue to CVE-2015-0231. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-416 Use After Free Metrics CVSS Version Base Score Base Severity Vector String 3.0 9.8 CRITICAL CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H CVE-2022-23807 An issue was discovered in phpMyAdmin 4.9 before 4.9.8 and 5.1 before 5.1.2. A valid user who is already authenticated to phpMyAdmin can manipulate their account to bypass two-factor authentication for future login instances. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-287 Improper Authentication Metrics CVSS Version Base Score Base Severity Vector String 3.1 4.3 MEDIUM CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:L/A:N CVE-2020-2752 Vulnerability in the MySQL Client product of Oracle MySQL (component: C API). Supported versions that are affected are 5.6.47 and prior, 5.7.27 and prior and 8.0.17 and prior. Difficult to exploit vulnerability allows low privileged attacker with network access via multiple protocols to compromise MySQL Client. Successful attacks of this vulnerability can result in unauthorized ability to cause a hang or frequently repeatable crash (complete DOS) of MySQL Client. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-20 Improper Input Validation Metrics CVSS Version Base Score Base Severity Vector String 3.1 5.3 MEDIUM CVSS:3.1/AV:N/AC:H/PR:L/UI:N/S:U/C:N/I:N/A:H CVE-2021-46666 MariaDB before 10.6.2 allows an application crash because of mishandling of a pushdown from a HAVING clause to a WHERE clause. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-617 Reachable Assertion Metrics CVSS Version Base Score Base Severity Vector String 3.1 5.5 MEDIUM CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H CVE-2020-2814 Vulnerability in the MySQL Server product of Oracle MySQL (component: InnoDB). Supported versions that are affected are 5.6.47 and prior, 5.7.28 and prior and 8.0.18 and prior. Easily exploitable vulnerability allows high privileged attacker with network access via multiple protocols to compromise MySQL Server. Successful attacks of this vulnerability can result in unauthorized ability to cause a hang or frequently repeatable crash (complete DOS) of MySQL Server. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-20 Improper Input Validation Metrics CVSS Version Base Score Base Severity Vector String 3.1 4.9 MEDIUM CVSS:3.1/AV:N/AC:L/PR:H/UI:N/S:U/C:N/I:N/A:H CVE-2020-7065 In PHP versions 7.3.x below 7.3.16 and 7.4.x below 7.4.4, while using mb_strtolower() function with UTF-32LE encoding, certain invalid strings could cause PHP to overwrite stack-allocated buffer. This could lead to memory corruption, crashes and potentially code execution. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-121 Stack-based Buffer Overflow Metrics CVSS Version Base Score Base Severity Vector String 3.1 8.8 HIGH CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H CVE-2021-21705 In PHP versions 7.3.x below 7.3.29, 7.4.x below 7.4.21 and 8.0.x below 8.0.8, when using URL validation functionality via filter_var() function with FILTER_VALIDATE_URL parameter, an URL with invalid password field can be accepted as valid. This can lead to the code incorrectly parsing the URL and potentially leading to other security implications - like contacting a wrong server or making a wrong access decision. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-20 Improper Input Validation Metrics CVSS Version Base Score Base Severity Vector String 3.1 5.3 MEDIUM CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:L/A:N CVE-2020-7062 In PHP versions 7.2.x below 7.2.28, 7.3.x below 7.3.15 and 7.4.x below 7.4.3, when using file upload functionality, if upload progress tracking is enabled, but session.upload_progress.cleanup is set to 0 (disabled), and the file upload fails, the upload procedure would try to clean up data that does not exist and encounter null pointer dereference, which would likely lead to a crash. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-476 NULL Pointer Dereference Metrics CVSS Version Base Score Base Severity Vector String 3.1 7.5 HIGH CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H CVE-2019-11039 Function iconv_mime_decode_headers() in PHP versions 7.1.x below 7.1.30, 7.2.x below 7.2.19 and 7.3.x below 7.3.6 may perform out-of-buffer read due to integer overflow when parsing MIME headers. This may lead to information disclosure or crash. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-125 Out-of-bounds Read Metrics CVSS Version Base Score Base Severity Vector String 3.1 9.1 CRITICAL CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:H CVE-2019-11035 When processing certain files, PHP EXIF extension in versions 7.1.x below 7.1.28, 7.2.x below 7.2.17 and 7.3.x below 7.3.4 can be caused to read past allocated buffer in exif_iif_add_value function. This may lead to information disclosure or crash. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-125 Out-of-bounds Read Metrics CVSS Version Base Score Base Severity Vector String 3.1 9.1 CRITICAL CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:H CVE-2022-27447 MariaDB Server v10.9 and below was discovered to contain a use-after-free via the component Binary_string::free_buffer() at /sql/sql_string.h. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-416 Use After Free Metrics CVSS Version Base Score Base Severity Vector String 3.1 7.5 HIGH CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H CVE-2019-11046 In PHP versions 7.2.x below 7.2.26, 7.3.x below 7.3.13 and 7.4.0, PHP bcmath extension functions on some systems, including Windows, can be tricked into reading beyond the allocated space by supplying it with string containing characters that are identified as numeric by the OS but aren't ASCII numbers. This can read to disclosure of the content of some memory locations. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-125 Out-of-bounds Read Metrics CVSS Version Base Score Base Severity Vector String 3.1 5.3 MEDIUM CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:N CVE-2022-27446 MariaDB Server v10.9 and below was discovered to contain a segmentation fault via the component sql/item_cmpfunc.h. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-617 Reachable Assertion Metrics CVSS Version Base Score Base Severity Vector String 3.1 7.5 HIGH CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H CVE-2022-27386 MariaDB Server v10.7 and below was discovered to contain a segmentation fault via the component sql/sql_class.cc. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-89 Improper Neutralization of Special Elements used in an SQL Command ('SQL Injection') Metrics CVSS Version Base Score Base Severity Vector String 3.1 7.5 HIGH CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H CVE-2019-9639 An issue was discovered in the EXIF component in PHP before 7.1.27, 7.2.x before 7.2.16, and 7.3.x before 7.3.3. There is an uninitialized read in exif_process_IFD_in_MAKERNOTE because of mishandling the data_len variable. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-909 Missing Initialization of Resource Metrics CVSS Version Base Score Base Severity Vector String 3.1 7.5 HIGH CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N CVE-2019-11042 When PHP EXIF extension is parsing EXIF information from an image, e.g. via exif_read_data() function, in PHP versions 7.1.x below 7.1.31, 7.2.x below 7.2.21 and 7.3.x below 7.3.8 it is possible to supply it with data what will cause it to read past the allocated buffer. This may lead to information disclosure or crash. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-125 Out-of-bounds Read Metrics CVSS Version Base Score Base Severity Vector String 3.1 7.1 HIGH CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:U/C:L/I:N/A:H CVE-2022-27385 An issue in the component Used_tables_and_const_cache::used_tables_and_const_cache_join of MariaDB Server v10.7 and below was discovered to allow attackers to cause a Denial of Service (DoS) via specially crafted SQL statements. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-89 Improper Neutralization of Special Elements used in an SQL Command ('SQL Injection') Metrics CVSS Version Base Score Base Severity Vector String 3.1 7.5 HIGH CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H CVE-2020-7059 When using fgetss() function to read data with stripping tags, in PHP versions 7.2.x below 7.2.27, 7.3.x below 7.3.14 and 7.4.x below 7.4.2 it is possible to supply data that will cause this function to read past the allocated buffer. This may lead to information disclosure or crash. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-125 Out-of-bounds Read Metrics CVSS Version Base Score Base Severity Vector String 3.1 9.1 CRITICAL CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:H CVE-2020-7070 In PHP versions 7.2.x below 7.2.34, 7.3.x below 7.3.23 and 7.4.x below 7.4.11, when PHP is processing incoming HTTP cookie values, the cookie names are url-decoded. This may lead to cookies with prefixes like __Host confused with cookies that decode to such prefix, thus leading to an attacker being able to forge cookie which is supposed to be secure. See also CVE-2020-8184 for more information. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-20 Improper Input Validation Metrics CVSS Version Base Score Base Severity Vector String 3.1 5.3 MEDIUM CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:L/A:N CVE-2022-32091 MariaDB v10.7 was discovered to contain an use-after-poison in in __interceptor_memset at /libsanitizer/sanitizer_common/sanitizer_common_interceptors.inc. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-416 Use After Free Metrics CVSS Version Base Score Base Severity Vector String 3.1 7.5 HIGH CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H CVE-2015-2348 The move_uploaded_file implementation in ext/standard/basic_functions.c in PHP before 5.4.39, 5.5.x before 5.5.23, and 5.6.x before 5.6.7 truncates a pathname upon encountering a \x00 character, which allows remote attackers to bypass intended extension restrictions and create files with unexpected names via a crafted second argument. NOTE: this vulnerability exists because of an incomplete fix for CVE-2006-7243. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-626 Null Byte Interaction Error (Poison Null Byte) Metrics CVSS Version Base Score Base Severity Vector String 3.0 9.8 CRITICAL CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H CVE-2019-9020 An issue was discovered in PHP before 5.6.40, 7.x before 7.1.26, 7.2.x before 7.2.14, and 7.3.x before 7.3.1. Invalid input to the function xmlrpc_decode() can lead to an invalid memory access (heap out of bounds read or read after free). This is related to xml_elem_parse_buf in ext/xmlrpc/libxmlrpc/xml_element.c. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-125 Out-of-bounds Read Metrics CVSS Version Base Score Base Severity Vector String 3.0 9.8 CRITICAL CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H CVE-2021-35604 Vulnerability in the MySQL Server product of Oracle MySQL (component: InnoDB). Supported versions that are affected are 5.7.35 and prior and 8.0.26 and prior. Easily exploitable vulnerability allows high privileged attacker with network access via multiple protocols to compromise MySQL Server. Successful attacks of this vulnerability can result in unauthorized ability to cause a hang or frequently repeatable crash (complete DOS) of MySQL Server as well as unauthorized update, insert or delete access to some of MySQL Server accessible data. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-20 Improper Input Validation Metrics CVSS Version Base Score Base Severity Vector String 3.1 5.5 MEDIUM CVSS:3.1/AV:N/AC:L/PR:H/UI:N/S:U/C:N/I:L/A:H CVE-2022-27444 MariaDB Server v10.9 and below was discovered to contain a segmentation fault via the component sql/item_subselect.cc. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-89 Improper Neutralization of Special Elements used in an SQL Command ('SQL Injection') Metrics CVSS Version Base Score Base Severity Vector String 3.1 7.5 HIGH CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H CVE-2018-14883 An issue was discovered in PHP before 5.6.37, 7.0.x before 7.0.31, 7.1.x before 7.1.20, and 7.2.x before 7.2.8. An Integer Overflow leads to a heap-based buffer over-read in exif_thumbnail_extract of exif.c. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-125 Out-of-bounds Read Metrics CVSS Version Base Score Base Severity Vector String 3.0 7.5 HIGH CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H CVE-2014-9705 Heap-based buffer overflow in the enchant_broker_request_dict function in ext/enchant/enchant.c in PHP before 5.4.38, 5.5.x before 5.5.22, and 5.6.x before 5.6.6 allows remote attackers to execute arbitrary code via vectors that trigger creation of multiple dictionaries. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-119 Improper Restriction of Operations within the Bounds of a Memory Buffer Metrics CVSS Version Base Score Base Severity Vector String 3.0 9.8 CRITICAL CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H CVE-2020-7064 In PHP versions 7.2.x below 7.2.9, 7.3.x below 7.3.16 and 7.4.x below 7.4.4, while parsing EXIF data with exif_read_data() function, it is possible for malicious data to cause PHP to read one byte of uninitialized memory. This could potentially lead to information disclosure or crash. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-125 Out-of-bounds Read Metrics CVSS Version Base Score Base Severity Vector String 3.1 5.4 MEDIUM CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:U/C:L/I:N/A:L CVE-2022-27382 MariaDB Server v10.7 and below was discovered to contain a segmentation fault via the component Item_field::used_tables/update_depend_map_for_order. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-617 Reachable Assertion Metrics CVSS Version Base Score Base Severity Vector String 3.1 7.5 HIGH CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H CVE-2020-7063 In PHP versions 7.2.x below 7.2.28, 7.3.x below 7.3.15 and 7.4.x below 7.4.3, when creating PHAR archive using PharData::buildFromIterator() function, the files are added with default permissions (0666, or all access) even if the original files on the filesystem were with more restrictive permissions. This may result in files having more lax permissions than intended when such archive is extracted. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-281 Improper Preservation of Permissions Metrics CVSS Version Base Score Base Severity Vector String 3.1 5.3 MEDIUM CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:L/A:N CVE-2021-2372 Vulnerability in the MySQL Server product of Oracle MySQL (component: InnoDB). Supported versions that are affected are 5.7.34 and prior and 8.0.25 and prior. Difficult to exploit vulnerability allows high privileged attacker with network access via multiple protocols to compromise MySQL Server. Successful attacks of this vulnerability can result in unauthorized ability to cause a hang or frequently repeatable crash (complete DOS) of MySQL Server. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-20 Improper Input Validation Metrics CVSS Version Base Score Base Severity Vector String 3.1 4.4 MEDIUM CVSS:3.1/AV:N/AC:H/PR:H/UI:N/S:U/C:N/I:N/A:H CVE-2019-9021 An issue was discovered in PHP before 5.6.40, 7.x before 7.1.26, 7.2.x before 7.2.14, and 7.3.x before 7.3.1. A heap-based buffer over-read in PHAR reading functions in the PHAR extension may allow an attacker to read allocated or unallocated memory past the actual data when trying to parse the file name, a different vulnerability than CVE-2018-20783. This is related to phar_detect_phar_fname_ext in ext/phar/phar.c. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-125 Out-of-bounds Read Metrics CVSS Version Base Score Base Severity Vector String 3.0 9.8 CRITICAL CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H CVE-2018-14851 exif_process_IFD_in_MAKERNOTE in ext/exif/exif.c in PHP before 5.6.37, 7.0.x before 7.0.31, 7.1.x before 7.1.20, and 7.2.x before 7.2.8 allows remote attackers to cause a denial of service (out-of-bounds read and application crash) via a crafted JPEG file. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-125 Out-of-bounds Read Metrics CVSS Version Base Score Base Severity Vector String 3.0 5.5 MEDIUM CVSS:3.0/AV:L/AC:L/PR:N/UI:R/S:U/C:N/I:N/A:H CVE-2022-27448 There is an Assertion failure in MariaDB Server v10.9 and below via 'node->pcur->rel_pos == BTR_PCUR_ON' at /row/row0mysql.cc. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-617 Reachable Assertion Metrics CVSS Version Base Score Base Severity Vector String 3.1 7.5 HIGH CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H CVE-2021-46663 MariaDB through 10.5.13 allows a ha_maria::extra application crash via certain SELECT statements. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-20 Improper Input Validation Metrics CVSS Version Base Score Base Severity Vector String 3.1 5.5 MEDIUM CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H CVE-2021-2180 Vulnerability in the MySQL Server product of Oracle MySQL (component: InnoDB). Supported versions that are affected are 5.7.33 and prior and 8.0.23 and prior. Easily exploitable vulnerability allows high privileged attacker with network access via multiple protocols to compromise MySQL Server. Successful attacks of this vulnerability can result in unauthorized ability to cause a hang or frequently repeatable crash (complete DOS) of MySQL Server. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-20 Improper Input Validation Metrics CVSS Version Base Score Base Severity Vector String 3.1 4.9 MEDIUM CVSS:3.1/AV:N/AC:L/PR:H/UI:N/S:U/C:N/I:N/A:H CVE-2014-9709 The GetCode_ function in gd_gif_in.c in GD 2.1.1 and earlier, as used in PHP before 5.5.21 and 5.6.x before 5.6.5, allows remote attackers to cause a denial of service (buffer over-read and application crash) via a crafted GIF image that is improperly handled by the gdImageCreateFromGif function. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-119 Improper Restriction of Operations within the Bounds of a Memory Buffer Metrics CVSS Version Base Score Base Severity Vector String 3.0 9.1 CRITICAL CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:H CVE-2023-25690 Some mod_proxy configurations on Apache HTTP Server versions 2.4.0 through 2.4.55 allow a HTTP Request Smuggling attack. Configurations are affected when mod_proxy is enabled along with some form of RewriteRule or ProxyPassMatch in which a non-specific pattern matches some portion of the user-supplied request-target (URL) data and is then re-inserted into the proxied request-target using variable substitution. For example, something like: RewriteEngine on RewriteRule "^/here/(.*)" "http://example.com:8080/elsewhere?$1"; [P] ProxyPassReverse /here/ http://example.com:8080/Request splitting/smuggling could result in bypass of access controls in the proxy server, proxying unintended URLs to existing origin servers, and cache poisoning. Users are recommended to update to at least version 2.4.56 of Apache HTTP Server. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-444 Inconsistent Interpretation of HTTP Requests ('HTTP Request/Response Smuggling') Metrics CVSS Version Base Score Base Severity Vector String 3.1 9.8 CRITICAL CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H CVE-2022-32082 MariaDB v10.5 to v10.7 was discovered to contain an assertion failure at table->get_ref_count() == 0 in dict0dict.cc. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-617 Reachable Assertion Metrics CVSS Version Base Score Base Severity Vector String 3.1 7.5 HIGH CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H CVE-2022-31629 In PHP versions before 7.4.31, 8.0.24 and 8.1.11, the vulnerability enables network and same-site attackers to set a standard insecure cookie in the victim's browser which is treated as a `__Host-` or `__Secure-` cookie by PHP applications. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-20 Improper Input Validation Metrics CVSS Version Base Score Base Severity Vector String 3.1 6.5 MEDIUM CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:U/C:N/I:H/A:N CVE-2019-9022 An issue was discovered in PHP 7.x before 7.1.26, 7.2.x before 7.2.14, and 7.3.x before 7.3.2. dns_get_record misparses a DNS response, which can allow a hostile DNS server to cause PHP to misuse memcpy, leading to read operations going past the buffer allocated for DNS data. This affects php_parserr in ext/standard/dns.c for DNS_CAA and DNS_ANY queries. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-125 Out-of-bounds Read Metrics CVSS Version Base Score Base Severity Vector String 3.0 7.5 HIGH CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N CVE-2016-3078 Multiple integer overflows in php_zip.c in the zip extension in PHP before 7.0.6 allow remote attackers to cause a denial of service (heap-based buffer overflow and application crash) or possibly have unspecified other impact via a crafted call to (1) getFromIndex or (2) getFromName in the ZipArchive class. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-190 Integer Overflow or Wraparound Metrics CVSS Version Base Score Base Severity Vector String 3.1 9.8 CRITICAL CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H CVE-2023-0662 In PHP 8.0.X before 8.0.28, 8.1.X before 8.1.16 and 8.2.X before 8.2.3, excessive number of parts in HTTP form upload can cause high resource consumption and excessive number of log entries. This can cause denial of service on the affected server by exhausting CPU resources or disk space. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-400 Uncontrolled Resource Consumption Metrics CVSS Version Base Score Base Severity Vector String 3.1 7.5 HIGH CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H CVE-2021-2022 Vulnerability in the MySQL Server product of Oracle MySQL (component: InnoDB). Supported versions that are affected are 5.6.50 and prior, 5.7.32 and prior and 8.0.22 and prior. Difficult to exploit vulnerability allows high privileged attacker with network access via multiple protocols to compromise MySQL Server. Successful attacks of this vulnerability can result in unauthorized ability to cause a hang or frequently repeatable crash (complete DOS) of MySQL Server. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-20 Improper Input Validation Metrics CVSS Version Base Score Base Severity Vector String 3.1 4.4 MEDIUM CVSS:3.1/AV:N/AC:H/PR:H/UI:N/S:U/C:N/I:N/A:H CVE-2022-32089 MariaDB v10.5 to v10.7 was discovered to contain a segmentation fault via the component st_select_lex_unit::exclude_level. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-229 Improper Handling of Values Metrics CVSS Version Base Score Base Severity Vector String 3.1 7.5 HIGH CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H CVE-2019-11048 In PHP versions 7.2.x below 7.2.31, 7.3.x below 7.3.18 and 7.4.x below 7.4.6, when HTTP file uploads are allowed, supplying overly long filenames or field names could lead PHP engine to try to allocate oversized memory storage, hit the memory limit and stop processing the request, without cleaning up temporary files created by upload request. This potentially could lead to accumulation of uncleaned temporary files exhausting the disk space on the target server. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-400 Uncontrolled Resource Consumption Metrics CVSS Version Base Score Base Severity Vector String 3.1 5.3 MEDIUM CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:L CVE-2021-46669 MariaDB through 10.5.9 allows attackers to trigger a convert_const_to_int use-after-free when the BIGINT data type is used. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-416 Use After Free Metrics CVSS Version Base Score Base Severity Vector String 3.1 7.5 HIGH CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H CVE-2019-11047 When PHP EXIF extension is parsing EXIF information from an image, e.g. via exif_read_data() function, in PHP versions 7.2.x below 7.2.26, 7.3.x below 7.3.13 and 7.4.0 it is possible to supply it with data what will cause it to read past the allocated buffer. This may lead to information disclosure or crash. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-125 Out-of-bounds Read Metrics CVSS Version Base Score Base Severity Vector String 3.1 6.5 MEDIUM CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:L CVE-2022-27383 MariaDB Server v10.6 and below was discovered to contain an use-after-free in the component my_strcasecmp_8bit, which is exploited via specially crafted SQL statements. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-416 Use After Free Metrics CVSS Version Base Score Base Severity Vector String 3.1 7.5 HIGH CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H CVE-2021-46667 MariaDB before 10.6.5 has a sql_lex.cc integer overflow, leading to an application crash. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-190 Integer Overflow or Wraparound Metrics CVSS Version Base Score Base Severity Vector String 3.1 5.5 MEDIUM CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H CVE-2022-32087 MariaDB v10.2 to v10.7 was discovered to contain a segmentation fault via the component Item_args::walk_args. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-229 Improper Handling of Values Metrics CVSS Version Base Score Base Severity Vector String 3.1 7.5 HIGH CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H CVE-2022-36760 Inconsistent Interpretation of HTTP Requests ('HTTP Request Smuggling') vulnerability in mod_proxy_ajp of Apache HTTP Server allows an attacker to smuggle requests to the AJP server it forwards requests to. This issue affects Apache HTTP Server Apache HTTP Server 2.4 version 2.4.54 and prior versions. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-444 Inconsistent Interpretation of HTTP Requests ('HTTP Request/Response Smuggling') Metrics CVSS Version Base Score Base Severity Vector String 3.1 9 CRITICAL CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:C/C:H/I:H/A:H CVE-2020-7060 When using certain mbstring functions to convert multibyte encodings, in PHP versions 7.2.x below 7.2.27, 7.3.x below 7.3.14 and 7.4.x below 7.4.2 it is possible to supply data that will cause function mbfl_filt_conv_big5_wchar to read past the allocated buffer. This may lead to information disclosure or crash. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-125 Out-of-bounds Read Metrics CVSS Version Base Score Base Severity Vector String 3.1 9.1 CRITICAL CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:H CVE-2018-17082 The Apache2 component in PHP before 5.6.38, 7.0.x before 7.0.32, 7.1.x before 7.1.22, and 7.2.x before 7.2.10 allows XSS via the body of a "Transfer-Encoding: chunked" request, because the bucket brigade is mishandled in the php_handler function in sapi/apache2handler/sapi_apache2.c. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-79 Improper Neutralization of Input During Web Page Generation ('Cross-site Scripting') Metrics CVSS Version Base Score Base Severity Vector String 3.0 6.1 MEDIUM CVSS:3.0/AV:N/AC:L/PR:N/UI:R/S:C/C:L/I:L/A:N CVE-2019-9640 An issue was discovered in the EXIF component in PHP before 7.1.27, 7.2.x before 7.2.16, and 7.3.x before 7.3.3. There is an Invalid Read in exif_process_SOFn. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-125 Out-of-bounds Read Metrics CVSS Version Base Score Base Severity Vector String 3.1 7.5 HIGH CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N CVE-2021-46661 MariaDB through 10.5.9 allows an application crash in find_field_in_tables and find_order_in_list via an unused common table expression (CTE). View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-20 Improper Input Validation Metrics CVSS Version Base Score Base Severity Vector String 3.1 5.5 MEDIUM CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H CVE-2019-11034 When processing certain files, PHP EXIF extension in versions 7.1.x below 7.1.28, 7.2.x below 7.2.17 and 7.3.x below 7.3.4 can be caused to read past allocated buffer in exif_process_IFD_TAG function. This may lead to information disclosure or crash. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-125 Out-of-bounds Read Metrics CVSS Version Base Score Base Severity Vector String 3.1 9.1 CRITICAL CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:H CVE-2022-27456 MariaDB Server v10.6.3 and below was discovered to contain an use-after-free in the component VDec::VDec at /sql/sql_type.cc. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-416 Use After Free Metrics CVSS Version Base Score Base Severity Vector String 3.1 7.5 HIGH CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H CVE-2020-7061 In PHP versions 7.3.x below 7.3.15 and 7.4.x below 7.4.3, while extracting PHAR files on Windows using phar extension, certain content inside PHAR file could lead to one-byte read past the allocated buffer. This could potentially lead to information disclosure or crash. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-125 Out-of-bounds Read Metrics CVSS Version Base Score Base Severity Vector String 3.1 9.1 CRITICAL CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:H CVE-2022-27455 MariaDB Server v10.6.3 and below was discovered to contain an use-after-free in the component my_wildcmp_8bit_impl at /strings/ctype-simple.c. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-416 Use After Free Metrics CVSS Version Base Score Base Severity Vector String 3.1 7.5 HIGH CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H CVE-2021-2144 Vulnerability in the MySQL Server product of Oracle MySQL (component: Server: Parser). Supported versions that are affected are 5.7.29 and prior and 8.0.19 and prior. Easily exploitable vulnerability allows high privileged attacker with network access via multiple protocols to compromise MySQL Server. Successful attacks of this vulnerability can result in takeover of MySQL Server. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-20 Improper Input Validation Metrics CVSS Version Base Score Base Severity Vector String 3.1 7.2 HIGH CVSS:3.1/AV:N/AC:L/PR:H/UI:N/S:U/C:H/I:H/A:H CVE-2021-2154 Vulnerability in the MySQL Server product of Oracle MySQL (component: Server: DML). Supported versions that are affected are 5.7.33 and prior. Easily exploitable vulnerability allows high privileged attacker with network access via multiple protocols to compromise MySQL Server. Successful attacks of this vulnerability can result in unauthorized ability to cause a hang or frequently repeatable crash (complete DOS) of MySQL Server. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-20 Improper Input Validation Metrics CVSS Version Base Score Base Severity Vector String 3.1 4.9 MEDIUM CVSS:3.1/AV:N/AC:L/PR:H/UI:N/S:U/C:N/I:N/A:H CVE-2022-21595 Vulnerability in the MySQL Server product of Oracle MySQL (component: C API). Supported versions that are affected are 5.7.36 and prior and 8.0.27 and prior. Difficult to exploit vulnerability allows high privileged attacker with network access via multiple protocols to compromise MySQL Server. Successful attacks of this vulnerability can result in unauthorized ability to cause a hang or frequently repeatable crash (complete DOS) of MySQL Server. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-20 Improper Input Validation Metrics CVSS Version Base Score Base Severity Vector String 3.1 4.4 MEDIUM CVSS:3.1/AV:N/AC:H/PR:H/UI:N/S:U/C:N/I:N/A:H CVE-2019-11040 When PHP EXIF extension is parsing EXIF information from an image, e.g. via exif_read_data() function, in PHP versions 7.1.x below 7.1.30, 7.2.x below 7.2.19 and 7.3.x below 7.3.6 it is possible to supply it with data what will cause it to read past the allocated buffer. This may lead to information disclosure or crash. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-125 Out-of-bounds Read Metrics CVSS Version Base Score Base Severity Vector String 3.1 9.1 CRITICAL CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:H CVE-2021-2389 Vulnerability in the MySQL Server product of Oracle MySQL (component: InnoDB). Supported versions that are affected are 5.7.34 and prior and 8.0.25 and prior. Difficult to exploit vulnerability allows unauthenticated attacker with network access via multiple protocols to compromise MySQL Server. Successful attacks of this vulnerability can result in unauthorized ability to cause a hang or frequently repeatable crash (complete DOS) of MySQL Server. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-20 Improper Input Validation Metrics CVSS Version Base Score Base Severity Vector String 3.1 5.9 MEDIUM CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:N/I:N/A:H CVE-2023-27522 HTTP Response Smuggling vulnerability in Apache HTTP Server via mod_proxy_uwsgi. This issue affects Apache HTTP Server: from 2.4.30 through 2.4.55. Special characters in the origin response header can truncate/split the response forwarded to the client. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-444 Inconsistent Interpretation of HTTP Requests ('HTTP Request/Response Smuggling') Metrics CVSS Version Base Score Base Severity Vector String 3.1 7.5 HIGH CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:N CVE-2020-2812 Vulnerability in the MySQL Server product of Oracle MySQL (component: Server: Stored Procedure). Supported versions that are affected are 5.6.47 and prior, 5.7.29 and prior and 8.0.19 and prior. Easily exploitable vulnerability allows high privileged attacker with network access via multiple protocols to compromise MySQL Server. Successful attacks of this vulnerability can result in unauthorized ability to cause a hang or frequently repeatable crash (complete DOS) of MySQL Server. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-20 Improper Input Validation Metrics CVSS Version Base Score Base Severity Vector String 3.1 4.9 MEDIUM CVSS:3.1/AV:N/AC:L/PR:H/UI:N/S:U/C:N/I:N/A:H CVE-2021-46665 MariaDB through 10.5.9 allows a sql_parse.cc application crash because of incorrect used_tables expectations. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-20 Improper Input Validation Metrics CVSS Version Base Score Base Severity Vector String 3.1 5.5 MEDIUM CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H CVE-2022-32086 MariaDB v10.4 to v10.8 was discovered to contain a segmentation fault via the component Item_field::fix_outer_field. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-229 Improper Handling of Values Metrics CVSS Version Base Score Base Severity Vector String 3.1 7.5 HIGH CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H CVE-2022-32085 MariaDB v10.2 to v10.7 was discovered to contain a segmentation fault via the component Item_func_in::cleanup/Item::cleanup_processor. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-229 Improper Handling of Values Metrics CVSS Version Base Score Base Severity Vector String 3.1 7.5 HIGH CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H CVE-2021-21704 In PHP versions 7.3.x below 7.3.29, 7.4.x below 7.4.21 and 8.0.x below 8.0.8, when using Firebird PDO driver extension, a malicious database server could cause crashes in various database functions, such as getAttribute(), execute(), fetch() and others by returning invalid response data that is not parsed correctly by the driver. This can result in crashes, denial of service or potentially memory corruption. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-125 Out-of-bounds Read Metrics CVSS Version Base Score Base Severity Vector String 3.1 5.9 MEDIUM CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:N/I:N/A:H CVE-2020-7066 In PHP versions 7.2.x below 7.2.29, 7.3.x below 7.3.16 and 7.4.x below 7.4.4, while using get_headers() with user-supplied URL, if the URL contains zero (\0) character, the URL will be silently truncated at it. This may cause some software to make incorrect assumptions about the target of the get_headers() and possibly send some information to a wrong server. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-170 Improper Null Termination Metrics CVSS Version Base Score Base Severity Vector String 3.1 4.3 MEDIUM CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:U/C:L/I:N/A:N CVE-2022-31628 In PHP versions before 7.4.31, 8.0.24 and 8.1.11, the phar uncompressor code would recursively uncompress "quines" gzip files, resulting in an infinite loop. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-674 Uncontrolled Recursion Metrics CVSS Version Base Score Base Severity Vector String 3.1 5.5 MEDIUM CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H CVE-2021-46662 MariaDB through 10.5.9 allows a set_var.cc application crash via certain uses of an UPDATE statement in conjunction with a nested subquery. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-20 Improper Input Validation Metrics CVSS Version Base Score Base Severity Vector String 3.1 5.5 MEDIUM CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H CVE-2016-5385 PHP through 7.0.8 does not attempt to address RFC 3875 section 4.1.18 namespace conflicts and therefore does not protect applications from the presence of untrusted client data in the HTTP_PROXY environment variable, which might allow remote attackers to redirect an application's outbound HTTP traffic to an arbitrary proxy server via a crafted Proxy header in an HTTP request, as demonstrated by (1) an application that makes a getenv('HTTP_PROXY') call or (2) a CGI configuration of PHP, aka an "httpoxy" issue. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-601 URL Redirection to Untrusted Site ('Open Redirect') Metrics CVSS Version Base Score Base Severity Vector String 3.1 8.1 HIGH CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:H/I:H/A:H CVE-2022-37436 Prior to Apache HTTP Server 2.4.55, a malicious backend can cause the response headers to be truncated early, resulting in some headers being incorporated into the response body. If the later headers have any security purpose, they will not be interpreted by the client. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-113 Improper Neutralization of CRLF Sequences in HTTP Headers ('HTTP Request/Response Splitting') Metrics CVSS Version Base Score Base Severity Vector String 3.1 5.3 MEDIUM CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:L/A:N CVE-2013-6501 The default soap.wsdl_cache_dir setting in (1) php.ini-production and (2) php.ini-development in PHP through 5.6.7 specifies the /tmp directory, which makes it easier for local users to conduct WSDL injection attacks by creating a file under /tmp with a predictable filename that is used by the get_sdl function in ext/soap/php_sdl.c. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-74 Improper Neutralization of Special Elements in Output Used by a Downstream Component ('Injection') Metrics CVSS Version Base Score Base Severity Vector String 3.0 8.8 HIGH CVSS:3.0/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H CVE-2021-21702 In PHP versions 7.3.x below 7.3.27, 7.4.x below 7.4.15 and 8.0.x below 8.0.2, when using SOAP extension to connect to a SOAP server, a malicious SOAP server could return malformed XML data as a response that would cause PHP to access a null pointer and thus cause a crash. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-476 NULL Pointer Dereference Metrics CVSS Version Base Score Base Severity Vector String 3.1 7.5 HIGH CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H CVE-2019-9024 An issue was discovered in PHP before 5.6.40, 7.x before 7.1.26, 7.2.x before 7.2.14, and 7.3.x before 7.3.1. xmlrpc_decode() can allow a hostile XMLRPC server to cause PHP to read memory outside of allocated areas in base64_decode_xmlrpc in ext/xmlrpc/libxmlrpc/base64.c. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-125 Out-of-bounds Read Metrics CVSS Version Base Score Base Severity Vector String 3.0 7.5 HIGH CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N CVE-2019-9023 An issue was discovered in PHP before 5.6.40, 7.x before 7.1.26, 7.2.x before 7.2.14, and 7.3.x before 7.3.1. A number of heap-based buffer over-read instances are present in mbstring regular expression functions when supplied with invalid multibyte data. These occur in ext/mbstring/oniguruma/regcomp.c, ext/mbstring/oniguruma/regexec.c, ext/mbstring/oniguruma/regparse.c, ext/mbstring/oniguruma/enc/unicode.c, and ext/mbstring/oniguruma/src/utf32_be.c when a multibyte regular expression pattern contains invalid multibyte sequences. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-125 Out-of-bounds Read Metrics CVSS Version Base Score Base Severity Vector String 3.0 9.8 CRITICAL CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H CVE-2022-27449 MariaDB Server v10.9 and below was discovered to contain a segmentation fault via the component sql/item_func.cc:148. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-617 Reachable Assertion Metrics CVSS Version Base Score Base Severity Vector String 3.1 7.5 HIGH CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H CVE-2021-46664 MariaDB through 10.5.9 allows an application crash in sub_select_postjoin_aggr for a NULL value of aggr. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-476 NULL Pointer Dereference Metrics CVSS Version Base Score Base Severity Vector String 3.1 5.5 MEDIUM CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H CVE-2019-11050 When PHP EXIF extension is parsing EXIF information from an image, e.g. via exif_read_data() function, in PHP versions 7.2.x below 7.2.26, 7.3.x below 7.3.13 and 7.4.0 it is possible to supply it with data what will cause it to read past the allocated buffer. This may lead to information disclosure or crash. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-125 Out-of-bounds Read Metrics CVSS Version Base Score Base Severity Vector String 3.1 6.5 MEDIUM CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:L CVE-2021-21708 In PHP versions 7.4.x below 7.4.28, 8.0.x below 8.0.16, and 8.1.x below 8.1.3, when using filter functions with FILTER_VALIDATE_FLOAT filter and min/max limits, if the filter fails, there is a possibility to trigger use of allocated memory after free, which can result it crashes, and potentially in overwrite of other memory chunks and RCE. This issue affects: code that uses FILTER_VALIDATE_FLOAT with min/max limits. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-416 Use After Free Metrics CVSS Version Base Score Base Severity Vector String 3.1 9.8 CRITICAL CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H CVE-2022-31625 In PHP versions 7.4.x below 7.4.30, 8.0.x below 8.0.20, and 8.1.x below 8.1.7, when using Postgres database extension, supplying invalid parameters to the parametrized query may lead to PHP attempting to free memory using uninitialized data as pointers. This could lead to RCE vulnerability or denial of service. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-590 Free of Memory not on the Heap Metrics CVSS Version Base Score Base Severity Vector String 3.1 8.1 HIGH CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:H/I:H/A:H CVE-2022-32081 MariaDB v10.4 to v10.7 was discovered to contain an use-after-poison in prepare_inplace_add_virtual at /storage/innobase/handler/handler0alter.cc. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-416 Use After Free Metrics CVSS Version Base Score Base Severity Vector String 3.1 7.5 HIGH CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H CVE-2022-27378 An issue in the component Create_tmp_table::finalize of MariaDB Server v10.7 and below was discovered to allow attackers to cause a Denial of Service (DoS) via specially crafted SQL statements. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-89 Improper Neutralization of Special Elements used in an SQL Command ('SQL Injection') Metrics CVSS Version Base Score Base Severity Vector String 3.1 7.5 HIGH CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H CVE-2006-20001 A carefully crafted If: request header can cause a memory read, or write of a single zero byte, in a pool (heap) memory location beyond the header value sent. This could cause the process to crash. This issue affects Apache HTTP Server 2.4.54 and earlier. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-787 Out-of-bounds Write Metrics CVSS Version Base Score Base Severity Vector String 3.1 7.5 HIGH CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H CVE-2018-19935 ext/imap/php_imap.c in PHP 5.x and 7.x before 7.3.0 allows remote attackers to cause a denial of service (NULL pointer dereference and application crash) via an empty string in the message argument to the imap_mail function. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-476 NULL Pointer Dereference Metrics CVSS Version Base Score Base Severity Vector String 3.1 7.5 HIGH CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H CVE-2022-4900 A vulnerability was found in PHP where setting the environment variable PHP_CLI_SERVER_WORKERS to a large value leads to a heap buffer overflow. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-119 Improper Restriction of Operations within the Bounds of a Memory Buffer Metrics CVSS Version Base Score Base Severity Vector String 3.1 5.5 MEDIUM CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H CVE-2018-12882 exif_read_from_impl in ext/exif/exif.c in PHP 7.2.x through 7.2.7 allows attackers to trigger a use-after-free (in exif_read_from_file) because it closes a stream that it is not responsible for closing. The vulnerable code is reachable through the PHP exif_read_data function. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-416 Use After Free Metrics CVSS Version Base Score Base Severity Vector String 3.0 9.8 CRITICAL CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H CVE-2019-9641 An issue was discovered in the EXIF component in PHP before 7.1.27, 7.2.x before 7.2.16, and 7.3.x before 7.3.3. There is an uninitialized read in exif_process_IFD_in_TIFF. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-908 Use of Uninitialized Resource Metrics CVSS Version Base Score Base Severity Vector String 3.1 9.8 CRITICAL CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H CVE-2022-27380 An issue in the component my_decimal::operator= of MariaDB Server v10.6.3 and below was discovered to allow attackers to cause a Denial of Service (DoS) via specially crafted SQL statements. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-89 Improper Neutralization of Special Elements used in an SQL Command ('SQL Injection') Metrics CVSS Version Base Score Base Severity Vector String 3.1 7.5 HIGH CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H CVE-2022-27381 An issue in the component Field::set_default of MariaDB Server v10.6 and below was discovered to allow attackers to cause a Denial of Service (DoS) via specially crafted SQL statements. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-89 Improper Neutralization of Special Elements used in an SQL Command ('SQL Injection') Metrics CVSS Version Base Score Base Severity Vector String 3.1 7.5 HIGH CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H CVE-2021-21707 In PHP versions 7.3.x below 7.3.33, 7.4.x below 7.4.26 and 8.0.x below 8.0.13, certain XML parsing functions, like simplexml_load_file(), URL-decode the filename passed to them. If that filename contains URL-encoded NUL character, this may cause the function to interpret this as the end of the filename, thus interpreting the filename differently from what the user intended, which may lead it to reading a different file than intended. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-159 Improper Handling of Invalid Use of Special Elements Metrics CVSS Version Base Score Base Severity Vector String 3.1 5.3 MEDIUM CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:N CVE-2022-27451 MariaDB Server v10.9 and below was discovered to contain a segmentation fault via the component sql/field_conv.cc. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-1173 Improper Use of Validation Framework Metrics CVSS Version Base Score Base Severity Vector String 3.1 7.5 HIGH CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H CVE-2020-2780 Vulnerability in the MySQL Server product of Oracle MySQL (component: Server: DML). Supported versions that are affected are 5.6.47 and prior, 5.7.29 and prior and 8.0.19 and prior. Easily exploitable vulnerability allows low privileged attacker with network access via multiple protocols to compromise MySQL Server. Successful attacks of this vulnerability can result in unauthorized ability to cause a hang or frequently repeatable crash (complete DOS) of MySQL Server. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-400 Uncontrolled Resource Consumption Metrics CVSS Version Base Score Base Severity Vector String 3.1 6.5 MEDIUM CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H CVE-2019-11041 When PHP EXIF extension is parsing EXIF information from an image, e.g. via exif_read_data() function, in PHP versions 7.1.x below 7.1.31, 7.2.x below 7.2.21 and 7.3.x below 7.3.8 it is possible to supply it with data what will cause it to read past the allocated buffer. This may lead to information disclosure or crash. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-125 Out-of-bounds Read Metrics CVSS Version Base Score Base Severity Vector String 3.1 7.1 HIGH CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:U/C:L/I:N/A:H CVE-2021-2174 Vulnerability in the MySQL Server product of Oracle MySQL (component: InnoDB). Supported versions that are affected are 5.7.33 and prior and 8.0.23 and prior. Difficult to exploit vulnerability allows high privileged attacker with network access via multiple protocols to compromise MySQL Server. Successful attacks of this vulnerability can result in unauthorized ability to cause a hang or frequently repeatable crash (complete DOS) of MySQL Server. View CVE Details Affected Products Festo Didactic SE MES PC Vendor: Festo Didactic SE Product Version: Festo Didactic SE MES PC shipped with Windows 10 Product Status: known_affected Remediations Vendor fix Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities. Relevant CWE: CWE-20 Improper Input Validation Metrics CVSS Version Base Score Base Severity Vector String 3.1 4.4 MEDIUM CVSS:3.1/AV:N/AC:H/PR:H/UI:N/S:U/C:N/I:N/A:H Acknowledgments CERT@VDE helped coordinate and support this publication General recommendation Festo Didactic offers products with security functions that aid the safe operation of plants, systems, machines and networks. In order to protect plants, systems, machines and networks from cyber threats, a comprehensive security concept must be implemented and continuously updated. Festo products and services only constitute one part of such a concept. The customer is responsible for preventing unauthorized access to their plants, systems, machines and networks. Systems, machines and components should only be connected to a company's network or the Internet if and as necessary, and only when the suitable security measures (e.g., firewalls and network segmentation, defense-in-depth) are in place. Failure to ensure adequate security measures when connecting the product to the network can result in vulnerabilities which allow unauthorized, remote access to the network - even beyond the product boundaries. This access could be abused to incur a loss of data or manipulate or sabotage systems. Typical forms of attack include but are not limited to: Denial-of-Service (rendering the system temporarily non-functional), remote execution of malicious code, privilege escalation (executing malicious code with higher system privileges than expected), ransomware (encryption of data and demanding payment for decryption). In the context of industrial systems and machines this can also lead to unsafe states, posing a danger to people and equipment. Furthermore, Festo guidelines on suitable security measures should be observed. Festo products and solutions are constantly being developed further in order to make them more secure. Festo strongly recommends that customers install product updates as soon as they become available and always use the latest versions of its products. Any use of product versions that are no longer supported or any failure to install the latest updates may render the customer vulnerable to cyber-attacks. Disclaimer Festo assumes no liability whatsoever for indirect, collateral, accidental or consequential losses that occur by the distribution and/or use of this document or any losses in connection with the distribution and/or use of this document. All information published in this document is provided free of charge and on good faith by Festo. Insofar as permissible by law, however, none of this information shall establish any warranty, guarantee, commitment, or liability on the part of Festo.\n\nNote: In no case does this information release the operator or responsible person from the obligation to check the effect on his system or installation before using the information and, in the event of negative consequences, not to use the information.\n\nIn addition, the actual general terms, and conditions for delivery, payment and software use of Festo, available under http://www.festo.com and the special provisions for the use of Festo Security Advisory available at https://www.festo.com/psirt shall apply. Impact The vulnerabilities covered by this advisory have a broad range of impacts ranging from denial-of-service to disclosure or manipulation/deletion of information. Given the intended usage of MES PCs for didactic purposes in controlled lab environments, separate from productive systems, it never comes into contact with sensitive information. Therefore the impact is reduced to limited availability of the system. Legal Notice and Terms of Use This product is provided subject to this Notification (https://www.cisa.gov/notification) and this Privacy & Use policy (https://www.cisa.gov/privacy-policy). Recommended Practices CISA recommends users take defensive measures to minimize the exploitation risk of this vulnerability. Minimize network exposure for all control system devices and/or systems, and ensure they are not accessible from the internet. Locate control system networks and remote devices behind firewalls and isolate them from business networks. When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most recent version available. Also recognize VPN is only as secure as its connected devices. CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures. CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies. CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets. Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies. Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents. Advisory Conversion Disclaimer This ICSA is a verbatim republication of Festo SE & Co. KG FSA-202402 from a direct conversion of the vendor's Common Security Advisory Framework (CSAF) advisory. This is republished to CISA's website as a means of increasing visibility and is provided "as-is" for informational purposes only. CISA is not responsible for the editorial or technical accuracy of republished advisories and provides no warranties of any kind regarding any information contained within this advisory. Further, CISA does not endorse any commercial product or service. Please contact Festo SE & Co. KG directly for any questions regarding this advisory. Revision History Initial Release Date: 2024-02-27 Date Revision Summary 2024-02-27 1 Initial version 2025-11-04 2 Adjust to VDE template. Add missing CWE-IDs if available. Updated legal disclaimer to add references to special provisions. 2025-12-08 3 Add all missing CWE identifier and CVSS 3.x scores. 2026-01-27 4 Initial Republication of Festo SE & Co. KG FSA-202402 advisory Legal Notice and Terms of Use
· CISA Cybersecurity Advisory

CISA Adds One Known Exploited Vulnerability to Catalog

CISA has added one new vulnerability to its Known Exploited Vulnerabilities (KEV) Catalog, based on evidence of active exploitation. CVE-2026-24858 Fortinet Multiple Products Authentication Bypass Using an Alternate Path or Channel Vulnerability This type of vulnerability is a frequent attack vector for malicious cyber actors and poses significant risks to the federal enterprise. Binding Operational Directive (BOD)…
Read full source summary
CISA has added one new vulnerability to its Known Exploited Vulnerabilities (KEV) Catalog, based on evidence of active exploitation. CVE-2026-24858 Fortinet Multiple Products Authentication Bypass Using an Alternate Path or Channel Vulnerability This type of vulnerability is a frequent attack vector for malicious cyber actors and poses significant risks to the federal enterprise. Binding Operational Directive (BOD) 22-01: Reducing the Significant Risk of Known Exploited Vulnerabilities established the KEV Catalog as a living list of known Common Vulnerabilities and Exposures (CVEs) that carry significant risk to the federal enterprise. BOD 22-01 requires Federal Civilian Executive Branch (FCEB) agencies to remediate identified vulnerabilities by the due date to protect FCEB networks against active threats. See the BOD 22-01 Fact Sheet for more information. Although BOD 22-01 only applies to FCEB agencies, CISA strongly urges all organizations to reduce their exposure to cyberattacks by prioritizing timely remediation of KEV Catalog vulnerabilities as part of their vulnerability management practice. CISA will continue to add vulnerabilities to the catalog that meet the specified criteria.
· CISA Cybersecurity Advisory

Johnson Controls Metasys Products

View CSAF Summary Successful exploitation of this vulnerability could result in remote SQL execution, leading to alteration or loss of data. The following versions of Johnson Controls Metasys Products are affected: Metasys Application and Data Server (ADS) (CVE-2025-26385) Metasys Extended Application and Data Server (ADX) (CVE-2025-26385) Metasys LCS8500 (CVE-2025-26385) Metasys NAE8500 (CVE-2025-26385) Metasys…
Read full source summary
View CSAF Summary Successful exploitation of this vulnerability could result in remote SQL execution, leading to alteration or loss of data. The following versions of Johnson Controls Metasys Products are affected: Metasys Application and Data Server (ADS) (CVE-2025-26385) Metasys Extended Application and Data Server (ADX) (CVE-2025-26385) Metasys LCS8500 (CVE-2025-26385) Metasys NAE8500 (CVE-2025-26385) Metasys System Configuration Tool (SCT) (CVE-2025-26385) Metasys Controller Configuration Tool (CCT) (CVE-2025-26385) CVSS Vendor Equipment Vulnerabilities v3 10 Johnson Controls Johnson Controls Metasys Products Improper Neutralization of Special Elements used in a Command ('Command Injection') Background Critical Infrastructure Sectors: Commercial Facilities, Critical Manufacturing, Energy, Government Services and Facilities, Transportation Systems Countries/Areas Deployed: Worldwide Company Headquarters Location: Ireland Vulnerabilities Expand All + CVE-2025-26385 Under certain circumstances a successful exploitation of this vulnerability could allow remote SQL execution. View CVE Details Affected Products Johnson Controls Metasys Products Vendor: Johnson Controls Product Version: Johnson Controls Metasys Application and Data Server (ADS): <=14.1, Johnson Controls Metasys Extended Application and Data Server (ADX):14.1, Johnson Controls Metasys LCS8500: >=12.0|<=14.1, Johnson Controls Metasys NAE8500: >=12.0|<=14.1, Johnson Controls Metasys System Configuration Tool (SCT): <=17.1, Johnson Controls Metasys Controller Configuration Tool (CCT): <=17.0 Product Status: known_affected Remediations Mitigation Johnson Controls recommends downloading and executing the Metasys patch for GIV-165989 from the License Portal. Login credentials are required. Mitigation Johnson Controls advises following the Metasys Release 14 Hardening Guide to ensure each Metasys installation is on a segmented network and not exposed to untrusted networks such as the internet. Mitigation Additionally, closing incoming TCP port 1433 can protect against exploitation of this vulnerability. Mitigation For more detailed mitigation instructions, visit Johnson Controls Product Security Advisory JCI-PSA-2026-02. Relevant CWE: CWE-77 Improper Neutralization of Special Elements used in a Command ('Command Injection') Metrics CVSS Version Base Score Base Severity Vector String 3.1 10 CRITICAL CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:H Acknowledgments Johnson Controls reported this vulnerability to CISA Legal Notice and Terms of Use This product is provided subject to this Notification (https://www.cisa.gov/notification) and this Privacy & Use policy (https://www.cisa.gov/privacy-policy). Recommended Practices CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability, such as: Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet. Locate control system networks and remote devices behind firewalls and isolating them from business networks. When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as the connected devices. CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures. CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies. CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets. Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies. Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents. No known public exploitation specifically targeting this vulnerability has been reported to CISA at this time. Revision History Initial Release Date: 2026-01-27 Date Revision Summary 2026-01-27 1 Initial Republication of Johnson Controls advisory JCI-PSA-2026-02 Legal Notice and Terms of Use
Browse saved snapshots