Eppendorf BioFlo 320

View CSAF Summary Successful exploitation of this vulnerability could allow an attacker to gain full access to functionality and data with the bioreactor. The following versions of Eppendorf BioFlo 320 are affected: BioFlo 320 Bioreactor vers:all/* CVSS Vendor Equipment Vulnerabilities v3 9.8 Eppendorf Eppendorf BioFlo 320 Use of Hard-coded Password Background Critical Infrastructure Sectors: Healthcare and Public…
Read full source summary
View CSAF Summary Successful exploitation of this vulnerability could allow an attacker to gain full access to functionality and data with the bioreactor. The following versions of Eppendorf BioFlo 320 are affected: BioFlo 320 Bioreactor vers:all/* CVSS Vendor Equipment Vulnerabilities v3 9.8 Eppendorf Eppendorf BioFlo 320 Use of Hard-coded Password Background Critical Infrastructure Sectors: Healthcare and Public Health Countries/Areas Deployed: Worldwide Company Headquarters Location: Germany Vulnerabilities Expand All + CVE-2026-7251 The affected product is vulnerable to due to VNC server using a hard-coded password. If a remote attacker knows the network address of any BioFlo 320 model with remote access enabled, they can gain full control of the user interface by using this password. Once connected, the attacker would have full access to all control panel features for the BioFlo 320. VNC traffic is not encrypted. View CVE Details Affected Products Eppendorf BioFlo 320 Vendor: Eppendorf Product Version: Eppendorf BioFlo 320 Bioreactor: vers:all/* Product Status: known_affected Remediations Mitigation Eppendorf has released a software update that permanently removes VNC access from the controller. Users should download and apply this update from: https://www.eppendorf.com/software-downloads. https://www.eppendorf.com/software-downloads Mitigation All affected BioFlo 320 systems always shipped with Virtual Network Computing (VNC) disabled by default, and VNC can only be enabled locally at the tower. Eppendorf has removed VNC configuration information from all current documentation, so it no longer appears in BioFlo 320 Operating Manuals. Mitigation Eppendorf recommends user do the following: Verify that VNC is disabled on the controller Enable security so that only Admin and Supervisor roles can change VNC settings Install Version 5.0 Software as soon as possible Relevant CWE: CWE-259 Use of Hard-coded Password Metrics CVSS Version Base Score Base Severity Vector String 3.1 9.8 CRITICAL CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H Acknowledgments BIO-ISAC reported this vulnerability to CISA Legal Notice and Terms of Use This product is provided subject to this Notification (https://www.cisa.gov/notification) and this Privacy & Use policy (https://www.cisa.gov/privacy-policy). Recommended Practices CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability. Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet. Locate control system networks and remote devices behind firewalls and isolating them from business networks. When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as the connected devices. CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures. CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies. CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets. Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies. Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents. CISA also recommends users take the following measures to protect themselves from social engineering attacks: Do not click web links or open attachments in unsolicited email messages. Refer to Recognizing and Avoiding Email Scams for more information on avoiding email scams. Refer to Avoiding Social Engineering and Phishing Attacks for more information on social engineering attacks. No known public exploitation specifically targeting this vulnerability has been reported to CISA at this time. Revision History Initial Release Date: 2026-05-26 Date Revision Summary 2026-05-26 1 Initial Publication Legal Notice and Terms of Use
· CISA Cybersecurity Advisory

ABB Ability Camera Connect

View CSAF Summary ABB is aware of public reports of vulnerabilities in a 3rd party component VLC media player Version 2.2.4 which was delivered together with the installation package of Camera Connect Version 1.5.0.14 and below. An update is available that resolves a privately reported outdated 3rd party component with vulnerabilities in the product versions listed as affected in this advisory. An attacker who…
Read full source summary
View CSAF Summary ABB is aware of public reports of vulnerabilities in a 3rd party component VLC media player Version 2.2.4 which was delivered together with the installation package of Camera Connect Version 1.5.0.14 and below. An update is available that resolves a privately reported outdated 3rd party component with vulnerabilities in the product versions listed as affected in this advisory. An attacker who successfully exploited any of these vulnerabilities in the 3rd party component could potentially compromise the system in different ways. The following versions of ABB Ability Camera Connect are affected: Ability Camera Connect vers:intdot/<=1.5.0.14, 1.5.0.15 CVSS Vendor Equipment Vulnerabilities v3 9.8 ABB ABB Ability Camera Connect Heap-based Buffer Overflow, Integer Underflow (Wrap or Wraparound), Out-of-bounds Write, Uncontrolled Search Path Element, Integer Overflow or Wraparound, Off-by-one Error, Out-of-bounds Read, Double Free, Improper Restriction of Operations within the Bounds of a Memory Buffer, Use After Free Background Critical Infrastructure Sectors: Chemical, Commercial Facilities, Communications, Critical Manufacturing, Energy, Transportation Systems Countries/Areas Deployed: Worldwide Company Headquarters Location: Switzerland Vulnerabilities Expand All + CVE-2024-46461 VLC media player 3.0.20 and earlier is vulnerable to denial of service through an integer overflow which could be triggered with a maliciously crafted mms stream (heap based overflow). If successful, a malicious third party could trigger either a crash of VLC or an arbitrary code execution with the target user's privileges. View CVE Details Affected Products ABB Ability Camera Connect Vendor: ABB Product Version: ABB Ability Camera Connect <=1.5.0.14 Product Status: fixed, known_affected Remediations Mitigation The VLC-based component operates solely within completely isolated environments without internet access or any connectivity to external networks. Consequently: • No exposure to untrusted MMS streams: The integer overflow vulnerability relies on handling a maliciously crafted external stream, which is not possible in isolated environments • No remote attacker access: Without network ingress, attackers cannot trigger the vulnerability remotely. • Drastically reduced attack surface: The absence of any external media inputs effectively neutralizes the exploit path, significantly lowering the risk of both denial of service and code execution. Vendor fix The problem is corrected in the following product versions: ABB Ability Camera Connect 1.5.0.15 The 3rd party component has already been updated. The easiest path to mitigate the problem is an update of just VLC Media Player by the customer. ABB recommends that customers apply the update at earliest convenience. It is also possible to update to the latest Version of Camera Connect. Relevant CWE: CWE-122 Heap-based Buffer Overflow Metrics CVSS Version Base Score Base Severity Vector String 3.1 8 HIGH CVSS:3.1/AV:N/AC:L/PR:L/UI:R/S:U/C:H/I:H/A:H/E:F/RL:T/RC:C CVE-2023-47360 Videolan VLC prior to version 3.0.20 contains an Integer underflow that leads to an incorrect packet length. View CVE Details Affected Products ABB Ability Camera Connect Vendor: ABB Product Version: ABB Ability Camera Connect <=1.5.0.14 Product Status: fixed, known_affected Remediations Mitigation • Air-gapped environments only: Camera Connect is deployed in completely isolated environments lacking any network connectivity or internet access. • No exposure to MMS streams: The vulnerability depends on processing crafted MMS streams, which cannot originate from external or internal network sources when the system is air-gapped. • Elimination of remote attack surface: Without any method for an attacker to deliver malicious media inputs, the vulnerability cannot be triggered remotely. • Strong reduction in exploitation risk: The combined absence of external media ingestion and unavailable network paths effectively neutralizes the integer underflow exploit, significantly reducing the likelihood of both denial-of-service and memory corruption scenarios. Vendor fix The problem is corrected in the following product versions: ABB Ability Camera Connect 1.5.0.15 The 3rd party component has already been updated. The easiest path to mitigate the problem is an update of just VLC Media Player by the customer. ABB recommends that customers apply the update at earliest convenience. It is also possible to update to the latest Version of Camera Connect. Relevant CWE: CWE-191 Integer Underflow (Wrap or Wraparound) Metrics CVSS Version Base Score Base Severity Vector String 3.1 7.5 HIGH CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H CVE-2023-47359 Videolan VLC prior to version 3.0.20 contains an incorrect offset read that leads to a Heap-Based Buffer Overflow in function GetPacket() and results in a memory corruption. View CVE Details Affected Products ABB Ability Camera Connect Vendor: ABB Product Version: ABB Ability Camera Connect <=1.5.0.14 Product Status: fixed, known_affected Remediations Mitigation Given that Camera Connect is deployed exclusively in fully isolated, air-gapped environments with no internet access or external network connectivity, the following risk-reduction factors apply: • No exposure to crafted MMS streams: The exploit requires the receipt of specially crafted packets via the MMS protocol, which cannot occur without network connectivity. • Network attack vector eliminated: As the vulnerability’s CVSS vector highlights a network-based attack (AV:N), the lack of any ingress network path nullifies the attack surface. • Low likelihood of exploitation: Without access to malicious media input, there is effectively no practical method for an attacker to trigger memory corruption, making the likelihood of denial of service or arbitrary code execution negligible. Vendor fix The problem is corrected in the following product versions: ABB Ability Camera Connect 1.5.0.15 The 3rd party component has already been updated. The easiest path to mitigate the problem is an update of just VLC Media Player by the customer. ABB recommends that customers apply the update at earliest convenience. It is also possible to update to the latest Version of Camera Connect. Relevant CWE: CWE-787 Out-of-bounds Write Metrics CVSS Version Base Score Base Severity Vector String 3.1 9.8 CRITICAL CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H CVE-2023-46814 A binary hijacking vulnerability exists within the VideoLAN VLC media player before 3.0.19 on Windows. The uninstaller attempts to execute code with elevated privileges out of a standard user writable location. Standard users may use this to gain arbitrary code execution as SYSTEM. View CVE Details Affected Products ABB Ability Camera Connect Vendor: ABB Product Version: ABB Ability Camera Connect <=1.5.0.14 Product Status: fixed, known_affected Remediations Mitigation Given that the VLC-based component is installed exclusively within air-gapped environments under strict administrative control, the following factors substantially reduce risk: • Restricted user access: Only trusted, privileged users perform installations and modifications. Standard users have no write permissions to the uninstaller directory. • No internet or network access: The exploit requires local manipulation of VLC’s uninstaller files; without external connectivity, remote coercion or manipulation is impossible. • Elimination of attacker vector: In air gapped deployments with administrative controls, un-privileged users cannot place malicious DLLs or executables in the uninstaller’s search path. • Minimized privilege escalation risk: The combination of controlled write access, absence of network exposure, and trusted user roles effectively neutralizes the binary hijacking threat, rendering successful exploitation highly unlikely. Vendor fix The problem is corrected in the following product versions: ABB Ability Camera Connect 1.5.0.15 The 3rd party component has already been updated. The easiest path to mitigate the problem is an update of just VLC Media Player by the customer. ABB recommends that customers apply the update at earliest convenience. It is also possible to update to the latest Version of Camera Connect. Relevant CWE: CWE-427 Uncontrolled Search Path Element Metrics CVSS Version Base Score Base Severity Vector String 3.1 7.8 HIGH CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H CVE-2022-41325 An integer overflow in the VNC module in VideoLAN VLC Media Player through 3.0.17.4 allows attackers, by tricking a user into opening a crafted playlist or connecting to a rogue VNC server, to crash VLC or execute code under some conditions. View CVE Details Affected Products ABB Ability Camera Connect Vendor: ABB Product Version: ABB Ability Camera Connect <=1.5.0.14 Product Status: fixed, known_affected Remediations Mitigation Camera Connect is deployed exclusively in air-gapped environments with no internet connectivity or external network access, which significantly reduces the risk: • No exposure to malicious MKV files: The exploit requires a specially crafted Matroska file. In controlled environments without external media sources, such files cannot be introduced. • Remote attack vector eliminated: The vulnerability’s CVSS vector indicates a network-based attack scenario, which is impossible without connectivity. • Strict operational controls: Media ingestion is limited to trusted sources under administrative supervision, further minimizing the likelihood of malicious file introduction. • Effective risk reduction: These combined factors render exploitation highly improbable, neutralizing the buffer overflow threat. Vendor fix The problem is corrected in the following product versions: ABB Ability Camera Connect 1.5.0.15 The 3rd party component has already been updated. The easiest path to mitigate the problem is an update of just VLC Media Player by the customer. ABB recommends that customers apply the update at earliest convenience. It is also possible to update to the latest Version of Camera Connect. Relevant CWE: CWE-190 Integer Overflow or Wraparound Metrics CVSS Version Base Score Base Severity Vector String 3.1 7.8 HIGH CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H CVE-2020-26664 A vulnerability in EbmlTypeDispatcher::send in VideoLAN VLC media player 3.0.11 allows attackers to trigger a heap-based buffer overflow via a crafted .mkv file. View CVE Details Affected Products ABB Ability Camera Connect Vendor: ABB Product Version: ABB Ability Camera Connect <=1.5.0.14 Product Status: fixed, known_affected Remediations Mitigation • No exposure to malicious ASF files: The exploit requires a specially crafted ASF file. In con-trolled environments without external media sources, such files cannot be introduced. • Remote attack vector eliminated: The vulnerability’s CVSS vector indicates a network-based attack scenario, which is impossible without connectivity. • Strict operational controls: Media ingestion is limited to trusted sources under administrative supervision, further minimizing the likelihood of malicious file introduction. • Effective risk reduction: These combined factors render exploitation highly improbable, neutralizing the buffer overflow threat. Vendor fix The problem is corrected in the following product versions: ABB Ability Camera Connect 1.5.0.15 The 3rd party component has already been updated. The easiest path to mitigate the problem is an update of just VLC Media Player by the customer. ABB recommends that customers apply the update at earliest convenience. It is also possible to update to the latest Version of Camera Connect. Relevant CWE: CWE-787 Out-of-bounds Write Metrics CVSS Version Base Score Base Severity Vector String 3.1 7.8 HIGH CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H CVE-2019-19721 An off-by-one error in the DecodeBlock function in codec/sdl_image.c in VideoLAN VLC media player before 3.0.9 allows remote attackers to cause a denial of service (memory corruption) via a crafted image file. NOTE: this may be related to the SDL_Image product. View CVE Details Affected Products ABB Ability Camera Connect Vendor: ABB Product Version: ABB Ability Camera Connect <=1.5.0.14 Product Status: fixed, known_affected Remediations Mitigation • No exposure to malicious ASF files: The exploit requires a specially crafted ASF file. In con-trolled environments without external media sources, such files cannot be introduced. • Remote attack vector eliminated: The vulnerability’s CVSS vector indicates a network-based attack scenario, which is impossible without connectivity. • Strict operational controls: Media ingestion is limited to trusted sources under administrative supervision, further minimizing the likelihood of malicious file introduction. • Effective risk reduction: These combined factors render exploitation highly improbable, neutralizing the buffer overflow threat. Vendor fix The problem is corrected in the following product versions: ABB Ability Camera Connect 1.5.0.15 The 3rd party component has already been updated. The easiest path to mitigate the problem is an update of just VLC Media Player by the customer. ABB recommends that customers apply the update at earliest convenience. It is also possible to update to the latest Version of Camera Connect. Relevant CWE: CWE-193 Off-by-one Error Metrics CVSS Version Base Score Base Severity Vector String 3.1 7.8 HIGH CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H CVE-2019-13962 lavc_CopyPicture in modules/codec/avcodec/video.c in VideoLAN VLC media player through 3.0.7 has a heap-based buffer over-read because it does not properly validate the width and height. View CVE Details Affected Products ABB Ability Camera Connect Vendor: ABB Product Version: ABB Ability Camera Connect <=1.5.0.14 Product Status: fixed, known_affected Remediations Mitigation • No exposure to malicious MKV files: The exploit requires a specially crafted MKV file. In con-trolled environments without external media sources, such files cannot be introduced. • Remote attack vector eliminated: The vulnerability’s CVSS vector indicates a network-based attack scenario, which is impossible without connectivity. • Strict operational controls: Media ingestion is limited to trusted sources under administrative supervision, further minimizing the likelihood of malicious file introduction. • Effective risk reduction: These combined factors render exploitation highly improbable, neutralizing the buffer overflow threat. Vendor fix The problem is corrected in the following product versions: ABB Ability Camera Connect 1.5.0.15 The 3rd party component has already been updated. The easiest path to mitigate the problem is an update of just VLC Media Player by the customer. ABB recommends that customers apply the update at earliest convenience. It is also possible to update to the latest Version of Camera Connect. Relevant CWE: CWE-125 Out-of-bounds Read Metrics CVSS Version Base Score Base Severity Vector String 3.1 9.8 CRITICAL CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H CVE-2019-13615 libebml before 1.3.6, as used in the MKV module in VideoLAN VLC Media Player binaries before 3.0.3, has a heap-based buffer over-read in EbmlElement::FindNextElement. View CVE Details Affected Products ABB Ability Camera Connect Vendor: ABB Product Version: ABB Ability Camera Connect <=1.5.0.14 Product Status: fixed, known_affected Remediations Mitigation • No exposure to malicious ASF files: The exploit requires a specially crafted ASF file. In con-trolled environments without external media sources, such files cannot be introduced. • Remote attack vector eliminated: The vulnerability’s CVSS vector indicates a network-based attack scenario, which is impossible without connectivity. • Strict operational controls: Media ingestion is limited to trusted sources under administrative supervision, further minimizing the likelihood of malicious file introduction. • Effective risk reduction: These combined factors render exploitation highly improbable, neutralizing the buffer overflow threat. Vendor fix The problem is corrected in the following product versions: ABB Ability Camera Connect 1.5.0.15 The 3rd party component has already been updated. The easiest path to mitigate the problem is an update of just VLC Media Player by the customer. ABB recommends that customers apply the update at earliest convenience. It is also possible to update to the latest Version of Camera Connect. Relevant CWE: CWE-125 Out-of-bounds Read Metrics CVSS Version Base Score Base Severity Vector String 3.1 5.5 MEDIUM CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:N/I:N/A:H CVE-2019-13602 An Integer Underflow in MP4_EIA608_Convert() in modules/demux/mp4/mp4.c in VideoLAN VLC me-dia player through 3.0.7.1 allows remote attackers to cause a denial of service (heap-based buffer over-flow and crash) or possibly have unspecified other impact via a crafted .mp4 file. View CVE Details Affected Products ABB Ability Camera Connect Vendor: ABB Product Version: ABB Ability Camera Connect <=1.5.0.14 Product Status: fixed, known_affected Remediations Mitigation • No exposure to malicious ASF files: The exploit requires a specially crafted ASF file. In con-trolled environments without external media sources, such files cannot be introduced. • Remote attack vector eliminated: The vulnerability’s CVSS vector indicates a network-based attack scenario, which is impossible without connectivity. • Strict operational controls: Media ingestion is limited to trusted sources under administrative supervision, further minimizing the likelihood of malicious file introduction. • Effective risk reduction: These combined factors render exploitation highly improbable, neutralizing the buffer overflow threat. Vendor fix The problem is corrected in the following product versions: ABB Ability Camera Connect 1.5.0.15 The 3rd party component has already been updated. The easiest path to mitigate the problem is an update of just VLC Media Player by the customer. ABB recommends that customers apply the update at earliest convenience. It is also possible to update to the latest Version of Camera Connect. Relevant CWE: CWE-191 Integer Underflow (Wrap or Wraparound) Metrics CVSS Version Base Score Base Severity Vector String 3.1 7.8 HIGH CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H CVE-2019-5460 Double Free in VLC versions <= 3.0.6 leads to a crash. View CVE Details Affected Products ABB Ability Camera Connect Vendor: ABB Product Version: ABB Ability Camera Connect <=1.5.0.14 Product Status: fixed, known_affected Remediations Mitigation • No exposure to malicious ASF files: The exploit requires a specially crafted ASF file. In con-trolled environments without external media sources, such files cannot be introduced. • Remote attack vector eliminated: The vulnerability’s CVSS vector indicates a network-based attack scenario, which is impossible without connectivity. • Strict operational controls: Media ingestion is limited to trusted sources under administrative supervision, further minimizing the likelihood of malicious file introduction. • Effective risk reduction: These combined factors render exploitation highly improbable, neutralizing the buffer overflow threat. Vendor fix The problem is corrected in the following product versions: ABB Ability Camera Connect 1.5.0.15 The 3rd party component has already been updated. The easiest path to mitigate the problem is an update of just VLC Media Player by the customer. ABB recommends that customers apply the update at earliest convenience. It is also possible to update to the latest Version of Camera Connect. Relevant CWE: CWE-415 Double Free Metrics CVSS Version Base Score Base Severity Vector String 3.1 5.5 MEDIUM CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:N/I:N/A:H CVE-2019-5459 An Integer underflow in VLC Media Player versions < 3.0.7 leads to an out-of-band read. View CVE Details Affected Products ABB Ability Camera Connect Vendor: ABB Product Version: ABB Ability Camera Connect <=1.5.0.14 Product Status: fixed, known_affected Remediations Mitigation • No exposure to malicious ASF files: The exploit requires a specially crafted ASF file. In con-trolled environments without external media sources, such files cannot be introduced. • Remote attack vector eliminated: The vulnerability’s CVSS vector indicates a network-based attack scenario, which is impossible without connectivity. • Strict operational controls: Media ingestion is limited to trusted sources under administrative supervision, further minimizing the likelihood of malicious file introduction. • Effective risk reduction: These combined factors render exploitation highly improbable, neutralizing the buffer overflow threat. Vendor fix The problem is corrected in the following product versions: ABB Ability Camera Connect 1.5.0.15 The 3rd party component has already been updated. The easiest path to mitigate the problem is an update of just VLC Media Player by the customer. ABB recommends that customers apply the update at earliest convenience. It is also possible to update to the latest Version of Camera Connect. Relevant CWE: CWE-191 Integer Underflow (Wrap or Wraparound) Metrics CVSS Version Base Score Base Severity Vector String 3.1 7.1 HIGH CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:N/A:H CVE-2019-5439 A Buffer Overflow in VLC Media Player < 3.0.7 causes a crash which can possibly be further developed into a remote code execution exploit. View CVE Details Affected Products ABB Ability Camera Connect Vendor: ABB Product Version: ABB Ability Camera Connect <=1.5.0.14 Product Status: fixed, known_affected Remediations Mitigation • No exposure to malicious ASF files: The exploit requires a specially crafted ASF file. In con-trolled environments without external media sources, such files cannot be introduced. • Remote attack vector eliminated: The vulnerability’s CVSS vector indicates a network-based attack scenario, which is impossible without connectivity. • Strict operational controls: Media ingestion is limited to trusted sources under administrative supervision, further minimizing the likelihood of malicious file introduction. • Effective risk reduction: These combined factors render exploitation highly improbable, neutralizing the buffer overflow threat. Vendor fix The problem is corrected in the following product versions: ABB Ability Camera Connect 1.5.0.15 The 3rd party component has already been updated. The easiest path to mitigate the problem is an update of just VLC Media Player by the customer. ABB recommends that customers apply the update at earliest convenience. It is also possible to update to the latest Version of Camera Connect. Relevant CWE: CWE-119 Improper Restriction of Operations within the Bounds of a Memory Buffer Metrics CVSS Version Base Score Base Severity Vector String 3.1 6.5 MEDIUM CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:U/C:N/I:N/A:H CVE-2018-11529 VideoLAN VLC media player 2.2.x is prone to a use after free vulnerability which an attacker can lever-age to execute arbitrary code via crafted MKV files. Failed exploit attempts will likely result in denial of service conditions. View CVE Details Affected Products ABB Ability Camera Connect Vendor: ABB Product Version: ABB Ability Camera Connect <=1.5.0.14 Product Status: fixed, known_affected Remediations Mitigation The affected software is deployed exclusively in isolated environments with no internet connectivity and restricted external access. Exploitation of this vulnerability requires a user to open a specially crafted MKV file provided by an attacker. Since the system operates in a controlled network without exposure to untrusted sources, the likelihood of receiving and executing malicious media files is significantly reduced. Additionally, operational procedures can enforce the use of trusted media files only, further minimizing the risk. Vendor fix The problem is corrected in the following product versions: ABB Ability Camera Connect 1.5.0.15 The 3rd party component has already been updated. The easiest path to mitigate the problem is an update of just VLC Media Player by the customer. ABB recommends that customers apply the update at earliest convenience. It is also possible to update to the latest Version of Camera Connect. Relevant CWE: CWE-416 Use After Free Metrics CVSS Version Base Score Base Severity Vector String 3.1 8 HIGH CVSS:3.1/AV:A/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H CVE-2017-17670 In VideoLAN VLC media player through 2.2.8, there is a type conversion vulnerability in mod-ules/demux/mp4/libmp4.c in the MP4 demux module leading to a invalid free, because the type of a box may be changed between a read operation and a free operation. View CVE Details Affected Products ABB Ability Camera Connect Vendor: ABB Product Version: ABB Ability Camera Connect <=1.5.0.14 Product Status: fixed, known_affected Remediations Mitigation The affected VLC component is deployed exclusively in fully isolated, air gapped environments with no internet connectivity and tightly controlled external sources. Exploitation of CVE 2017 17670 re-quires a user to open a specifically crafted MP4 file containing a type conversion error in the demuxer. Since the system only processes trusted media files—validated through internal procedures and se-cured media channels—the probability of exposure to hostile MP4 content is minimal. Therefore, the risk of successful exploitation is significantly mitigated by the restricted deployment context. Vendor fix The problem is corrected in the following product versions: ABB Ability Camera Connect 1.5.0.15 The 3rd party component has already been updated. The easiest path to mitigate the problem is an update of just VLC Media Player by the customer. ABB recommends that customers apply the update at earliest convenience. It is also possible to update to the latest Version of Camera Connect. Relevant CWE: CWE-416 Use After Free Metrics CVSS Version Base Score Base Severity Vector String 3.1 8.8 HIGH CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H CVE-2017-10699 avcodec 2.2.x, as used in VideoLAN VLC media player 2.2.7-x before 2017-06-29, allows out-of-bounds heap memory write due to calling memcpy() with a wrong size, leading to a denial of service (application crash) or possibly code execution. View CVE Details Affected Products ABB Ability Camera Connect Vendor: ABB Product Version: ABB Ability Camera Connect <=1.5.0.14 Product Status: fixed, known_affected Remediations Mitigation No network-based exposure: The vulnerability requires an external actor to supply malicious media content. With no Internet connectivity and presumably controlled file sources, the risk of loading un-trusted files is minimal. Vendor fix The problem is corrected in the following product versions: ABB Ability Camera Connect 1.5.0.15 The 3rd party component has already been updated. The easiest path to mitigate the problem is an update of just VLC Media Player by the customer. ABB recommends that customers apply the update at earliest convenience. It is also possible to update to the latest Version of Camera Connect. Relevant CWE: CWE-787 Out-of-bounds Write Metrics CVSS Version Base Score Base Severity Vector String 3.1 9.8 CRITICAL CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H CVE-2017-9301 plugins\audio_filter\libmpgatofixed32_plugin.dll in VideoLAN VLC media player 2.2.4 allows remote attackers to cause a denial of service (invalid read and application crash) or possibly have unspecified other impact via a crafted file. View CVE Details Affected Products ABB Ability Camera Connect Vendor: ABB Product Version: ABB Ability Camera Connect <=1.5.0.14 Product Status: fixed, known_affected Remediations Mitigation This vulnerability affects the libmpgatofixed32_plugin.dll module in VLC 2.2.4, which is responsible for decoding MPEG audio streams. The software in question does not process audio files or use any functionality related to audio decoding, meaning the vulnerable component is never invoked during normal operation. Additionally, the deployment environment is fully offline with no internet connectivity, and media ingestion is restricted to trusted internal sources. As a result, the attack surface for this vulnerability is effectively nonexistent, and the risk of exploitation is negligible under these conditions. Vendor fix The problem is corrected in the following product versions: ABB Ability Camera Connect 1.5.0.15 The 3rd party component has already been updated. The easiest path to mitigate the problem is an update of just VLC Media Player by the customer. ABB recommends that customers apply the update at earliest convenience. It is also possible to update to the latest Version of Camera Connect. Relevant CWE: CWE-125 Out-of-bounds Read Metrics CVSS Version Base Score Base Severity Vector String 3.1 7.8 HIGH CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H CVE-2017-9300 plugins\codec\libflac_plugin.dll in VideoLAN VLC media player 2.2.4 allows remote attackers to cause a denial of service (heap corruption and application crash) or possibly have unspecified other impact via a crafted FLAC file. View CVE Details Affected Products ABB Ability Camera Connect Vendor: ABB Product Version: ABB Ability Camera Connect <=1.5.0.14 Product Status: fixed, known_affected Remediations Mitigation This vulnerability affects VLC’s FLAC audio processing component. Camera Connect does not handle or process audio files, meaning the vulnerable code path is never executed during normal operation. Combined with the fact that the deployment environment is fully isolated (air gapped) and does not allow external file transfers from untrusted sources, the likelihood of exploitation is effectively eliminated. Vendor fix The problem is corrected in the following product versions: ABB Ability Camera Connect 1.5.0.15 The 3rd party component has already been updated. The easiest path to mitigate the problem is an update of just VLC Media Player by the customer. ABB recommends that customers apply the update at earliest convenience. It is also possible to update to the latest Version of Camera Connect. Relevant CWE: CWE-119 Improper Restriction of Operations within the Bounds of a Memory Buffer Metrics CVSS Version Base Score Base Severity Vector String 3.1 7.8 HIGH CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H CVE-2017-8313 Heap out-of-bound read in ParseJSS in VideoLAN VLC before 2.2.5 due to missing check of string termination allows attackers to read data beyond allocated memory and potentially crash the process via a crafted subtitles file. View CVE Details Affected Products ABB Ability Camera Connect Vendor: ABB Product Version: ABB Ability Camera Connect <=1.5.0.14 Product Status: fixed, known_affected Remediations Mitigation Even though the affected VLC version (2.2.4) contains this vulnerability, the software is deployed in fully air-gapped environments with no external or internet-facing connectivity. As a result, the likeli-hood of exploiting this vulnerability is extremely low. Vendor fix The problem is corrected in the following product versions: ABB Ability Camera Connect 1.5.0.15 The 3rd party component has already been updated. The easiest path to mitigate the problem is an update of just VLC Media Player by the customer. ABB recommends that customers apply the update at earliest convenience. It is also possible to update to the latest Version of Camera Connect. Relevant CWE: CWE-125 Out-of-bounds Read Metrics CVSS Version Base Score Base Severity Vector String 3.1 5.5 MEDIUM CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:N/I:N/A:H CVE-2017-8312 Heap out-of-bound read in ParseJSS in VideoLAN VLC due to missing check of string length allows attackers to read heap uninitialized data via a crafted subtitles file. View CVE Details Affected Products ABB Ability Camera Connect Vendor: ABB Product Version: ABB Ability Camera Connect <=1.5.0.14 Product Status: fixed, known_affected Remediations Mitigation Because the affected VLC version (2.2.4) suffers from a heap out of bound read in the ParseJSS function—allowing an attacker to read uninitialized heap data via a crafted subtitles file—the risk of external exploitation is significantly reduced in your environment. Since the software is installed in strictly isolated systems with no internet access, no external attacker can deliver malicious subtitle files re-motely. Consequently, the only remaining exposure is local: an insider would need to intentionally load a crafted subtitle file to trigger the issue—a scenario considered highly unlikely under current governance and usage controls. Vendor fix The problem is corrected in the following product versions: ABB Ability Camera Connect 1.5.0.15 The 3rd party component has already been updated. The easiest path to mitigate the problem is an update of just VLC Media Player by the customer. ABB recommends that customers apply the update at earliest convenience. It is also possible to update to the latest Version of Camera Connect. Relevant CWE: CWE-125 Out-of-bounds Read Metrics CVSS Version Base Score Base Severity Vector String 3.1 5.5 MEDIUM CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:N/A:N CVE-2017-8311 Potential heap based buffer overflow in ParseJSS in VideoLAN VLC before 2.2.5 due to skipping NULL terminator in an input string allows attackers to execute arbitrary code via a crafted subtitles file. View CVE Details Affected Products ABB Ability Camera Connect Vendor: ABB Product Version: ABB Ability Camera Connect <=1.5.0.14 Product Status: fixed, known_affected Remediations Mitigation Since the application is deployed exclusively in isolated, air-gapped environments with no external network connectivity, the attack vector—specifically, the ability for an attacker to deliver a crafted subtitle file—is significantly constrained. Vendor fix The problem is corrected in the following product versions: ABB Ability Camera Connect 1.5.0.15 The 3rd party component has already been updated. The easiest path to mitigate the problem is an update of just VLC Media Player by the customer. ABB recommends that customers apply the update at earliest convenience. It is also possible to update to the latest Version of Camera Connect. Relevant CWE: CWE-119 Improper Restriction of Operations within the Bounds of a Memory Buffer Metrics CVSS Version Base Score Base Severity Vector String 3.1 7.8 HIGH CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H CVE-2017-8310 Heap out-of-bound read in CreateHtmlSubtitle in VideoLAN VLC 2.2.x due to missing check of string termination allows attackers to read data beyond allocated memory and potentially crash the process (causing a denial of service) via a crafted subtitles file. View CVE Details Affected Products ABB Ability Camera Connect Vendor: ABB Product Version: ABB Ability Camera Connect <=1.5.0.14 Product Status: fixed, known_affected Remediations Mitigation Because your team’s VLC based software is deployed only in isolated environments without internet access, the risk of malicious delivery of crafted subtitle files is greatly diminished. This significantly reduces exploitation likelihood. Vendor fix The problem is corrected in the following product versions: ABB Ability Camera Connect 1.5.0.15 The 3rd party component has already been updated. The easiest path to mitigate the problem is an update of just VLC Media Player by the customer. ABB recommends that customers apply the update at earliest convenience. It is also possible to update to the latest Version of Camera Connect. Relevant CWE: CWE-125 Out-of-bounds Read Metrics CVSS Version Base Score Base Severity Vector String 3.1 5.5 MEDIUM CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:N/I:N/A:H Acknowledgments ABB PSIRT reported these vulnerabilities to CISA. Notice The information in this document is subject to change without notice, and should not be construed as a commitment by ABB. ABB provides no warranty, express or implied, including warranties of merchantability and fitness for a particular purpose, for the information contained in this document, and assumes no responsibility for any errors that may appear in this document. In no event shall ABB or any of its suppliers be liable for direct, indirect, special, incidental or consequential damages of any nature or kind arising from the use of this document, or from the use of any hardware or software described in this document, even if ABB or its suppliers have been advised of the possibility of such damages. This document and parts hereof must not be reproduced or copied without written permission from ABB, and the contents hereof must not be imparted to a third party nor used for any unauthorized purpose. All rights to registrations and trademarks reside with their respective owners. Frequently Asked Questions What causes the vulnerability? The vulnerability is caused by unchecked input data in the VLC media player in Camera Connect What is ? VLC media player What might an attacker use the vulnerability to do? An attacker who successfully exploited this vulnerability could cause the affected system node to stop or become inaccessible and allow the attacker to insert and run arbitrary code . How could an attacker exploit the vulnerability? An attacker could try to exploit the vulnerability by creating a specially crafted file, copying the file to affected system nodes and then manually open the file via VLC Mediaplayer. This would require that the attacker has access to the system network, by connecting to the network either directly or through a wrongly configured or penetrated firewall, or that he installs malicious software on a system node or otherwise infects the network with malicious software. Recommended practices help mitigate such attacks, see section Mitigating Factors above. Could the vulnerability be exploited remotely? No, to exploit this vulnerability an attacker would need to have physical access to an affected system node. Can functional safety be affected by an exploit of this vulnerability? While these vulnerabilities primarily impact confidentiality, integrity, and availability, they do not directly affect functional safety in the traditional sense. However, a compromised system (due to arbitrary code execution or a critical service crash) may compromise safety-related processes dependent on VLC, potentially disrupting business operations or compliance. What does the update do? The update removes the vulnerability by providing a newer version of the VLC media player When this security advisory was issued, had this vulnerability been publicly disclosed? This vulnerability has been publicly disclosed for the 3rd party component, but not for the ABB product using this component When this security advisory was issued, had ABB received any reports that this vulnerability was being exploited? No, ABB had not received any information indicating that this vulnerability had been exploited when this security advisory was originally issued. Legal Notice and Terms of Use This product is provided subject to this Notification (https://www.cisa.gov/notification) and this Privacy & Use policy (https://www.cisa.gov/privacy-policy). Recommended Practices CISA recommends users take defensive measures to minimize the exploitation risk of this vulnerability. Minimize network exposure for all control system devices and/or systems, and ensure they are not accessible from the internet. Locate control system networks and remote devices behind firewalls and isolate them from business networks. When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most recent version available. Also recognize VPN is only as secure as its connected devices. CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures. CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies. CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets. Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies. Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents. Advisory Conversion Disclaimer This ICSA is a verbatim republication of ABB PSIRT 4HZM000603 from a direct conversion of the vendor's Common Security Advisory Framework (CSAF) advisory. This is republished to CISA's website as a means of increasing visibility and is provided "as-is" for informational purposes only. CISA is not responsible for the editorial or technical accuracy of republished advisories and provides no warranties of any kind regarding any information contained within this advisory. Further, CISA does not endorse any commercial product or service. Please contact ABB PSIRT directly for any questions regarding this advisory. Revision History Initial Release Date: 2025-11-27 Date Revision Summary 2025-11-27 1 Initial version. 2025-11-28 2 Correction in References 2026-05-26 3 Initial CISA Republication of ABB PSIRT 4HZM000603 advisory Legal Notice and Terms of Use
· CISA Cybersecurity Advisory

ABB B&R Automation Runtime DoS Vulnerability in System Diagnostics Manager (SDM)

View CSAF Summary An update is available that resolves a vulnerability identified by B&Rs internal security analysis in the product versions listed as affected in this advisory. An attacker who successfully exploited this vulnerability could cause the product to stop. The following versions of ABB B&R Automation Runtime DoS Vulnerability in System Diagnostics Manager (SDM) are affected: Automation Runtime <6.3…
Read full source summary
View CSAF Summary An update is available that resolves a vulnerability identified by B&Rs internal security analysis in the product versions listed as affected in this advisory. An attacker who successfully exploited this vulnerability could cause the product to stop. The following versions of ABB B&R Automation Runtime DoS Vulnerability in System Diagnostics Manager (SDM) are affected: Automation Runtime <6.3 Automation Runtime <Q4.93 CVSS Vendor Equipment Vulnerabilities v3 10 B&R ABB B&R Automation Runtime DoS Vulnerability in System Diagnostics Manager (SDM) Improper Resource Locking Background Critical Infrastructure Sectors: Chemical, Communications, Critical Manufacturing, Dams, Energy, Healthcare and Public Health, Information Technology, Water and Wastewater Countries/Areas Deployed: Worldwide Company Headquarters Location: Switzerland Vulnerabilities Expand All + CVE-2025-3450 An Improper Resource Locking vulnerability in the SDM component of B&R Automation Runtime versions before 6.3 and before Q4.93 may allow an unauthenticated network-based attacker to delete data causing denial of service conditions. View CVE Details Affected Products ABB B&R Automation Runtime DoS Vulnerability in System Diagnostics Manager (SDM) Vendor: B&R Product Version: Automation Runtime <6.3, Automation Runtime <Q4.93 Product Status: fixed, known_affected Remediations Vendor fix The problem is corrected in Automation Runtime versions 6.3 and Q4.93. The System Diagnostic Manager (SDM) is disabled by default in Automation Runtime 6 and is not in-tended be enabled on active systems located outside properly secured production networks or in facilities lacking adequate physical and logical access controls to prevent any form of unauthorized interaction. For customers who use SDM on their systems, B&R recommends applying the update at the earliest convenience. The process to install updates is described in the user manual. The step to identify the installed product version is described in the user manual. Relevant CWE: CWE-413 Improper Resource Locking Metrics CVSS Version Base Score Base Severity Vector String 3.1 10 CRITICAL CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:C/C:N/I:H/A:H/E:U/RL:O/RC:C Acknowledgments ABB PSIRT reported this vulnerability to CISA. Notice The information in this document is subject to change without notice, and should not be construed as a commitment by B&R. B&R provides no warranty, express or implied, including warranties of merchantability and fitness for a particular purpose, for the information contained in this document, and assumes no responsibility for any errors that may appear in this document. In no event shall B&R or any of its suppliers be liable for direct, indirect, special, incidental or consequential damages of any nature or kind arising from the use of this document, or from the use of any hardware or software described in this document, even if B&R or its suppliers have been advised of the possibility of such damages. This document and parts hereof must not be reproduced or copied without written permission from B&R, and the contents hereof must not be imparted to a third party nor used for any unauthorized purpose. All rights to registrations and trademarks reside with their respective owners. Mitigating factors Deactivate the vulnerable component The SDM is deactivated by default on Automation Runtime version >=6.0. For Automation Runtime versions <6.0, the SDM can be deactivated in the Automation Studio project. Please refer to Automation Help GUID 1d915d67-07f7-4034-a472-c204b5cabbfe for further guidance. Access to the System Diagnostic Manager (SDM) shall be restricted to trusted personnel through appropriate external security measures. If SDM is required solely for maintenance purposes, it should be enabled or access granted only for the minimum time necessary to perform the task. Limit accessibility B&R recommends in general to configure the HTTP protocol over TLS (HTTPS). Customers may restrict access to the webserver by configuring mutual TLS (mTLS) in the Automation Studio project (Option “Validate SSL communication partner”). Be aware that configuring mTLS would impact also other applications using the AR webserver (e.g. mapp View). Please refer to Automation Help GUID 01ced6c0-28ef-4aaa-bd05-2442b971859c to learn more about the TLS Configuration in Automation Studio. In addition, accessibility of the webserver can be limited to trusted IP addresses using the Automation Runtime host-based firewall. Please refer to Automation Help GUID 75b8994b-f97a-4e0f-8278-43c7a737e65f for details. Refer to section “General security recommendations” for further advise on how to keep your system secure. Frequently asked questions What causes the vulnerability? The vulnerabilities are caused by improper resource locking. What is System Diagnostics Manager (SDM)? System Diagnostics Manager (SDM) is a webpage available over the Automation Runtime Webserver, showing key diagnostic information of the running controller What is Automation Runtime (AR)? B&R Automation Runtime is a middleware system enabling customers to run applications on B&R target systems. What might an attacker use the vulnerability to do? An attacker who successfully exploited these vulnerabilities could cause the affected system node to stop. How could an attacker exploit the vulnerability? An attacker could try to exploit the vulnerability by creating a specially crafted message and sending the message to an affected system node. This would require that the attacker has access to the system network, by connecting to the network either directly or through a wrongly configured or penetrated firewall, or that he installs malicious software on a system node or otherwise infects the network with malicious software. Recommended practices help mitigate such attacks, see section Mitigating Factors above. Could the vulnerability be exploited remotely? Yes, an attacker who has network access to an affected system node could exploit this vulnerability. Recommended practices include that process control systems are physically protected, have no direct connections to the Internet, and are separated from other networks by means of a firewall system that has a minimal number of ports exposed. When this security advisory was issued, had this vulnerability been publicly disclosed? No, B&R discovered the vulnerabilities through its own security analysis. When this security advisory was issued, had B&R received any reports that this vulnerability was being exploited? No, B&R had not received any information indicating that this vulnerability had been exploited when this security advisory was originally issued. Legal Notice and Terms of Use This product is provided subject to this Notification (https://www.cisa.gov/notification) and this Privacy & Use policy (https://www.cisa.gov/privacy-policy). Recommended Practices CISA recommends users take defensive measures to minimize the exploitation risk of these vulnerabilities. Minimize network exposure for all control system devices and/or systems, and ensure they are not accessible from the internet. Locate control system networks and remote devices behind firewalls and isolate them from business networks. When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most recent version available. Also recognize VPN is only as secure as its connected devices. CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures. CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies. CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets. Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies. Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents. Advisory Conversion Disclaimer This ICSA is a verbatim republication of ABB PSIRT SA25P002 from a direct conversion of the vendor's Common Security Advisory Framework (CSAF) advisory. This is republished to CISA's website as a means of increasing visibility and is provided "as-is" for informational purposes only. CISA is not responsible for the editorial or technical accuracy of republished advisories and provides no warranties of any kind regarding any information contained within this advisory. Further, CISA does not endorse any commercial product or service. Please contact ABB PSIRT directly for any questions regarding this advisory. Revision History Initial Release Date: 2025-10-07 Date Revision Summary 2025-10-07 1 Initial version. 2026-05-26 2 Initial CISA Republication of ABB PSIRT SA25P002 advisory Legal Notice and Terms of Use
· CISA Cybersecurity Advisory

ABB LVS MConfig

View CSAF Summary ABB became aware of an internally discovered vulnerability in the MConfig product versions listed as affected in the advisory. An attacker with access to local networks who successfully exploits vulnerability could have access to application’s sensitive information. ABB strongly advises customers to update MConfig with latest software version. The following versions of ABB LVS MConfig are affected:…
Read full source summary
View CSAF Summary ABB became aware of an internally discovered vulnerability in the MConfig product versions listed as affected in the advisory. An attacker with access to local networks who successfully exploits vulnerability could have access to application’s sensitive information. ABB strongly advises customers to update MConfig with latest software version. The following versions of ABB LVS MConfig are affected: LVS <=1.4.9.21 CVSS Vendor Equipment Vulnerabilities v3 7.4 ABB ABB LVS MConfig Cleartext Storage of Sensitive Information in Memory Background Critical Infrastructure Sectors: Chemical, Critical Manufacturing, Energy, Food and Agriculture, Transportation Systems, Water and Wastewater Countries/Areas Deployed: Worldwide Company Headquarters Location: Switzerland Vulnerabilities Expand All + CVE-2025-9970 During the runtime of the MConfig Software application, an attacker can export the memory dump file into the operating system. If passwords are stored in plain text in memory, they will be included in these dump files. If such dump files are mishandled, attackers could obtain them and extract the passwords. View CVE Details Affected Products ABB LVS MConfig Vendor: ABB Product Version: MConfig Version <=1.4.9.21 Product Status: fixed, known_affected Remediations Vendor fix The vulnerability is resolved in the following product versions: MConfig version 1.4.9.22 ABB advises users to update their devices to the latest software version. Additionally, ABB recommends implementing defensive measures to reduce the risk of vulnerability exploitation, as outlined in the product instruction manual. Please refer to the section “Mitigation factors” for more information Relevant CWE: CWE-316 Cleartext Storage of Sensitive Information in Memory Metrics CVSS Version Base Score Base Severity Vector String 3.1 7.4 HIGH CVSS:3.1/AV:L/AC:H/PR:L/UI:R/S:C/C:L/I:H/A:H/E:P/RL:O/RC:C/CR:L/IR:L/AR:L Acknowledgments ABB PSIRT reported this vulnerability to CISA. Notice The information in this document is subject to change without notice, and should not be construed as a commitment by ABB. ABB provides no warranty, express or implied, including warranties of merchantability and fitness for a particular purpose, for the information contained in this document, and assumes no responsibility for any errors that may appear in this document. In no event shall ABB or any of its suppliers be liable for direct, indirect, special, incidental or consequential damages of any nature or kind arising from the use of this document, or from the use of any hardware or software described in this document, even if ABB or its suppliers have been advised of the possibility of such damages. This document and parts hereof must not be reproduced or copied without written permission from ABB, and the contents hereof must not be imparted to a third-party nor used for any unauthorized purpose. All rights to registrations and trademarks reside with their respective owners. Mitigating factors Mitigating factors describe conditions and circumstances that make an attack that exploits the vulnerability difficult or less likely to succeed. In case customer cannot upgrade the firmware or it is not feasible then please immediately apply mitigating factors mentioned in “General security recommendations”. Frequently asked questions What causes the vulnerability? The vulnerability is caused by code defect allowing the attacker to extract the sensitive information such as user credentials from memory dump of the application. Please refer to Vulnerability severity and details for further details. What is MConfig ? MConfig is the parameterizing software for ABB LV switchgear components such as motor and feeder controller, operation panel, temperature monitoring solutions and protocol converter. The components are physically installed in a low voltage switchgear located in switch rooms that require authority to access. To run this software on a host machine (computer), the operating system should be Win11 or later version. What might an attacker use the vulnerability to do? If the mentioned vulnerability has been successfully exploited by an attacker, this could allow the attacker to extract sensitive information such as user credentials. With user credentials and access to a host machine with MConfig installed, and access to the switch room with components installed in a switchgear, the attacker can modify the setting of the components potentially compromising its correct operation. How could an attacker exploit vulnerability? An attacker with host machine physical access could, after a user log into MConfig, exploit a vulnerability by exporting a memory dump during runtime, potentially exposing the user's password. Could vulnerability be exploited remotely? The vulnerability can only be exploited if an attacker has physical access to the host machine with MConfig software. What does the update do? MConfig version V1.4.9.22 update has fix for the vulnerability mentioned in Vulnerability severity and details section. The measures below were implemented to fix the vulnerability: • Clear any authentication-related memory data after a successful login. • Hash the passwords in SHA256 Legal Notice and Terms of Use This product is provided subject to this Notification (https://www.cisa.gov/notification) and this Privacy & Use policy (https://www.cisa.gov/privacy-policy). Recommended Practices CISA recommends users take defensive measures to minimize the exploitation risk of these vulnerabilities. Minimize network exposure for all control system devices and/or systems, and ensure they are not accessible from the internet. Locate control system networks and remote devices behind firewalls and isolate them from business networks. When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most recent version available. Also recognize VPN is only as secure as its connected devices. CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures. CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies. CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets. Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies. Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents. Advisory Conversion Disclaimer This ICSA is a verbatim republication of ABB PSIRT 4TZ00000006008 from a direct conversion of the vendor's Common Security Advisory Framework (CSAF) advisory. This is republished to CISA's website as a means of increasing visibility and is provided "as-is" for informational purposes only. CISA is not responsible for the editorial or technical accuracy of republished advisories and provides no warranties of any kind regarding any information contained within this advisory. Further, CISA does not endorse any commercial product or service. Please contact ABB PSIRT directly for any questions regarding this advisory. Revision History Initial Release Date: 2025-10-08 Date Revision Summary 2025-10-08 1 Initial version. 2026-05-26 2 Initial CISA Republication of ABB PSIRT 4TZ00000006008 advisory Legal Notice and Terms of Use
· CISA Cybersecurity Advisory

CISA Adds One Known Exploited Vulnerability to Catalog

CISA has added one new vulnerability to its Known Exploited Vulnerabilities (KEV) Catalog, based on evidence of active exploitation. CVE-2026-48172 LiteSpeed cPanel Plugin Privilege Escalation Vulnerability This type of vulnerability is a frequent attack vector for malicious cyber actors and poses significant risks to the federal enterprise. Binding Operational Directive (BOD) 22-01: Reducing the Significant Risk of…
Read full source summary
CISA has added one new vulnerability to its Known Exploited Vulnerabilities (KEV) Catalog, based on evidence of active exploitation. CVE-2026-48172 LiteSpeed cPanel Plugin Privilege Escalation Vulnerability This type of vulnerability is a frequent attack vector for malicious cyber actors and poses significant risks to the federal enterprise. Binding Operational Directive (BOD) 22-01: Reducing the Significant Risk of Known Exploited Vulnerabilities established the KEV Catalog as a living list of known Common Vulnerabilities and Exposures (CVEs) that carry significant risk to the federal enterprise. BOD 22-01 requires Federal Civilian Executive Branch (FCEB) agencies to remediate identified vulnerabilities by the due date to protect FCEB networks against active threats. See the BOD 22-01 Fact Sheet for more information. Although BOD 22-01 only applies to FCEB agencies, CISA strongly urges all organizations to reduce their exposure to cyberattacks by prioritizing timely remediation of KEV Catalog vulnerabilities as part of their vulnerability management practice. CISA will continue to add vulnerabilities to the catalog that meet the specified criteria.
· CISA Cybersecurity Advisory

ABB AC500 V2

View CSAF Summary ABB became aware of vulnerabilities in AC500 V2 listed as affected in the advisory. An attacker who successfully exploited this vulnerability could access fragments of Modbus telegrams that have been sent earlier by that PLC The following versions of ABB AC500 V2 are affected: AC500 V2 <=2.5.2, 2.5.3 CVSS Vendor Equipment Vulnerabilities v3 5.8 ABB ABB AC500 V2 Buffer Over-read Background Critical…
Read full source summary
View CSAF Summary ABB became aware of vulnerabilities in AC500 V2 listed as affected in the advisory. An attacker who successfully exploited this vulnerability could access fragments of Modbus telegrams that have been sent earlier by that PLC The following versions of ABB AC500 V2 are affected: AC500 V2 <=2.5.2, 2.5.3 CVSS Vendor Equipment Vulnerabilities v3 5.8 ABB ABB AC500 V2 Buffer Over-read Background Critical Infrastructure Sectors: Critical Manufacturing, Energy, Water and Wastewater Countries/Areas Deployed: Worldwide Company Headquarters Location: Switzerland Vulnerabilities Expand All + CVE-2025-7745 Sending unsupported function codes to the AC500 V2 Modbus server might result in invalid responses. Fragments of previous responses might be added to the end of the response. View CVE Details Affected Products ABB AC500 V2 Vendor: ABB Product Version: ABB AC500 V2 <=2.5.2 Product Status: fixed, known_affected Remediations Vendor fix The vulnerabilities have been resolved in the following product versions: AC500 V2 firmware version 2.5.3 (released in 2016) and later Relevant CWE: CWE-126 Buffer Over-read Metrics CVSS Version Base Score Base Severity Vector String 3.1 5.8 MEDIUM CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:C/C:L/I:N/A:N Acknowledgments Reid Wightman of Dragos. Inc reported these vulnerabilities to Schneider Electric. Notice The information in this document is subject to change without notice, and should not be construed as a commitment by ABB. ABB provides no warranty, express or implied, including warranties of merchantability and fitness for a particular purpose, for the information contained in this document, and assumes no responsibility for any errors that may appear in this document. In no event shall ABB or any of its suppliers be liable for direct, indirect, special, incidental or consequential damages of any nature or kind arising from the use of this document, or from the use of any hardware or software described in this document, even if ABB or its suppliers have been advised of the possibility of such damages. This document and parts hereof must not be reproduced or copied without written permission from ABB, and the contents hereof must not be imparted to a third party nor used for any unauthorized purpose. All rights to registrations and trademarks reside with their respective owners. Mitigating factors Mitigating factors describe conditions and circumstances that make an attack that exploits the vulnerability difficult or less likely to succeed. Regarding this vulnerability it is recommended to • Do not use the Modbus server for sending any sensitive data, as fragments might be accessible even after the initial sending of the response • Only use supported Modbus function codes, as invalid responses to unsupported function codes might have negative effects on the requesting Modbus client. Refer to section “General security recommendations” for further advise on how to keep your system secure. Legal Notice and Terms of Use This product is provided subject to this Notification (https://www.cisa.gov/notification) and this Privacy & Use policy (https://www.cisa.gov/privacy-policy). Recommended Practices CISA recommends users take defensive measures to minimize the exploitation risk of these vulnerabilities. Minimize network exposure for all control system devices and/or systems, and ensure they are not accessible from the internet. Locate control system networks and remote devices behind firewalls and isolate them from business networks. When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most recent version available. Also recognize VPN is only as secure as its connected devices. CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures. CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies. CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets. Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies. Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents. Advisory Conversion Disclaimer This ICSA is a verbatim republication of ABB PSIRT 3ADR011432 from a direct conversion of the vendor's Common Security Advisory Framework (CSAF) advisory. This is republished to CISA's website as a means of increasing visibility and is provided "as-is" for informational purposes only. CISA is not responsible for the editorial or technical accuracy of republished advisories and provides no warranties of any kind regarding any information contained within this advisory. Further, CISA does not endorse any commercial product or service. Please contact ABB PSIRT directly for any questions regarding this advisory. Revision History Initial Release Date: 2025-07-23 Date Revision Summary 2025-07-23 1 Initial version. 2026-05-22 2 Minor correction to the affected product version in the product tree. 2026-05-26 3 Initial CISA Republication of ABB PSIRT 3ADR011432 advisory Legal Notice and Terms of Use
· CISA Cybersecurity Advisory

ABB Terra AC

View CSAF Summary ABB is aware of vulnerabilities in the product versions listed as affected in the advisory. An attacker who successfully exploited this vulnerability could cause the pollution of heap memory which potentially takes remote control of the product and performs a write operation to the flash memory to alter the firmware behavior. The following versions of ABB Terra AC are affected: Terra AC wallbox…
Read full source summary
View CSAF Summary ABB is aware of vulnerabilities in the product versions listed as affected in the advisory. An attacker who successfully exploited this vulnerability could cause the pollution of heap memory which potentially takes remote control of the product and performs a write operation to the flash memory to alter the firmware behavior. The following versions of ABB Terra AC are affected: Terra AC wallbox (UL40/80A) <=1.8.32, 1.8.33 Terra AC wallbox (UL32A) <=1.8.2, 1.8.34 Terra AC wallbox (MID/ CE) <=1.8.32, 1.8.34 Terra AC wallbox (JP) <=1.8.2, 1.8.34 CVSS Vendor Equipment Vulnerabilities v3 6.8 ABB ABB Terra AC Heap-based Buffer Overflow Background Critical Infrastructure Sectors: Commercial Facilities, Critical Manufacturing, Energy, Transportation Systems Countries/Areas Deployed: Worldwide Company Headquarters Location: Switzerland Vulnerabilities Expand All + CVE-2025-5517 There is potential risk to pollute the memory when a specially crafted OCPP message may be sent to a target vulnerable charger by exploiting unencrypted communication to the Charging Station Management System (CSMS) or fully remotely from its CSMS server. View CVE Details Affected Products ABB Terra AC Vendor: ABB Product Version: ABB Terra AC wallbox (UL40/80A) <=1.8.32, ABB Terra AC wallbox (UL32A) <=1.8.2, ABB Terra AC wallbox (MID/ CE) Terra AC MID <=1.8.32, ABB Terra AC wallbox (JP) <=1.8.2 Product Status: fixed, known_affected Remediations Vendor fix The problem is corrected in the product versions listed as fixed in the advisory. Terra AC wallbox (UL40/80A) 1.8.33 Terra AC wallbox (UL32A) 1.8.34 Terra AC MID 1.8.34 Terra AC Juno CE 1.8.34 Terra AC PTB 1.8.33 Terra AC wallbox (JP) 1.8.34 Additionally, we strongly recommend not use unsafe mode(http) to connect your charger to your backend even though OCPP is allowed to do in this way, which absolutely could be attacked by malicious man or organization as a common knowledge. ABB recommends that customers apply the update at earliest convenience. Relevant CWE: CWE-122 Heap-based Buffer Overflow Metrics CVSS Version Base Score Base Severity Vector String 3.1 6.8 MEDIUM CVSS:3.1/AV:N/AC:H/PR:L/UI:N/S:U/C:N/I:H/A:H/E:P/RL:O/RC:C Acknowledgments Itai Shmueli of Saiflow reported this vulnerability to Schneider Electric. Notice The information in this document is subject to change without notice, and should not be construed as a commitment by ABB. ABB provides no warranty, express or implied, including warranties of merchantability and fitness for a particular purpose, for the information contained in this document, and assumes no responsibility for any errors that may appear in this document. In no event shall ABB or any of its suppliers be liable for direct, indirect, special, incidental or consequential damages of any nature or kind arising from the use of this document, or from the use of any hardware or software described in this document, even if ABB or its suppliers have been advised of the possibility of such damages. This document and parts hereof must not be reproduced or copied without written permission from ABB, and the contents hereof must not be imparted to a third party nor used for any unauthorized purpose. All rights to registrations and trademarks reside with their respective owners. Mitigating factors To attack with this kind of message, hackers must hijack CSMS (OCPP backends) first and then can send messages, OR the way to OCPP backend is unsafe itself (http) which can cause any kind of attack behavior and known as a common knowledge. Refer to section “General security recommendations” for further advise on how to keep your system secure. Workarounds Make sure OCPP backend that chargers are connected is strictly secured to avoid any kind of at-tack especially the communication relevant components. Use https(TLS) as basic communication foundation between charger and OCPP backend instead of http. Frequently asked questions What causes the vulnerability? The vulnerability is caused by firmware which it didn’t limit the length of OCPP field in certain case. What is Terra AC wallbox? Terra AC wallbox is a Level 2 Electric Vehicle charger. What might an attacker use the vulnerability to do? An attacker who successfully exploited this vulnerability could cause the affected system node to take control of the charger to response wrong messages, Denial-of-Service, compromised internal state, and possibly remote code execution. How could an attacker exploit the vulnerability? An attacker could try to exploit the vulnerability by sending a specially crafted OCPP message to chargers via OCPP backend(CSMS), which could be done remotely. This would require that the attacker has access to the system network and hijack the API of sending message OR hijack the network data directly if the charger is connected with unsafe http mode. Recommended practices help mitigate such attacks, see section Mitigating Factors above. Could the vulnerability be exploited remotely? Yes, an attacker who has network access to an affected system node could exploit this vulnerability. Can functional safety be affected by an exploit of this vulnerability? The charger potentially is running with unpredictable mode, including Denial-of-Service, compromised internal state, and possibly remote code execution. What does the update do? The update removes the vulnerability by modifying the validation rules of receiving data from OCPP backend. When this security advisory was issued, had this vulnerability been publicly disclosed? No, ABB received information about this vulnerability through responsible disclosure. When this security advisory was issued, had ABB received any reports that this vulnerability was being exploited? No, ABB had not received any information indicating that this vulnerability had been exploited when this security advisory was originally issued Legal Notice and Terms of Use This product is provided subject to this Notification (https://www.cisa.gov/notification) and this Privacy & Use policy (https://www.cisa.gov/privacy-policy). Recommended Practices CISA recommends users take defensive measures to minimize the exploitation risk of these vulnerabilities. Minimize network exposure for all control system devices and/or systems, and ensure they are not accessible from the internet. Locate control system networks and remote devices behind firewalls and isolate them from business networks. When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most recent version available. Also recognize VPN is only as secure as its connected devices. CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures. CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies. CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets. Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies. Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents. Advisory Conversion Disclaimer This ICSA is a verbatim republication of ABB PSIRT 9AKK108471A8948 from a direct conversion of the vendor's Common Security Advisory Framework (CSAF) advisory. This is republished to CISA's website as a means of increasing visibility and is provided "as-is" for informational purposes only. CISA is not responsible for the editorial or technical accuracy of republished advisories and provides no warranties of any kind regarding any information contained within this advisory. Further, CISA does not endorse any commercial product or service. Please contact ABB PSIRT directly for any questions regarding this advisory. Revision History Initial Release Date: 2025-10-20 Date Revision Summary 2025-10-20 1 Initial version. 2025-10-21 2 Final version 2026-05-26 3 Initial CISA Republication of ABB PSIRT 9AKK108471A8948 advisory Legal Notice and Terms of Use
· CISA Cybersecurity Advisory

ABB AbilityTM Zenon Remote Transport Vulnerability

View CSAF Summary ABB is aware of vulnerabilities in the product versions listed as affected in the advisory. The vulnerability enables unauthorized access to the Reboot OS function within the Remote Transport Service, allowing an attacker to trigger a system reboot without the required authentication. This functionality initiates a system reboot on the target machine. However, remote exploitation of this…
Read full source summary
View CSAF Summary ABB is aware of vulnerabilities in the product versions listed as affected in the advisory. The vulnerability enables unauthorized access to the Reboot OS function within the Remote Transport Service, allowing an attacker to trigger a system reboot without the required authentication. This functionality initiates a system reboot on the target machine. However, remote exploitation of this vulnerability is not feasible unless the attacker has already gained access to the network where the affected ABB Ability™ zenon system is deployed. At the time of writing, there is no evidence that this vulnerability is being actively exploited in the wild. The following versions of ABB AbilityTM Zenon Remote Transport Vulnerability are affected: AbilityTM zenon >=7.50|<=14 CVSS Vendor Equipment Vulnerabilities v3 7.5 ABB ABB AbilityTM Zenon Remote Transport Vulnerability Missing Authentication for Critical Function Background Critical Infrastructure Sectors: Chemical, Communications, Critical Manufacturing, Dams, Energy, Healthcare and Public Health, Information Technology, Water and Wastewater Countries/Areas Deployed: Worldwide Company Headquarters Location: Switzerland Vulnerabilities Expand All + CVE-2025-8754 In the default configuration of the ABB zenon software platform, the zensyssrv.exe service is set to start automatically. To utilize the Remote Transport Service, users are required to configure a password beforehand. However, a security vulnerability has been identified that enables unauthorized attackers to bypass authentication mechanisms and remotely initiate a system reboot without proper authorization View CVE Details Affected Products ABB AbilityTM Zenon Remote Transport Vulnerability Vendor: ABB Product Version: ABB Ability Zenon >=7.50|<=14 Product Status: known_affected Remediations Workaround • Restrict network access to systems with the ABB zenon Software Platform installed. - Ensure that access to a system is restricted by implementing access controls to minimize the risk of unauthorized access. • Assess the necessity of the ABB zenon Remote Transport functionality. - Ensure that if the Remote Transport functionality is not used, the zensyssrv.exe (ABB zenon System Service) is stopped or terminated. The zensyssrv.exe can also be stopped or terminated after authorized use to prevent this vulnerability. Relevant CWE: CWE-306 Missing Authentication for Critical Function Metrics CVSS Version Base Score Base Severity Vector String 3.1 7.5 HIGH CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H Acknowledgments ABB PSIRT reported this vulnerability to CISA. Notice The information in this document is subject to change without notice, and should not be construed as a commitment by ABB. ABB provides no warranty, express or implied, including warranties of merchantability and fitness for a particular purpose, for the information contained in this document, and assumes no responsibility for any errors that may appear in this document. In no event shall ABB or any of its suppliers be liable for direct, indirect, special, incidental or consequential damages of any nature or kind arising from the use of this document, or from the use of any hard-ware or software described in this document, even if ABB or its suppliers have been advised of the possibility of such damages. This document and parts hereof must not be reproduced or copied without written permission from ABB, and the contents hereof must not be imparted to a third party nor used for any unauthorized purpose. All rights to registrations and trademarks reside with their respective owners. Work around • Restrict network access to systems with the ABB zenon Software Platform installed. - Ensure that access to a system is restricted by implementing access controls to minimize the risk of unauthorized access. • Assess the necessity of the ABB zenon Remote Transport functionality. - Ensure that if the Remote Transport functionality is not used, the zensyssrv.exe (ABB zenon System Service) is stopped or terminated. The zensyssrv.exe can also be stopped or terminated after authorized use to prevent this vulnerability. Legal Notice and Terms of Use This product is provided subject to this Notification (https://www.cisa.gov/notification) and this Privacy & Use policy (https://www.cisa.gov/privacy-policy). Recommended Practices CISA recommends users take defensive measures to minimize the exploitation risk of these vulnerabilities. Minimize network exposure for all control system devices and/or systems, and ensure they are not accessible from the internet. Locate control system networks and remote devices behind firewalls and isolate them from business networks. When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most recent version available. Also recognize VPN is only as secure as its connected devices. CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures. CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies. CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets. Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies. Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents. Advisory Conversion Disclaimer This ICSA is a verbatim republication of ABB PSIRT 2NGA002743 from a direct conversion of the vendor's Common Security Advisory Framework (CSAF) advisory. This is republished to CISA's website as a means of increasing visibility and is provided "as-is" for informational purposes only. CISA is not responsible for the editorial or technical accuracy of republished advisories and provides no warranties of any kind regarding any information contained within this advisory. Further, CISA does not endorse any commercial product or service. Please contact ABB PSIRT directly for any questions regarding this advisory. Revision History Initial Release Date: 2025-08-12 Date Revision Summary 2025-08-12 1 Initial version. 2026-05-26 2 Initial CISA Republication of ABB PSIRT 2NGA002743 advisory Legal Notice and Terms of Use
· CISA Cybersecurity Advisory

CISA Adds One Known Exploited Vulnerability to Catalog

CISA has added one new vulnerability to its Known Exploited Vulnerabilities (KEV) Catalog, based on evidence of active exploitation. CVE-2026-9082 Drupal Core SQL Injection Vulnerability This type of vulnerability is a frequent attack vector for malicious cyber actors and poses significant risks to the federal enterprise. Binding Operational Directive (BOD) 22-01: Reducing the Significant Risk of Known Exploited…
Read full source summary
CISA has added one new vulnerability to its Known Exploited Vulnerabilities (KEV) Catalog, based on evidence of active exploitation. CVE-2026-9082 Drupal Core SQL Injection Vulnerability This type of vulnerability is a frequent attack vector for malicious cyber actors and poses significant risks to the federal enterprise. Binding Operational Directive (BOD) 22-01: Reducing the Significant Risk of Known Exploited Vulnerabilities established the KEV Catalog as a living list of known Common Vulnerabilities and Exposures (CVEs) that carry significant risk to the federal enterprise. BOD 22-01 requires Federal Civilian Executive Branch (FCEB) agencies to remediate identified vulnerabilities by the due date to protect FCEB networks against active threats. See the BOD 22-01 Fact Sheet for more information. Although BOD 22-01 only applies to FCEB agencies, CISA strongly urges all organizations to reduce their exposure to cyberattacks by prioritizing timely remediation of KEV Catalog vulnerabilities as part of their vulnerability management practice. CISA will continue to add vulnerabilities to the catalog that meet the specified criteria.
· CISA Cybersecurity Advisory

CISA Adds Two Known Exploited Vulnerabilities to Catalog

CISA has added two new vulnerabilities to its Known Exploited Vulnerabilities (KEV) Catalog, based on evidence of active exploitation. CVE-2025-34291 Langflow Origin Validation Error Vulnerability CVE-2026-34926 Trend Micro Apex One (On-Premise) Directory Traversal Vulnerability These types of vulnerabilities are frequent attack vectors for malicious cyber actors and pose significant risks to the federal enterprise.…
Read full source summary
CISA has added two new vulnerabilities to its Known Exploited Vulnerabilities (KEV) Catalog, based on evidence of active exploitation. CVE-2025-34291 Langflow Origin Validation Error Vulnerability CVE-2026-34926 Trend Micro Apex One (On-Premise) Directory Traversal Vulnerability These types of vulnerabilities are frequent attack vectors for malicious cyber actors and pose significant risks to the federal enterprise. Binding Operational Directive (BOD) 22-01: Reducing the Significant Risk of Known Exploited Vulnerabilities established the KEV Catalog as a living list of known Common Vulnerabilities and Exposures (CVEs) that carry significant risk to the federal enterprise. BOD 22-01 requires Federal Civilian Executive Branch (FCEB) agencies to remediate identified vulnerabilities by the due date to protect FCEB networks against active threats. See the BOD 22-01 Fact Sheet for more information. Although BOD 22-01 only applies to FCEB agencies, CISA strongly urges all organizations to reduce their exposure to cyberattacks by prioritizing timely remediation of KEV Catalog vulnerabilities as part of their vulnerability management practice. CISA will continue to add vulnerabilities to the catalog that meet the specified criteria.
· CISA Cybersecurity Advisory

ABB B&R Automation Runtime

View CSAF Summary An update is available that resolves a vulnerability identified by B&Rs internal security analysis in the product versions listed as affected in this advisory. An attacker who successfully exploited these vulnerabilities could take over a remote session or execute code in the context of the user’s browser session. The following versions of ABB B&R Automation Runtime are affected: Automation Runtime…
Read full source summary
View CSAF Summary An update is available that resolves a vulnerability identified by B&Rs internal security analysis in the product versions listed as affected in this advisory. An attacker who successfully exploited these vulnerabilities could take over a remote session or execute code in the context of the user’s browser session. The following versions of ABB B&R Automation Runtime are affected: Automation Runtime <6.4, 6.4 (CVE-2025-3449, CVE-2025-3448, CVE-2025-11498) CVSS Vendor Equipment Vulnerabilities v3 6.1 B&R ABB B&R Automation Runtime Generation of Predictable Numbers or Identifiers, Improper Neutralization of Input During Web Page Generation ('Cross-site Scripting'), Improper Neutralization of Formula Elements in a CSV File Background Critical Infrastructure Sectors: Energy Countries/Areas Deployed: Worldwide Company Headquarters Location: Switzerland Vulnerabilities Expand All + CVE-2025-3449 A Generation of Predictable Numbers or Identifiers vulnerability in the SDM component of B&R Automation Runtime versions before 6.4 may allow an unauthenticated network-based attacker to take over already established sessions. View CVE Details Affected Products ABB B&R Automation Runtime Vendor: B&R Product Version: Automation Runtime <6.4 Product Status: fixed, known_affected Remediations Vendor fix The problem is corrected in Automation Runtime 6.4. The System Diagnostic Manager (SDM) is disabled by default in Automation Runtime 6 and is not intended be enabled on active systems located outside properly secured production networks or in facilities lacking adequate physical and logical access controls to prevent any form of unauthorized interaction. For customers who use SDM on their systems, B&R recommends applying the update based on risk assessment at the earliest convenience. The process to install updates is described in the user manual. The step to identify the installed product version is described in the user manual. Relevant CWE: CWE-340 Generation of Predictable Numbers or Identifiers Metrics CVSS Version Base Score Base Severity Vector String 3.1 4.2 MEDIUM CVSS:3.1/AV:N/AC:H/PR:N/UI:R/S:U/C:L/I:L/A:N/E:F/RL:O/RC:C CVE-2025-3448 Reflected cross-site scripting (XSS) vulnerabilities exist in System Diagnostics Manager (SDM) of B&R Automation Runtime versions before 6.4 that enables a remote attacker to execute arbitrary JavaScript code in the context of the attacked user’s browser session View CVE Details Affected Products ABB B&R Automation Runtime Vendor: B&R Product Version: Automation Runtime <6.4 Product Status: fixed, known_affected Remediations Vendor fix The problem is corrected in Automation Runtime 6.4. The System Diagnostic Manager (SDM) is disabled by default in Automation Runtime 6 and is not intended be enabled on active systems located outside properly secured production networks or in facilities lacking adequate physical and logical access controls to prevent any form of unauthorized interaction. For customers who use SDM on their systems, B&R recommends applying the update based on risk assessment at the earliest convenience. The process to install updates is described in the user manual. The step to identify the installed product version is described in the user manual. Relevant CWE: CWE-79 Improper Neutralization of Input During Web Page Generation ('Cross-site Scripting') Metrics CVSS Version Base Score Base Severity Vector String 3.1 6.1 MEDIUM CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:C/C:L/I:L/A:N/E:F/RC:C CVE-2025-11498 An Improper Neutralization of Formula Elements in a CSV File vulnerability exists in System Diagnostics Manager (SDM) of B&R Automation Runtime versions before 6.4 enabling a remote attacker to inject formula data into a generated CSV file. The exploitation of this vulnerability requires the attack-er to create a malicious link. The user would need to click on this link, after which the resulting CSV file additionally needs to be manually opened. View CVE Details Affected Products ABB B&R Automation Runtime Vendor: B&R Product Version: Automation Runtime <6.4 Product Status: fixed, known_affected Remediations Vendor fix The problem is corrected in Automation Runtime 6.4. The System Diagnostic Manager (SDM) is disabled by default in Automation Runtime 6 and is not intended be enabled on active systems located outside properly secured production networks or in facilities lacking adequate physical and logical access controls to prevent any form of unauthorized interaction. For customers who use SDM on their systems, B&R recommends applying the update based on risk assessment at the earliest convenience. The process to install updates is described in the user manual. The step to identify the installed product version is described in the user manual. Relevant CWE: CWE-1236 Improper Neutralization of Formula Elements in a CSV File Metrics CVSS Version Base Score Base Severity Vector String 3.1 6.1 MEDIUM CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:C/C:L/I:L/A:N/RL:O/RC:C Acknowledgments ABB PSIRT reported these vulnerabilities to CISA. Notice The information in this document is subject to change without notice, and should not be construed as a commitment by B&R. B&R provides no warranty, express or implied, including warranties of merchantability and fitness for a particular purpose, for the information contained in this document, and assumes no responsibility for any errors that may appear in this document. In no event shall B&R or any of its suppliers be liable for direct, indirect, special, incidental or consequential damages of any nature or kind arising from the use of this document, or from the use of any hardware or software described in this document, even if B&R or its suppliers have been advised of the possibility of such damages. This document and parts hereof must not be reproduced or copied without written permission from B&R, and the contents hereof must not be imparted to a third party nor used for any unauthorized purpose. All rights to registrations and trademarks reside with their respective owners. Mitigating factors Do not enable the System Diagnostics Manager when it is not required. Refer to section “General security recommendations” for further advise on how to keep your system secure. Workarounds Do not use Hyperlinks provided by untrusted 3rd party to access the SDM. Hyperlinks may be provided via: • Emails from unknown users • Social media channels • Messaging services • Webpages with comment functionality • QR Codes The use of external Web Application Firewalls (WAF) can mitigate attacks using reflected cross-site scripting. Frequently asked questions What causes the vulnerabilities? The vulnerabilities are caused by insufficient input sanitization and generation of predictable numbers. What is System Diagnostics Manager (SDM)? System Diagnostics Manager (SDM) is a webpage available over the Automation Runtime Webserver, showing key diagnostic information of the running controller. What is Automation Runtime (AR)? B&R Automation Runtime is a middleware system enabling customers to run applications on B&R target systems. What might an attacker use the vulnerabilities to do? An attacker who successfully exploited these vulnerabilities could cause to run arbitrary code in the context of the user’s browser session or take over the user’s session. Since the SDM currently does not process any session-specific data and also does not implement authentication mechanisms at the session level, B&R is not aware of any advantages an attacker could gain by taking over the session ID How could an attacker exploit the vulnerabilities? To exploit the XSS vulnerability CVE-2025-3448, an attacker could try to create a hyperlink including malicious script code. This hyperlink must be opened by the user to launch the attack. To exploit vulnerability CVE-2025-3449, an attacker would need to guess a user's session ID. Could the vulnerabilities be exploited remotely? Yes, an attacker who has network access to an affected system node could exploit this vulnerability. Recommended practices include that process control systems are physically protected, have no direct connections to the Internet, and are separated from other networks by means of a firewall system that has a minimal number of ports exposed. When this security advisory was issued, had this vulnerability been publicly disclosed? No, B&R discovered the vulnerabilities through its own security analysis. When this security advisory was issued, had B&R received any reports that this vulnerability was being exploited? No, B&R had not received any information indicating that this vulnerability had been exploited when this security advisory was originally issued. Legal Notice and Terms of Use This product is provided subject to this Notification (https://www.cisa.gov/notification) and this Privacy & Use policy (https://www.cisa.gov/privacy-policy). Recommended Practices CISA recommends users take defensive measures to minimize the exploitation risk of this vulnerability. Minimize network exposure for all control system devices and/or systems, and ensure they are not accessible from the internet. Locate control system networks and remote devices behind firewalls and isolate them from business networks. When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most recent version available. Also recognize VPN is only as secure as its connected devices. CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures. CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies. CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets. Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies. Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents. Advisory Conversion Disclaimer This ICSA is a verbatim republication of ABB PSIRT SA25P003 from a direct conversion of the vendor's Common Security Advisory Framework (CSAF) advisory. This is republished to CISA's website as a means of increasing visibility and is provided "as-is" for informational purposes only. CISA is not responsible for the editorial or technical accuracy of republished advisories and provides no warranties of any kind regarding any information contained within this advisory. Further, CISA does not endorse any commercial product or service. Please contact ABB PSIRT directly for any questions regarding this advisory. Revision History Initial Release Date: 2025-10-07 Date Revision Summary 2025-10-07 1 Initial version. 2025-10-14 2 Added information about CVE-2025-11498 2026-05-21 3 Initial CISA Republication of ABB PSIRT SA25P003 advisory Legal Notice and Terms of Use
· CISA Cybersecurity Advisory

ABB B&R Automation Studio

View CSAF Summary ABB became aware of vulnerability in the product versions listed as affected in the advisory. An update is available that replaces an outdated third-party component. Although no successful exploitation was observed during testing of the affected B&R products, the identified vulnerabilities could present potential attack vectors that might enable unauthorized access, data exposure, or remote code…
Read full source summary
View CSAF Summary ABB became aware of vulnerability in the product versions listed as affected in the advisory. An update is available that replaces an outdated third-party component. Although no successful exploitation was observed during testing of the affected B&R products, the identified vulnerabilities could present potential attack vectors that might enable unauthorized access, data exposure, or remote code execution. The following versions of ABB B&R Automation Studio are affected: B&R Automation Studio <6.5, 6.5 (CVE-2025-6965, CVE-2025-3277, CVE-2023-7104, CVE-2022-35737, CVE-2020-15358, CVE-2020-13632, CVE-2020-13631, CVE-2020-13630, CVE-2020-13435, CVE-2020-13434, CVE-2020-11656, CVE-2020-11655, CVE-2019-19646, CVE-2019-19645, CVE-2019-8457, CVE-2018-20506, CVE-2018-20505, CVE-2018-20346, CVE-2018-8740, CVE-2017-10989, CVE-2016-6153, CVE-2015-6607, CVE-2015-5895, CVE-2015-3717, CVE-2015-3416) CVSS Vendor Equipment Vulnerabilities v3 9.8 ABB ABB B&R Automation Studio Numeric Truncation Error, Heap-based Buffer Overflow, Improper Restriction of Operations within the Bounds of a Memory Buffer, Out-of-bounds Write, NULL Pointer Dereference, Incorrect User Management, Use After Free, Integer Overflow or Wraparound, Improper Check for Unusual or Exceptional Conditions, Uncontrolled Recursion, Out-of-bounds Read, Improper Input Validation, Exposure of Sensitive Information to an Unauthorized Actor, Buffer Copy without Checking Size of Input ('Classic Buffer Overflow') Background Critical Infrastructure Sectors: Energy Countries/Areas Deployed: Worldwide Company Headquarters Location: Switzerland Vulnerabilities Expand All + CVE-2025-6965 There exists a vulnerability in SQLite versions before 3.50.2 where the number of aggregate terms could exceed the number of columns available. This could lead to a memory corruption issue. View CVE Details Affected Products ABB B&R Automation Studio Vendor: ABB Product Version: ABB B&R Automation Studio <6.5 Product Status: fixed, known_affected Remediations Vendor fix The problem is corrected in the following product versions: B&R Automation Studio 6.5 B&R recommends that customers apply the update at earliest convenience. The process to install updates is described in the user manual. The step to identify the installed product version is described in the user manual. Mitigation Refer to section “General security recommendations” for advice on how to keep your system secure. Relevant CWE: CWE-197 Numeric Truncation Error Metrics CVSS Version Base Score Base Severity Vector String 3.1 9.8 CRITICAL CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H/E:P/RL:O/RC:C CVE-2025-3277 An integer overflow vulnerability exists in SQLite's concat_ws() function that can lead to a massive heap buffer overflow. When triggered, the integer overflow results in a truncated size value being used for buffer allocation, while the original untruncated size is used for writing the resulting string, causing a heap buffer overflow of approximately 4GB. View CVE Details Affected Products ABB B&R Automation Studio Vendor: ABB Product Version: ABB B&R Automation Studio <6.5 Product Status: fixed, known_affected Remediations Vendor fix The problem is corrected in the following product versions: B&R Automation Studio 6.5 B&R recommends that customers apply the update at earliest convenience. The process to install updates is described in the user manual. The step to identify the installed product version is described in the user manual. Mitigation Refer to section “General security recommendations” for advice on how to keep your system secure. Relevant CWE: CWE-122 Heap-based Buffer Overflow Metrics CVSS Version Base Score Base Severity Vector String 3.1 9.8 CRITICAL CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H/E:P/RL:O/RC:C CVE-2023-7104 A vulnerability was found in SQLite SQLite3 up to 3.43.0 and classified as critical. This issue affects the function sessionReadRecord of the file ext/session/sqlite3session.c of the component make alltest Handler. The manipulation leads to heap-based buffer overflow. View CVE Details Affected Products ABB B&R Automation Studio Vendor: ABB Product Version: ABB B&R Automation Studio <6.5 Product Status: fixed, known_affected Remediations Vendor fix The problem is corrected in the following product versions: B&R Automation Studio 6.5 B&R recommends that customers apply the update at earliest convenience. The process to install updates is described in the user manual. The step to identify the installed product version is described in the user manual. Mitigation Refer to section “General security recommendations” for advice on how to keep your system secure. Relevant CWE: CWE-122 Heap-based Buffer Overflow Metrics CVSS Version Base Score Base Severity Vector String 3.1 7.3 HIGH CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:L/A:L/E:P/RL:O/RC:C CVE-2022-35737 SQLite 1.0.12 through 3.39.x before 3.39.2 sometimes allows an array-bounds overflow if billions of bytes are used in a string argument to a C API. View CVE Details Affected Products ABB B&R Automation Studio Vendor: ABB Product Version: ABB B&R Automation Studio <6.5 Product Status: fixed, known_affected Remediations Vendor fix The problem is corrected in the following product versions: B&R Automation Studio 6.5 B&R recommends that customers apply the update at earliest convenience. The process to install updates is described in the user manual. The step to identify the installed product version is described in the user manual. Mitigation Refer to section “General security recommendations” for advice on how to keep your system secure. Relevant CWE: CWE-119 Improper Restriction of Operations within the Bounds of a Memory Buffer Metrics CVSS Version Base Score Base Severity Vector String 3.1 7.5 HIGH CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H/E:P/RL:O/RC:C CVE-2020-15358 In SQLite before 3.32.3, select.c mishandles query-flattener optimization, leading to a multiSelectOrderBy heap overflow because of misuse of transitive properties for constant propagation. View CVE Details Affected Products ABB B&R Automation Studio Vendor: ABB Product Version: ABB B&R Automation Studio <6.5 Product Status: fixed, known_affected Remediations Vendor fix The problem is corrected in the following product versions: B&R Automation Studio 6.5 B&R recommends that customers apply the update at earliest convenience. The process to install updates is described in the user manual. The step to identify the installed product version is described in the user manual. Mitigation Refer to section “General security recommendations” for advice on how to keep your system secure. Relevant CWE: CWE-787 Out-of-bounds Write Metrics CVSS Version Base Score Base Severity Vector String 3.1 5.5 MEDIUM CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H/E:P/RL:O/RC:C CVE-2020-13632 There exists a vulnerability in SQLite versions before 3.50.2 where the number of aggregate terms could exceed the number of columns available. This could lead to a memory corruption issue. View CVE Details Affected Products ABB B&R Automation Studio Vendor: ABB Product Version: ABB B&R Automation Studio <6.5 Product Status: fixed, known_affected Remediations Vendor fix The problem is corrected in the following product versions: B&R Automation Studio 6.5 B&R recommends that customers apply the update at earliest convenience. The process to install updates is described in the user manual. The step to identify the installed product version is described in the user manual. Mitigation Refer to section “General security recommendations” for advice on how to keep your system secure. Relevant CWE: CWE-476 NULL Pointer Dereference Metrics CVSS Version Base Score Base Severity Vector String 3.0 5.5 MEDIUM CVSS:3.0/AV:L/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H/E:P/RL:O/RC:C CVE-2020-13631 SQLite before 3.32.0 allows a virtual table to be renamed to the name of one of its shadow tables, related to alter.c and build.c. View CVE Details Affected Products ABB B&R Automation Studio Vendor: ABB Product Version: ABB B&R Automation Studio <6.5 Product Status: fixed, known_affected Remediations Vendor fix The problem is corrected in the following product versions: B&R Automation Studio 6.5 B&R recommends that customers apply the update at earliest convenience. The process to install updates is described in the user manual. The step to identify the installed product version is described in the user manual. Mitigation Refer to section “General security recommendations” for advice on how to keep your system secure. Relevant CWE: CWE-286 Incorrect User Management Metrics CVSS Version Base Score Base Severity Vector String 3.1 5.5 MEDIUM CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:N/I:H/A:N/E:P/RL:O/RC:C CVE-2020-13630 ext/fts3/fts3.c in SQLite before 3.32.0 has a use-after-free in fts3EvalNextRow, related to the snippet feature. View CVE Details Affected Products ABB B&R Automation Studio Vendor: ABB Product Version: ABB B&R Automation Studio <6.5 Product Status: fixed, known_affected Remediations Vendor fix The problem is corrected in the following product versions: B&R Automation Studio 6.5 B&R recommends that customers apply the update at earliest convenience. The process to install updates is described in the user manual. The step to identify the installed product version is described in the user manual. Mitigation Refer to section “General security recommendations” for advice on how to keep your system secure. Relevant CWE: CWE-416 Use After Free Metrics CVSS Version Base Score Base Severity Vector String 3.0 7 HIGH CVSS:3.0/AV:L/AC:H/PR:L/UI:N/S:U/C:H/I:H/A:H/E:P/RL:O/RC:C CVE-2020-13435 SQLite through 3.32.0 has a segmentation fault in sqlite3ExprCodeTarget in expr.c. View CVE Details Affected Products ABB B&R Automation Studio Vendor: ABB Product Version: ABB B&R Automation Studio <6.5 Product Status: fixed, known_affected Remediations Vendor fix The problem is corrected in the following product versions: B&R Automation Studio 6.5 B&R recommends that customers apply the update at earliest convenience. The process to install updates is described in the user manual. The step to identify the installed product version is described in the user manual. Mitigation Refer to section “General security recommendations” for advice on how to keep your system secure. Relevant CWE: CWE-476 NULL Pointer Dereference Metrics CVSS Version Base Score Base Severity Vector String 3.1 7.5 HIGH CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H/E:P/RL:O/RC:C CVE-2020-13434 SQLite through 3.32.0 has an integer overflow in sqlite3_str_vappendf in printf.c. View CVE Details Affected Products ABB B&R Automation Studio Vendor: ABB Product Version: ABB B&R Automation Studio <6.5 Product Status: fixed, known_affected Remediations Vendor fix The problem is corrected in the following product versions: B&R Automation Studio 6.5 B&R recommends that customers apply the update at earliest convenience. The process to install updates is described in the user manual. The step to identify the installed product version is described in the user manual. Mitigation Refer to section “General security recommendations” for advice on how to keep your system secure. Relevant CWE: CWE-190 Integer Overflow or Wraparound Metrics CVSS Version Base Score Base Severity Vector String 3.0 5.5 MEDIUM CVSS:3.0/AV:L/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H/E:P/RL:O/RC:C CVE-2020-11656 In SQLite through 3.31.1, the ALTER TABLE implementation has a use-after-free, as demonstrated by an ORDER BY clause that belongs to a compound SELECT statement. View CVE Details Affected Products ABB B&R Automation Studio Vendor: ABB Product Version: ABB B&R Automation Studio <6.5 Product Status: fixed, known_affected Remediations Vendor fix The problem is corrected in the following product versions: B&R Automation Studio 6.5 B&R recommends that customers apply the update at earliest convenience. The process to install updates is described in the user manual. The step to identify the installed product version is described in the user manual. Mitigation Refer to section “General security recommendations” for advice on how to keep your system secure. Relevant CWE: CWE-416 Use After Free Metrics CVSS Version Base Score Base Severity Vector String 3.1 7.5 HIGH CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H/E:P/RL:O/RC:C CVE-2020-11655 SQLite through 3.31.1 allows attackers to cause a denial of service (segmentation fault) via a malformed window-function query because the AggInfo object's initialization is mishandled. View CVE Details Affected Products ABB B&R Automation Studio Vendor: ABB Product Version: ABB B&R Automation Studio <6.5 Product Status: fixed, known_affected Remediations Vendor fix The problem is corrected in the following product versions: B&R Automation Studio 6.5 B&R recommends that customers apply the update at earliest convenience. The process to install updates is described in the user manual. The step to identify the installed product version is described in the user manual. Mitigation Refer to section “General security recommendations” for advice on how to keep your system secure. Relevant CWE: CWE-754 Improper Check for Unusual or Exceptional Conditions Metrics CVSS Version Base Score Base Severity Vector String 3.1 7.5 HIGH CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H/E:P/RL:O/RC:C CVE-2019-19646 pragma.c in SQLite through 3.30.1 mishandles NOT NULL in an integrity_check PRAGMA command in certain cases of generated columns. View CVE Details Affected Products ABB B&R Automation Studio Vendor: ABB Product Version: ABB B&R Automation Studio <6.5 Product Status: fixed, known_affected Remediations Vendor fix The problem is corrected in the following product versions: B&R Automation Studio 6.5 B&R recommends that customers apply the update at earliest convenience. The process to install updates is described in the user manual. The step to identify the installed product version is described in the user manual. Mitigation Refer to section “General security recommendations” for advice on how to keep your system secure. Relevant CWE: CWE-754 Improper Check for Unusual or Exceptional Conditions Metrics CVSS Version Base Score Base Severity Vector String 3.1 9.8 CRITICAL CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H/E:P/RL:O/RC:C CVE-2019-19645 alter.c in SQLite through 3.30.1 allows attackers to trigger infinite recursion via certain types of self-referential views in conjunction with ALTER TABLE statements. View CVE Details Affected Products ABB B&R Automation Studio Vendor: ABB Product Version: ABB B&R Automation Studio <6.5 Product Status: fixed, known_affected Remediations Vendor fix The problem is corrected in the following product versions: B&R Automation Studio 6.5 B&R recommends that customers apply the update at earliest convenience. The process to install updates is described in the user manual. The step to identify the installed product version is described in the user manual. Mitigation Refer to section “General security recommendations” for advice on how to keep your system secure. Relevant CWE: CWE-674 Uncontrolled Recursion Metrics CVSS Version Base Score Base Severity Vector String 3.1 5.5 MEDIUM CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H/E:P/RL:O/RC:C CVE-2019-8457 SQLite3 from 3.6.0 to and including 3.27.2 is vulnerable to heap out-of-bound read in the rtreenode() function when handling invalid rtree tables. View CVE Details Affected Products ABB B&R Automation Studio Vendor: ABB Product Version: ABB B&R Automation Studio <6.5 Product Status: fixed, known_affected Remediations Vendor fix The problem is corrected in the following product versions: B&R Automation Studio 6.5 B&R recommends that customers apply the update at earliest convenience. The process to install updates is described in the user manual. The step to identify the installed product version is described in the user manual. Mitigation Refer to section “General security recommendations” for advice on how to keep your system secure. Relevant CWE: CWE-125 Out-of-bounds Read Metrics CVSS Version Base Score Base Severity Vector String 3.1 9.8 CRITICAL CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H/E:P/RL:O/RC:C CVE-2018-20506 SQLite before 3.25.3, when the FTS3 extension is enabled, encounters an integer overflow (and resultant buffer overflow) for FTS3 queries in a "merge" operation that occurs after crafted changes to FTS3 shadow tables, allow-ing remote attackers to execute arbitrary code by leveraging the ability to run arbitrary SQL statements (such as in certain WebSQL use cases). This is a different vulnerability than CVE-2018-20346. View CVE Details Affected Products ABB B&R Automation Studio Vendor: ABB Product Version: ABB B&R Automation Studio <6.5 Product Status: fixed, known_affected Remediations Vendor fix The problem is corrected in the following product versions: B&R Automation Studio 6.5 B&R recommends that customers apply the update at earliest convenience. The process to install updates is described in the user manual. The step to identify the installed product version is described in the user manual. Mitigation Refer to section “General security recommendations” for advice on how to keep your system secure. Relevant CWE: CWE-190 Integer Overflow or Wraparound Metrics CVSS Version Base Score Base Severity Vector String 3.0 8.1 HIGH CVSS:3.0/AV:N/AC:H/PR:N/UI:N/S:U/C:H/I:H/A:H/E:P/RL:O/RC:C CVE-2018-20505 SQLite 3.25.2, when queries are run on a table with a malformed PRIMARY KEY, allows remote attackers to cause a denial of service (application crash) by leveraging the ability to run arbitrary SQL statements (such as in certain WebSQL use cases). View CVE Details Affected Products ABB B&R Automation Studio Vendor: ABB Product Version: ABB B&R Automation Studio <6.5 Product Status: fixed, known_affected Remediations Vendor fix The problem is corrected in the following product versions: B&R Automation Studio 6.5 B&R recommends that customers apply the update at earliest convenience. The process to install updates is described in the user manual. The step to identify the installed product version is described in the user manual. Mitigation Refer to section “General security recommendations” for advice on how to keep your system secure. Relevant CWE: CWE-20 Improper Input Validation Metrics CVSS Version Base Score Base Severity Vector String 3.0 7.5 HIGH CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H/E:P/RL:O/RC:C CVE-2018-20346 SQLite before 3.25.3, when the FTS3 extension is enabled, encounters an integer overflow (and resultant buffer overflow) for FTS3 queries that occur after crafted changes to FTS3 shadow tables, allowing remote attackers to execute arbitrary code by leveraging the ability to run arbitrary SQL statements (such as in certain WebSQL use cases), aka Magellan. View CVE Details Affected Products ABB B&R Automation Studio Vendor: ABB Product Version: ABB B&R Automation Studio <6.5 Product Status: fixed, known_affected Remediations Vendor fix The problem is corrected in the following product versions: B&R Automation Studio 6.5 B&R recommends that customers apply the update at earliest convenience. The process to install updates is described in the user manual. The step to identify the installed product version is described in the user manual. Mitigation Refer to section “General security recommendations” for advice on how to keep your system secure. Relevant CWE: CWE-190 Integer Overflow or Wraparound Metrics CVSS Version Base Score Base Severity Vector String 3.0 8.1 HIGH CVSS:3.0/AV:N/AC:H/PR:N/UI:N/S:U/C:H/I:H/A:H/E:P/RL:O/RC:C CVE-2018-8740 In SQLite through 3.22.0, databases whose schema is corrupted using a CREATE TABLE AS statement could cause a NULL pointer dereference, related to build.c and prepare.c. View CVE Details Affected Products ABB B&R Automation Studio Vendor: ABB Product Version: ABB B&R Automation Studio <6.5 Product Status: fixed, known_affected Remediations Vendor fix The problem is corrected in the following product versions: B&R Automation Studio 6.5 B&R recommends that customers apply the update at earliest convenience. The process to install updates is described in the user manual. The step to identify the installed product version is described in the user manual. Mitigation Refer to section “General security recommendations” for advice on how to keep your system secure. Relevant CWE: CWE-476 NULL Pointer Dereference Metrics CVSS Version Base Score Base Severity Vector String 3.0 7.5 HIGH CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H/E:P/RL:O/RC:C CVE-2017-10989 The getNodeSize function in ext/rtree/rtree.c in SQLite through 3.19.3, as used in GDAL and other products, mis-handles undersized RTree blobs in a crafted database, leading to a heap-based buffer over-read or possibly un-specified other impact. View CVE Details Affected Products ABB B&R Automation Studio Vendor: ABB Product Version: ABB B&R Automation Studio <6.5 Product Status: fixed, known_affected Remediations Vendor fix The problem is corrected in the following product versions: B&R Automation Studio 6.5 B&R recommends that customers apply the update at earliest convenience. The process to install updates is described in the user manual. The step to identify the installed product version is described in the user manual. Mitigation Refer to section “General security recommendations” for advice on how to keep your system secure. Relevant CWE: CWE-125 Out-of-bounds Read Metrics CVSS Version Base Score Base Severity Vector String 3.0 9.8 CRITICAL CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H/E:P/RL:O/RC:C CVE-2016-6153 There exists a vulnerability in SQLite versions before 3.50.2 where the number of aggregate terms could exceed the number of columns available. This could lead to a memory corruption issue. View CVE Details Affected Products ABB B&R Automation Studio Vendor: ABB Product Version: ABB B&R Automation Studio <6.5 Product Status: fixed, known_affected Remediations Vendor fix The problem is corrected in the following product versions: B&R Automation Studio 6.5 B&R recommends that customers apply the update at earliest convenience. The process to install updates is described in the user manual. The step to identify the installed product version is described in the user manual. Mitigation Refer to section “General security recommendations” for advice on how to keep your system secure. Relevant CWE: CWE-20 Improper Input Validation Metrics CVSS Version Base Score Base Severity Vector String 3.0 5.9 MEDIUM CVSS:3.0/AV:L/AC:L/PR:N/UI:N/S:U/C:L/I:L/A:L/E:P/RL:O/RC:C CVE-2015-6607 SQLite before 3.8.9, as used in Android before 5.1.1 LMY48T, allows attackers to gain privileges via a crafted application, aka internal bug 20099586. View CVE Details Affected Products ABB B&R Automation Studio Vendor: ABB Product Version: ABB B&R Automation Studio <6.5 Product Status: fixed, known_affected Remediations Vendor fix The problem is corrected in the following product versions: B&R Automation Studio 6.5 B&R recommends that customers apply the update at earliest convenience. The process to install updates is described in the user manual. The step to identify the installed product version is described in the user manual. Mitigation Refer to section “General security recommendations” for advice on how to keep your system secure. Relevant CWE: CWE-286 Incorrect User Management Metrics CVSS Version Base Score Base Severity Vector String 3.0 3.7 LOW CVSS:3.0/AV:N/AC:H/PR:N/UI:N/S:U/C:L/I:N/A:N/E:P/RL:O/RC:C CVE-2015-5895 Multiple unspecified vulnerabilities in SQLite before 3.8.10.2, as used in Apple iOS before 9, have unknown im-pact and attack vectors. View CVE Details Affected Products ABB B&R Automation Studio Vendor: ABB Product Version: ABB B&R Automation Studio <6.5 Product Status: fixed, known_affected Remediations Vendor fix The problem is corrected in the following product versions: B&R Automation Studio 6.5 B&R recommends that customers apply the update at earliest convenience. The process to install updates is described in the user manual. The step to identify the installed product version is described in the user manual. Mitigation Refer to section “General security recommendations” for advice on how to keep your system secure. Relevant CWE: CWE-200 Exposure of Sensitive Information to an Unauthorized Actor Metrics CVSS Version Base Score Base Severity Vector String 3.1 9.8 CRITICAL CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H/E:P/RL:O/RC:C CVE-2015-3717 Multiple buffer overflows in the printf functionality in SQLite, as used in Apple iOS before 8.4 and OS X before 10.10.4, allow remote attackers to execute arbitrary code or cause a denial of service (application crash) via un-specified vectors. View CVE Details Affected Products ABB B&R Automation Studio Vendor: ABB Product Version: ABB B&R Automation Studio <6.5 Product Status: fixed, known_affected Remediations Vendor fix The problem is corrected in the following product versions: B&R Automation Studio 6.5 B&R recommends that customers apply the update at earliest convenience. The process to install updates is described in the user manual. The step to identify the installed product version is described in the user manual. Mitigation Refer to section “General security recommendations” for advice on how to keep your system secure. Relevant CWE: CWE-120 Buffer Copy without Checking Size of Input ('Classic Buffer Overflow') Metrics CVSS Version Base Score Base Severity Vector String 3.0 7.5 HIGH CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H/E:P/RL:O/RC:C CVE-2015-3416 The sqlite3VXPrintf function in printf.c in SQLite before 3.8.9 does not properly handle precision and width values during floating-point conversions, which allows context-dependent attackers to cause a denial of service (integer overflow and stack-based buffer overflow) or possibly have unspecified other impact via large integers in a crafted printf function call in a SELECT statement. View CVE Details Affected Products ABB B&R Automation Studio Vendor: ABB Product Version: ABB B&R Automation Studio <6.5 Product Status: fixed, known_affected Remediations Vendor fix The problem is corrected in the following product versions: B&R Automation Studio 6.5 B&R recommends that customers apply the update at earliest convenience. The process to install updates is described in the user manual. The step to identify the installed product version is described in the user manual. Mitigation Refer to section “General security recommendations” for advice on how to keep your system secure. Relevant CWE: CWE-190 Integer Overflow or Wraparound Metrics CVSS Version Base Score Base Severity Vector String 3.0 7.8 HIGH CVSS:3.0/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H/E:P/RL:O/RC:C Acknowledgments ABB PSIRT reported these vulnerabilities to CISA. Notice The information in this document is subject to change without notice, and should not be construed as a commitment by B&R. B&R provides no warranty, express or implied, including warranties of merchantability and fitness for a particular purpose, for the information contained in this document, and assumes no responsibility for any errors that may appear in this document. In no event shall B&R or any of its suppliers be liable for direct, indirect, special, incidental or consequential damages of any nature or kind arising from the use of this document, or from the use of any hardware or software described in this document, even if B&R or its suppliers have been advised of the possibility of such damages. This document and parts hereof must not be reproduced or copied without written permission from B&R, and the contents hereof must not be imparted to a third party nor used for any unauthorized purpose. All rights to registrations and trademarks reside with their respective owners. Legal Notice and Terms of Use This product is provided subject to this Notification (https://www.cisa.gov/notification) and this Privacy & Use policy (https://www.cisa.gov/privacy-policy). Recommended Practices CISA recommends users take defensive measures to minimize the exploitation risk of this vulnerability. Minimize network exposure for all control system devices and/or systems, and ensure they are not accessible from the internet. Locate control system networks and remote devices behind firewalls and isolate them from business networks. When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most recent version available. Also recognize VPN is only as secure as its connected devices. CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures. CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies. CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets. Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies. Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents. Advisory Conversion Disclaimer This ICSA is a verbatim republication of ABB PSIRT SA25P007 from a direct conversion of the vendor's Common Security Advisory Framework (CSAF) advisory. This is republished to CISA's website as a means of increasing visibility and is provided "as-is" for informational purposes only. CISA is not responsible for the editorial or technical accuracy of republished advisories and provides no warranties of any kind regarding any information contained within this advisory. Further, CISA does not endorse any commercial product or service. Please contact ABB PSIRT directly for any questions regarding this advisory. Revision History Initial Release Date: 2026-02-18 Date Revision Summary 2026-02-18 1 Initial version. 2026-05-21 2 Initial CISA Republication of ABB PSIRT SA25P007 advisory Legal Notice and Terms of Use
· CISA Cybersecurity Advisory

Hitachi Energy GMS600

View CSAF Summary Hitachi Energy is aware of the vulnerability, CVE-2022-4304 in the OSS component OpenSSL, that affects the GMS600 versions that are listed below. An attacker successfully exploiting this vulnerability could send trial messages to the server and record the time taken to process them. After a sufficiently large number of messages the attacker could recover the pre-master secret used for the original…
Read full source summary
View CSAF Summary Hitachi Energy is aware of the vulnerability, CVE-2022-4304 in the OSS component OpenSSL, that affects the GMS600 versions that are listed below. An attacker successfully exploiting this vulnerability could send trial messages to the server and record the time taken to process them. After a sufficiently large number of messages the attacker could recover the pre-master secret used for the original connection and thus be able to decrypt the application data sent over that connection. For immediate mitigation /workaround information, please refer to the General Mitigation Factors/Workarounds The following versions of Hitachi Energy GMS600 are affected: GMS600 vers:GMS600/>=1.3.0|<=1.3.1 (CVE-2022-4304) CVSS Vendor Equipment Vulnerabilities v3 5.9 Hitachi Energy Hitachi Energy GMS600 Observable Discrepancy Background Critical Infrastructure Sectors: Critical Manufacturing Countries/Areas Deployed: Worldwide Company Headquarters Location: Switzerland Vulnerabilities Expand All + CVE-2022-4304 A timing-based side channel exists in the OpenSSL RSA Decryption implementation which could be sufficient to recover a plaintext across a network in a Bleichenbacher style attack. To achieve a successful decryption an attacker would have to be able to send a very large number of trial messages for decryption. The vulnerability affects all RSA padding modes: PKCS#1 v1.5, RSA-OEAP and RSASVE. For example, in a TLS connection, RSA is commonly used by a client to send an encrypted pre-master secret to the server. An attacker that had observed a genuine connection between a client and a server could use this flaw to send trial messages to the server and record the time taken to process them. After a sufficiently large number of messages the attacker could recover the pre-master secret used for the original connection and thus be able to decrypt the application data sent over that connection. View CVE Details Affected Products Hitachi Energy GMS600 Vendor: Hitachi Energy Product Version: GMS600 versions 1.3.0 and 1.3.1 Product Status: known_affected Remediations Vendor fix Upgrade to version 1.3.2 Relevant CWE: CWE-203 Observable Discrepancy Metrics CVSS Version Base Score Base Severity Vector String 3.1 5.9 MEDIUM CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:H/I:N/A:N Acknowledgments Hitachi Energy Internal Team reported this vulnerability to CISA Notice The information in this document is subject to change without notice and should not be construed as a commitment by Hitachi Energy. Hitachi Energy provides no warranty, express or implied, including warranties of merchantability and fitness for a particular purpose, for the information contained in this document, and assumes no responsibility for any errors that may appear in this document. In no event shall Hitachi Energy or any of its suppliers be liable for direct, indirect, special, incidental or consequential damages of any nature or kind arising from the use of this document, or from the use of any hardware or software described in this document, even if Hitachi Energy or its suppliers have been advised of the possibility of such damages. This document and parts hereof must not be reproduced or copied without written permission from Hitachi Energy and the contents hereof must not be imparted to a third party nor used for any unauthorized purpose. All rights to registrations and trademarks reside with their respective owners. Support For additional information and support please contact your product provider or Hitachi Energy service organization. For contact information, see https://www.hitachienergy.com/contact-us/ for Hitachi Energy contact-centers. General Mitigation Factors Recommended security practices and firewall configurations such as enforcing ingress IP allowlisting and applying traffic rate limiting in accordance with the operational security policy can help protect a process control network from attacks that originate from outside the network. Such practices include that process control systems are physically protected from direct access by unauthorized personnel, have no direct connections to the Internet, and are separated from other networks by means of a firewall system that has a minimal number of ports exposed, and others that have to be evaluated case by case. Process control systems should not be used for Internet surfing, instant messaging, or receiving e-mails. Portable computers and removable storage media should be carefully scanned for viruses before they are connected to a control system. SSVC SSVCv2/E:N/A:Y/2026-04-22T13:37:14Z/ Legal Notice and Terms of Use This product is provided subject to this Notification (https://www.cisa.gov/notification) and this Privacy & Use policy (https://www.cisa.gov/privacy-policy). Recommended Practices CISA recommends users take defensive measures to minimize the exploitation risk of these vulnerabilities. Minimize network exposure for all control system devices and/or systems, and ensure they are not accessible from the internet. Locate control system networks and remote devices behind firewalls and isolate them from business networks. When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most recent version available. Also recognize VPN is only as secure as its connected devices. CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures. CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies. CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets. Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies. Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents. Advisory Conversion Disclaimer This ICSA is a verbatim republication of Hitachi Energy PSIRT 8DBD000159 from a direct conversion of the vendor's Common Security Advisory Framework (CSAF) advisory. This is republished to CISA's website as a means of increasing visibility and is provided "as-is" for informational purposes only. CISA is not responsible for the editorial or technical accuracy of republished advisories and provides no warranties of any kind regarding any information contained within this advisory. Further, CISA does not endorse any commercial product or service. Please contact Hitachi Energy PSIRT directly for any questions regarding this advisory. Revision History Initial Release Date: 2023-06-27 Date Revision Summary 2023-06-27 1 Initial public release. 2026-04-28 2 Updated fixed version. 2026-05-21 3 Initial CISA Republication of Hitachi Energy PSIRT 8DBD000159 advisory Legal Notice and Terms of Use
· CISA Cybersecurity Advisory

ABB B&R PCs

View CSAF Summary ABB became aware of vulnerability in the product versions listed as affected in the advisory. An update is now available that addresses and remediates the vulnerability. A network attacker could exploit the vulnerabilities to execute remote code, initiate DoS attacks, conduct DNS cache poisoning, or extract sensitive information. The following versions of ABB B&R PCs are affected: APC4100 <1.09,…
Read full source summary
View CSAF Summary ABB became aware of vulnerability in the product versions listed as affected in the advisory. An update is now available that addresses and remediates the vulnerability. A network attacker could exploit the vulnerabilities to execute remote code, initiate DoS attacks, conduct DNS cache poisoning, or extract sensitive information. The following versions of ABB B&R PCs are affected: APC4100 <1.09, 1.09 (CVE-2023-45229, CVE-2023-45230, CVE-2023-45231, CVE-2023-45232, CVE-2023-45233, CVE-2023-45234, CVE-2023-45235, CVE-2023-45236, CVE-2023-45237) APC910 <=1.25 (CVE-2023-45229, CVE-2023-45230, CVE-2023-45231, CVE-2023-45232, CVE-2023-45233, CVE-2023-45234, CVE-2023-45235, CVE-2023-45236, CVE-2023-45237) C80 <1.14, 1.14 (CVE-2023-45229, CVE-2023-45230, CVE-2023-45231, CVE-2023-45232, CVE-2023-45233, CVE-2023-45234, CVE-2023-45235, CVE-2023-45236, CVE-2023-45237) MPC3100 <1.24, 1.24 (CVE-2023-45229, CVE-2023-45230, CVE-2023-45231, CVE-2023-45232, CVE-2023-45233, CVE-2023-45234, CVE-2023-45235, CVE-2023-45236, CVE-2023-45237) PPC1200 <1.14, 1.14 (CVE-2023-45229, CVE-2023-45230, CVE-2023-45231, CVE-2023-45232, CVE-2023-45233, CVE-2023-45234, CVE-2023-45235, CVE-2023-45236, CVE-2023-45237) PPC900 <2.16, 2.16 (CVE-2023-45229, CVE-2023-45230, CVE-2023-45231, CVE-2023-45232, CVE-2023-45233, CVE-2023-45234, CVE-2023-45235, CVE-2023-45236, CVE-2023-45237) APC2200 <1.35, 1.35 (CVE-2023-45229, CVE-2023-45230, CVE-2023-45231, CVE-2023-45232, CVE-2023-45233, CVE-2023-45234, CVE-2023-45235, CVE-2023-45236, CVE-2023-45237) PPC2200 <1.35, 1.35 (CVE-2023-45229, CVE-2023-45230, CVE-2023-45231, CVE-2023-45232, CVE-2023-45233, CVE-2023-45234, CVE-2023-45235, CVE-2023-45236, CVE-2023-45237) APC3100 <1.45, 1.45 (CVE-2023-45229, CVE-2023-45230, CVE-2023-45231, CVE-2023-45232, CVE-2023-45233, CVE-2023-45234, CVE-2023-45235, CVE-2023-45236, CVE-2023-45237) PPC3100 <1.45, 1.45 (CVE-2023-45229, CVE-2023-45230, CVE-2023-45231, CVE-2023-45232, CVE-2023-45233, CVE-2023-45234, CVE-2023-45235, CVE-2023-45236, CVE-2023-45237) CVSS Vendor Equipment Vulnerabilities v3 8.3 ABB ABB B&R PCs Out-of-bounds Read, Improper Restriction of Operations within the Bounds of a Memory Buffer, Loop with Unreachable Exit Condition ('Infinite Loop'), Use of Cryptographically Weak Pseudo-Random Number Generator (PRNG) Background Critical Infrastructure Sectors: Energy Countries/Areas Deployed: Worldwide Company Headquarters Location: Switzerland Vulnerabilities Expand All + CVE-2023-45229 EDK2's Network Package is susceptible to an out-of-bounds read vulnerability when processing the IA_NA or IA_TA option in a DHCPv6 Advertise message. This vulnerability can be exploited by an attacker to gain unauthorized access and potentially lead to a loss of Confidentiality. View CVE Details Affected Products ABB B&R PCs Vendor: ABB Product Version: ABB APC4100 <1.09, ABB APC910 <=1.25, ABB C80 <1.14, ABB MPC3100 <1.24, ABB PPC1200 <1.14, ABB PPC900 <2.16, ABB APC2200 <1.35, ABB PPC2200 <1.35, ABB APC3100 <1.45, ABB PPC3100 <1.45 Product Status: fixed, known_affected Remediations Vendor fix The problems are corrected in the following product versions: - APC4100 1.09 - APC910 No patch will be released (Please refer to the mitigation measures specified in this advisory). - C80 1.14 - MPC3100 1.24 - PPC1200 1.14 - PPC900 2.16 - APC2200 1.35 - PPC2200 1.35 - APC3100 1.45 - PPC3100 1.45 B&R recommends that customers apply the update at earliest convenience. The process to install updates is described in the user manual. The step to identify the installed product version is described in the user manual. Mitigation Deactivate the vulnerable component - The vulnerabilities exist in the Preboot eXecution Environment (PXE) of the UEFI firmware. If this functionality is not needed, it is recommended to disable it in the UEFI settings, thus making the vulnerabilities not exploitable. Limit accessibility - If PXE functionality is required, users should tightly restrict network traffic to legitimate users and block illegitimate PXE traffic, specifically related to IPv6. For instance, by blocking IPv6 network traffic on the control network firewall. https://help.br-automation.com/#/en/6/cyber-security/defense-in-depth-for-br-products/reference_architecture.html Refer to section “General security recommendations” for further advise on how to keep your system secure. Relevant CWE: CWE-125 Out-of-bounds Read Metrics CVSS Version Base Score Base Severity Vector String 3.1 6.5 MEDIUM CVSS:3.1/AV:A/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N/E:P/RL:O/RC:C CVE-2023-45230 EDK2's Network Package is susceptible to a buffer overflow vulnerability via a long server ID option in DHCPv6 client. This vulnerability can be exploited by an attacker to gain unauthorized access and potentially lead to a loss of Confidentiality, Integrity and/or Availability. View CVE Details Affected Products ABB B&R PCs Vendor: ABB Product Version: ABB APC4100 <1.09, ABB APC910 <=1.25, ABB C80 <1.14, ABB MPC3100 <1.24, ABB PPC1200 <1.14, ABB PPC900 <2.16, ABB APC2200 <1.35, ABB PPC2200 <1.35, ABB APC3100 <1.45, ABB PPC3100 <1.45 Product Status: fixed, known_affected Remediations Vendor fix The problems are corrected in the following product versions: - APC4100 1.09 - APC910 No patch will be released (Please refer to the mitigation measures specified in this advisory). - C80 1.14 - MPC3100 1.24 - PPC1200 1.14 - PPC900 2.16 - APC2200 1.35 - PPC2200 1.35 - APC3100 1.45 - PPC3100 1.45 B&R recommends that customers apply the update at earliest convenience. The process to install updates is described in the user manual. The step to identify the installed product version is described in the user manual. Mitigation Deactivate the vulnerable component - The vulnerabilities exist in the Preboot eXecution Environment (PXE) of the UEFI firmware. If this functionality is not needed, it is recommended to disable it in the UEFI settings, thus making the vulnerabilities not exploitable. Limit accessibility - If PXE functionality is required, users should tightly restrict network traffic to legitimate users and block illegitimate PXE traffic, specifically related to IPv6. For instance, by blocking IPv6 network traffic on the control network firewall. https://help.br-automation.com/#/en/6/cyber-security/defense-in-depth-for-br-products/reference_architecture.html Refer to section “General security recommendations” for further advise on how to keep your system secure. Relevant CWE: CWE-119 Improper Restriction of Operations within the Bounds of a Memory Buffer Metrics CVSS Version Base Score Base Severity Vector String 3.1 8.3 HIGH CVSS:3.1/AV:A/AC:L/PR:N/UI:N/S:U/C:H/I:L/A:H/E:P/RL:O/RC:C CVE-2023-45231 EDK2's Network Package is susceptible to an out-of-bounds read vulnerability when processing Neighbor Discovery Redirect message. This vulnerability can be exploited by an attacker to gain unauthorized access and potentially lead to a loss of Confidentiality. View CVE Details Affected Products ABB B&R PCs Vendor: ABB Product Version: ABB APC4100 <1.09, ABB APC910 <=1.25, ABB C80 <1.14, ABB MPC3100 <1.24, ABB PPC1200 <1.14, ABB PPC900 <2.16, ABB APC2200 <1.35, ABB PPC2200 <1.35, ABB APC3100 <1.45, ABB PPC3100 <1.45 Product Status: fixed, known_affected Remediations Vendor fix The problems are corrected in the following product versions: - APC4100 1.09 - APC910 No patch will be released (Please refer to the mitigation measures specified in this advisory). - C80 1.14 - MPC3100 1.24 - PPC1200 1.14 - PPC900 2.16 - APC2200 1.35 - PPC2200 1.35 - APC3100 1.45 - PPC3100 1.45 B&R recommends that customers apply the update at earliest convenience. The process to install updates is described in the user manual. The step to identify the installed product version is described in the user manual. Mitigation Deactivate the vulnerable component - The vulnerabilities exist in the Preboot eXecution Environment (PXE) of the UEFI firmware. If this functionality is not needed, it is recommended to disable it in the UEFI settings, thus making the vulnerabilities not exploitable. Limit accessibility - If PXE functionality is required, users should tightly restrict network traffic to legitimate users and block illegitimate PXE traffic, specifically related to IPv6. For instance, by blocking IPv6 network traffic on the control network firewall. https://help.br-automation.com/#/en/6/cyber-security/defense-in-depth-for-br-products/reference_architecture.html Refer to section “General security recommendations” for further advise on how to keep your system secure. Relevant CWE: CWE-125 Out-of-bounds Read Metrics CVSS Version Base Score Base Severity Vector String 3.1 6.5 MEDIUM CVSS:3.1/AV:A/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N/E:P/RL:O/RC:C CVE-2023-45232 EDK2's Network Package is susceptible to an infinite loop vulnerability when parsing unknown options in the Destination Options header of IPv6. This vulnerability can be exploited by an attacker to gain unauthorized access and potentially lead to a loss of Availability. View CVE Details Affected Products ABB B&R PCs Vendor: ABB Product Version: ABB APC4100 <1.09, ABB APC910 <=1.25, ABB C80 <1.14, ABB MPC3100 <1.24, ABB PPC1200 <1.14, ABB PPC900 <2.16, ABB APC2200 <1.35, ABB PPC2200 <1.35, ABB APC3100 <1.45, ABB PPC3100 <1.45 Product Status: fixed, known_affected Remediations Vendor fix The problems are corrected in the following product versions: - APC4100 1.09 - APC910 No patch will be released (Please refer to the mitigation measures specified in this advisory). - C80 1.14 - MPC3100 1.24 - PPC1200 1.14 - PPC900 2.16 - APC2200 1.35 - PPC2200 1.35 - APC3100 1.45 - PPC3100 1.45 B&R recommends that customers apply the update at earliest convenience. The process to install updates is described in the user manual. The step to identify the installed product version is described in the user manual. Mitigation Deactivate the vulnerable component - The vulnerabilities exist in the Preboot eXecution Environment (PXE) of the UEFI firmware. If this functionality is not needed, it is recommended to disable it in the UEFI settings, thus making the vulnerabilities not exploitable. Limit accessibility - If PXE functionality is required, users should tightly restrict network traffic to legitimate users and block illegitimate PXE traffic, specifically related to IPv6. For instance, by blocking IPv6 network traffic on the control network firewall. https://help.br-automation.com/#/en/6/cyber-security/defense-in-depth-for-br-products/reference_architecture.html Refer to section “General security recommendations” for further advise on how to keep your system secure. Relevant CWE: CWE-835 Loop with Unreachable Exit Condition ('Infinite Loop') Metrics CVSS Version Base Score Base Severity Vector String 3.1 7.5 HIGH CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H/E:P/RL:O/RC:C CVE-2023-45233 EDK2's Network Package is susceptible to an infinite loop vulnerability when parsing a PadN option in the Destination Options header of IPv6. This vulnerability can be exploited by an attacker to gain unauthorized access and potentially lead to a loss of Availability. View CVE Details Affected Products ABB B&R PCs Vendor: ABB Product Version: ABB APC4100 <1.09, ABB APC910 <=1.25, ABB C80 <1.14, ABB MPC3100 <1.24, ABB PPC1200 <1.14, ABB PPC900 <2.16, ABB APC2200 <1.35, ABB PPC2200 <1.35, ABB APC3100 <1.45, ABB PPC3100 <1.45 Product Status: fixed, known_affected Remediations Vendor fix The problems are corrected in the following product versions: - APC4100 1.09 - APC910 No patch will be released (Please refer to the mitigation measures specified in this advisory). - C80 1.14 - MPC3100 1.24 - PPC1200 1.14 - PPC900 2.16 - APC2200 1.35 - PPC2200 1.35 - APC3100 1.45 - PPC3100 1.45 B&R recommends that customers apply the update at earliest convenience. The process to install updates is described in the user manual. The step to identify the installed product version is described in the user manual. Mitigation Deactivate the vulnerable component - The vulnerabilities exist in the Preboot eXecution Environment (PXE) of the UEFI firmware. If this functionality is not needed, it is recommended to disable it in the UEFI settings, thus making the vulnerabilities not exploitable. Limit accessibility - If PXE functionality is required, users should tightly restrict network traffic to legitimate users and block illegitimate PXE traffic, specifically related to IPv6. For instance, by blocking IPv6 network traffic on the control network firewall. https://help.br-automation.com/#/en/6/cyber-security/defense-in-depth-for-br-products/reference_architecture.html Refer to section “General security recommendations” for further advise on how to keep your system secure. Relevant CWE: CWE-835 Loop with Unreachable Exit Condition ('Infinite Loop') Metrics CVSS Version Base Score Base Severity Vector String 3.1 7.5 HIGH CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H/E:P/RL:O/RC:C CVE-2023-45234 EDK2's Network Package is susceptible to a buffer overflow vulnerability when processing DNS Servers option from a DHCPv6 Advertise message. This vulnerability can be exploited by an attacker to gain unauthorized access and potentially lead to a loss of Confidentiality, Integrity and/or Availability. View CVE Details Affected Products ABB B&R PCs Vendor: ABB Product Version: ABB APC4100 <1.09, ABB APC910 <=1.25, ABB C80 <1.14, ABB MPC3100 <1.24, ABB PPC1200 <1.14, ABB PPC900 <2.16, ABB APC2200 <1.35, ABB PPC2200 <1.35, ABB APC3100 <1.45, ABB PPC3100 <1.45 Product Status: fixed, known_affected Remediations Vendor fix The problems are corrected in the following product versions: - APC4100 1.09 - APC910 No patch will be released (Please refer to the mitigation measures specified in this advisory). - C80 1.14 - MPC3100 1.24 - PPC1200 1.14 - PPC900 2.16 - APC2200 1.35 - PPC2200 1.35 - APC3100 1.45 - PPC3100 1.45 B&R recommends that customers apply the update at earliest convenience. The process to install updates is described in the user manual. The step to identify the installed product version is described in the user manual. Mitigation Deactivate the vulnerable component - The vulnerabilities exist in the Preboot eXecution Environment (PXE) of the UEFI firmware. If this functionality is not needed, it is recommended to disable it in the UEFI settings, thus making the vulnerabilities not exploitable. Limit accessibility - If PXE functionality is required, users should tightly restrict network traffic to legitimate users and block illegitimate PXE traffic, specifically related to IPv6. For instance, by blocking IPv6 network traffic on the control network firewall. https://help.br-automation.com/#/en/6/cyber-security/defense-in-depth-for-br-products/reference_architecture.html Refer to section “General security recommendations” for further advise on how to keep your system secure. Relevant CWE: CWE-119 Improper Restriction of Operations within the Bounds of a Memory Buffer Metrics CVSS Version Base Score Base Severity Vector String 3.1 8.3 HIGH CVSS:3.1/AV:A/AC:L/PR:N/UI:N/S:U/C:H/I:L/A:H/E:P/RL:O/RC:C CVE-2023-45235 EDK2's Network Package is susceptible to a buffer overflow vulnerability when handling Server ID option from a DHCPv6 proxy Advertise message. This vulnerability can be exploited by an attacker to gain unauthorized access and potentially lead to a loss of Confidentiality, Integrity and/or Availability. View CVE Details Affected Products ABB B&R PCs Vendor: ABB Product Version: ABB APC4100 <1.09, ABB APC910 <=1.25, ABB C80 <1.14, ABB MPC3100 <1.24, ABB PPC1200 <1.14, ABB PPC900 <2.16, ABB APC2200 <1.35, ABB PPC2200 <1.35, ABB APC3100 <1.45, ABB PPC3100 <1.45 Product Status: fixed, known_affected Remediations Vendor fix The problems are corrected in the following product versions: - APC4100 1.09 - APC910 No patch will be released (Please refer to the mitigation measures specified in this advisory). - C80 1.14 - MPC3100 1.24 - PPC1200 1.14 - PPC900 2.16 - APC2200 1.35 - PPC2200 1.35 - APC3100 1.45 - PPC3100 1.45 B&R recommends that customers apply the update at earliest convenience. The process to install updates is described in the user manual. The step to identify the installed product version is described in the user manual. Mitigation Deactivate the vulnerable component - The vulnerabilities exist in the Preboot eXecution Environment (PXE) of the UEFI firmware. If this functionality is not needed, it is recommended to disable it in the UEFI settings, thus making the vulnerabilities not exploitable. Limit accessibility - If PXE functionality is required, users should tightly restrict network traffic to legitimate users and block illegitimate PXE traffic, specifically related to IPv6. For instance, by blocking IPv6 network traffic on the control network firewall. https://help.br-automation.com/#/en/6/cyber-security/defense-in-depth-for-br-products/reference_architecture.html Refer to section “General security recommendations” for further advise on how to keep your system secure. Relevant CWE: CWE-119 Improper Restriction of Operations within the Bounds of a Memory Buffer Metrics CVSS Version Base Score Base Severity Vector String 3.1 8.3 HIGH CVSS:3.1/AV:A/AC:L/PR:N/UI:N/S:U/C:H/I:L/A:H/E:P/RL:O/RC:C CVE-2023-45236 EDK2's Network Package is susceptible to a predictable TCP Initial Sequence Number. This vulnerability can be exploited by an attacker to gain unauthorized access and potentially lead to a loss of Confidentiality. View CVE Details Affected Products ABB B&R PCs Vendor: ABB Product Version: ABB APC4100 <1.09, ABB APC910 <=1.25, ABB C80 <1.14, ABB MPC3100 <1.24, ABB PPC1200 <1.14, ABB PPC900 <2.16, ABB APC2200 <1.35, ABB PPC2200 <1.35, ABB APC3100 <1.45, ABB PPC3100 <1.45 Product Status: fixed, known_affected Remediations Vendor fix The problems are corrected in the following product versions: - APC4100 1.09 - APC910 No patch will be released (Please refer to the mitigation measures specified in this advisory). - C80 1.14 - MPC3100 1.24 - PPC1200 1.14 - PPC900 2.16 - APC2200 1.35 - PPC2200 1.35 - APC3100 1.45 - PPC3100 1.45 B&R recommends that customers apply the update at earliest convenience. The process to install updates is described in the user manual. The step to identify the installed product version is described in the user manual. Mitigation Deactivate the vulnerable component - The vulnerabilities exist in the Preboot eXecution Environment (PXE) of the UEFI firmware. If this functionality is not needed, it is recommended to disable it in the UEFI settings, thus making the vulnerabilities not exploitable. Limit accessibility - If PXE functionality is required, users should tightly restrict network traffic to legitimate users and block illegitimate PXE traffic, specifically related to IPv6. For instance, by blocking IPv6 network traffic on the control network firewall. https://help.br-automation.com/#/en/6/cyber-security/defense-in-depth-for-br-products/reference_architecture.html Refer to section “General security recommendations” for further advise on how to keep your system secure. Relevant CWE: CWE-338 Use of Cryptographically Weak Pseudo-Random Number Generator (PRNG) Metrics CVSS Version Base Score Base Severity Vector String 3.1 5.8 MEDIUM CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:C/C:L/I:N/A:N/E:P/RL:O/RC:C CVE-2023-45237 EDK2's Network Package is susceptible to a predictable TCP Initial Sequence Number. This vulnerability can be exploited by an attacker to gain unauthorized access and potentially lead to a loss of Confidentiality. View CVE Details Affected Products ABB B&R PCs Vendor: ABB Product Version: ABB APC4100 <1.09, ABB APC910 <=1.25, ABB C80 <1.14, ABB MPC3100 <1.24, ABB PPC1200 <1.14, ABB PPC900 <2.16, ABB APC2200 <1.35, ABB PPC2200 <1.35, ABB APC3100 <1.45, ABB PPC3100 <1.45 Product Status: fixed, known_affected Remediations Vendor fix The problems are corrected in the following product versions: - APC4100 1.09 - APC910 No patch will be released (Please refer to the mitigation measures specified in this advisory). - C80 1.14 - MPC3100 1.24 - PPC1200 1.14 - PPC900 2.16 - APC2200 1.35 - PPC2200 1.35 - APC3100 1.45 - PPC3100 1.45 B&R recommends that customers apply the update at earliest convenience. The process to install updates is described in the user manual. The step to identify the installed product version is described in the user manual. Mitigation Deactivate the vulnerable component - The vulnerabilities exist in the Preboot eXecution Environment (PXE) of the UEFI firmware. If this functionality is not needed, it is recommended to disable it in the UEFI settings, thus making the vulnerabilities not exploitable. Limit accessibility - If PXE functionality is required, users should tightly restrict network traffic to legitimate users and block illegitimate PXE traffic, specifically related to IPv6. For instance, by blocking IPv6 network traffic on the control network firewall. https://help.br-automation.com/#/en/6/cyber-security/defense-in-depth-for-br-products/reference_architecture.html Refer to section “General security recommendations” for further advise on how to keep your system secure. Relevant CWE: CWE-338 Use of Cryptographically Weak Pseudo-Random Number Generator (PRNG) Metrics CVSS Version Base Score Base Severity Vector String 3.1 5.3 MEDIUM CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:N/E:P/RL:O/RC:C Acknowledgments ABB PSIRT reported these vulnerabilities to CISA. Notice The information in this document is subject to change without notice, and should not be construed as a commitment by B&R. B&R provides no warranty, express or implied, including warranties of merchantability and fitness for a particular purpose, for the information contained in this document, and assumes no responsibility for any errors that may appear in this document. In no event shall B&R or any of its suppliers be liable for direct, indirect, special, incidental or consequential damages of any nature or kind arising from the use of this document, or from the use of any hardware or software described in this document, even if B&R or its suppliers have been advised of the possibility of such damages. This document and parts hereof must not be reproduced or copied without written permission from B&R, and the contents hereof must not be imparted to a third party nor used for any unauthorized purpose. All rights to registrations and trademarks reside with their respective owners. Frequently Asked Questions What is the scope of the vulnerabilities? - A network attacker who successfully exploited these vulnerabilities to execute remote code, initiate DoS attacks, conduct DNS cache poisoning, or extract sensitive information. In worst case, these vulnerabilities can be exploited by an attacker to gain unauthorized access and potentially lead to a loss of Confidentiality, Integrity and/or Availability. What causes the vulnerabilities? - The vulnerabilities are caused by usage of vulnerable UEFI firmware in some B&R xPCs. What is a B&R xPC? - A B&R xPC is an industrial PC (IPC) designed for use in industrial environments and is built to handle more demanding conditions than a standard PC. They often feature robust construction, resistance to dust and moisture, extended temperature ranges, and other specifications suited for industrial applications. What might an attacker use the vulnerabilities to do? - A network attacker who successfully exploited the vulnerabilities could execute remote code, initiate DoS attacks, conduct DNS cache poisoning, or extract sensitive information. How could an attacker exploit the vulnerabilities? - An attacker could try to exploit the vulnerabilities by creating a specially crafted message and sending the message to an affected system node. This would require that the attacker has access to the system network, by connecting to the network either directly or through a wrongly configured or penetrated firewall, or that he installs malicious software on a system node or otherwise infects the network with malicious software. Recommended practices help mitigate such attacks, see section Mitigating Factors above. Could the vulnerabilities be exploited remotely? - Yes, an attacker who has network access to an affected system node could exploit this vulnerability. Recommended practices include that process control systems are physically protected, have no direct connections to the Internet, and are separated from other networks by means of a firewall system that has a minimal number of ports exposed. What does the update do? - The update removes the vulnerabilities in the TCP/IP stack used by the UEFI firmware. When this security advisory was issued, had these vulnerabilities been publicly disclosed? - Yes, these vulnerabilities have been publicly disclosed. When this security advisory was issued, had B&R received any reports that this vulnerability was being exploited on B&R products? - No, B&R had not received any information indicating that this vulnerability had been exploited on B&R products when this security advisory was originally issued. Legal Notice and Terms of Use This product is provided subject to this Notification (https://www.cisa.gov/notification) and this Privacy & Use policy (https://www.cisa.gov/privacy-policy). Recommended Practices CISA recommends users take defensive measures to minimize the exploitation risk of this vulnerability. Minimize network exposure for all control system devices and/or systems, and ensure they are not accessible from the internet. Locate control system networks and remote devices behind firewalls and isolate them from business networks. When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most recent version available. Also recognize VPN is only as secure as its connected devices. CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures. CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies. CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets. Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies. Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents. Advisory Conversion Disclaimer This ICSA is a verbatim republication of ABB PSIRT SA24P003 from a direct conversion of the vendor's Common Security Advisory Framework (CSAF) advisory. This is republished to CISA's website as a means of increasing visibility and is provided "as-is" for informational purposes only. CISA is not responsible for the editorial or technical accuracy of republished advisories and provides no warranties of any kind regarding any information contained within this advisory. Further, CISA does not endorse any commercial product or service. Please contact ABB PSIRT directly for any questions regarding this advisory. Revision History Initial Release Date: 2026-01-29 Date Revision Summary 2026-01-29 1 Initial version. 2026-05-21 2 Initial CISA Republication of ABB PSIRT SA24P003 advisory Legal Notice and Terms of Use
· CISA Cybersecurity Advisory

ABB Terra AC Wallbox

View CSAF Summary ABB is aware of vulnerabilities in the product versions listed as affected in the advisory. An attacker who successfully exploited this vulnerability could cause the pollution of heap memory which potentially takes remote control of the product and performs a write operation to the flash memory to alter the firmware behavior. The following versions of ABB Terra AC Wallbox are affected: Terra AC…
Read full source summary
View CSAF Summary ABB is aware of vulnerabilities in the product versions listed as affected in the advisory. An attacker who successfully exploited this vulnerability could cause the pollution of heap memory which potentially takes remote control of the product and performs a write operation to the flash memory to alter the firmware behavior. The following versions of ABB Terra AC Wallbox are affected: Terra AC wallbox (JP) <=1.8.33, 1.8.36 (CVE-2025-10504, CVE-2025-12142, CVE-2025-12143) CVSS Vendor Equipment Vulnerabilities v3 6.1 ABB ABB Terra AC Wallbox Heap-based Buffer Overflow, Buffer Copy without Checking Size of Input ('Classic Buffer Overflow'), Stack-based Buffer Overflow Background Critical Infrastructure Sectors: Energy Countries/Areas Deployed: Worldwide Company Headquarters Location: Switzerland Vulnerabilities Expand All + CVE-2025-10504 There is potential risk to pollute the memory when developing apps which has used to communicate with charger according to self-defined protocol if developers don’t strictly follow the field length which has not been validated in firmware. View CVE Details Affected Products ABB Terra AC Wallbox Vendor: ABB Product Version: ABB Terra AC wallbox (JP) <=1.8.33 Product Status: fixed, known_affected Remediations Vendor fix The problem is corrected in the following product version; apply the following update depending on product variant: Terra AC wallbox (JP) 1.8.36 ABB recommends that customers apply the update at earliest convenience. Mitigation To attack with this kind of message, hackers must hijack Bluetooth first and then can send messages. Because the communication messages between BLE and charger have been encrypted. In theory, there is no way to attack the charger. Relevant CWE: CWE-122 Heap-based Buffer Overflow Metrics CVSS Version Base Score Base Severity Vector String 3.1 6.1 MEDIUM CVSS:3.1/AV:A/AC:L/PR:H/UI:N/S:U/C:N/I:H/A:H/E:P/RL:O/RC:C CVE-2025-12142 There is potential risk of polluting the BSS memory when developing apps which are used to communicate with charger via Bluetooth according to self-defined protocol if developers configure an unexpected length of bin files. View CVE Details Affected Products ABB Terra AC Wallbox Vendor: ABB Product Version: ABB Terra AC wallbox (JP) <=1.8.33 Product Status: fixed, known_affected Remediations Vendor fix The problem is corrected in the following product version; apply the following update depending on product variant: Terra AC wallbox (JP) 1.8.36 ABB recommends that customers apply the update at earliest convenience. Mitigation To attack with this kind of message, hackers must hijack Bluetooth first and then can send messages. Because the communication messages between BLE and charger have been encrypted. In theory, there is no way to attack the charger. Relevant CWE: CWE-120 Buffer Copy without Checking Size of Input ('Classic Buffer Overflow') Metrics CVSS Version Base Score Base Severity Vector String 3.1 6.1 MEDIUM CVSS:3.1/AV:A/AC:L/PR:H/UI:N/S:U/C:N/I:H/A:H/E:P/RL:O/RC:C CVE-2025-12143 There is potential risk of polluting the stack memory when developing a customized OCPP key of “Ran-domDelay“ in backend and configuring an unexpected number in the field. View CVE Details Affected Products ABB Terra AC Wallbox Vendor: ABB Product Version: ABB Terra AC wallbox (JP) <=1.8.33 Product Status: fixed, known_affected Remediations Vendor fix The problem is corrected in the following product version; apply the following update depending on product variant: Terra AC wallbox (JP) 1.8.36 ABB recommends that customers apply the update at earliest convenience. Mitigation To attack with this kind of message, hackers must hijack Bluetooth first and then can send messages. Because the communication messages between BLE and charger have been encrypted. In theory, there is no way to attack the charger. Relevant CWE: CWE-121 Stack-based Buffer Overflow Metrics CVSS Version Base Score Base Severity Vector String 3.1 6.1 MEDIUM CVSS:3.1/AV:A/AC:L/PR:H/UI:N/S:U/C:N/I:H/A:H/E:P/RL:O/RC:C Acknowledgments ABB PSIRT reported these vulnerabilities to CISA. Notice The information in this document is subject to change without notice, and should not be construed as a commitment by ABB. ABB provides no warranty, express or implied, including warranties of merchantability and fitness for a particular purpose, for the information contained in this document, and assumes no responsibility for any errors that may appear in this document. In no event shall ABB or any of its suppliers be liable for direct, indirect, special, incidental or consequential damages of any nature or kind arising from the use of this document, or from the use of any hardware or software described in this document, even if ABB or its suppliers have been advised of the possibility of such damages. This document and parts hereof must not be reproduced or copied without written permission from ABB, and the contents hereof must not be imparted to a third party nor used for any unauthorized purpose. All rights to registrations and trademarks reside with their respective owners. Legal Notice and Terms of Use This product is provided subject to this Notification (https://www.cisa.gov/notification) and this Privacy & Use policy (https://www.cisa.gov/privacy-policy). Recommended Practices CISA recommends users take defensive measures to minimize the exploitation risk of this vulnerability. Minimize network exposure for all control system devices and/or systems, and ensure they are not accessible from the internet. Locate control system networks and remote devices behind firewalls and isolate them from business networks. When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most recent version available. Also recognize VPN is only as secure as its connected devices. CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures. CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies. CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets. Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies. Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents. Advisory Conversion Disclaimer This ICSA is a verbatim republication of ABB PSIRT 9AKK108471A8107 from a direct conversion of the vendor's Common Security Advisory Framework (CSAF) advisory. This is republished to CISA's website as a means of increasing visibility and is provided "as-is" for informational purposes only. CISA is not responsible for the editorial or technical accuracy of republished advisories and provides no warranties of any kind regarding any information contained within this advisory. Further, CISA does not endorse any commercial product or service. Please contact ABB PSIRT directly for any questions regarding this advisory. Revision History Initial Release Date: 2025-09-16 Date Revision Summary 2025-09-16 1 Initial version. 2025-09-28 2 DocumentID update 2025-09-28 3 Minor corrections 2025-10-09 4 CVSS update 2025-10-27 5 CVE update 2025-11-28 6 CVE update 2025-11-28 7 Fixed Version update 2026-05-21 8 Initial CISA Republication of ABB PSIRT 9AKK108471A8107 advisory Legal Notice and Terms of Use
· CISA Cybersecurity Advisory

CISA Adds Seven Known Exploited Vulnerabilities to Catalog

CISA has added seven new vulnerabilities to its Known Exploited Vulnerabilities (KEV) Catalog, based on evidence of active exploitation. CVE-2008-4250 Microsoft Windows Buffer Overflow Vulnerability CVE-2009-1537 Microsoft DirectX NULL Byte Overwrite Vulnerability CVE-2009-3459 Adobe Acrobat and Reader Heap-Based Buffer Overflow Vulnerability CVE-2010-0249 Microsoft Internet Explorer Use-After-Free Vulnerability…
Read full source summary
CISA has added seven new vulnerabilities to its Known Exploited Vulnerabilities (KEV) Catalog, based on evidence of active exploitation. CVE-2008-4250 Microsoft Windows Buffer Overflow Vulnerability CVE-2009-1537 Microsoft DirectX NULL Byte Overwrite Vulnerability CVE-2009-3459 Adobe Acrobat and Reader Heap-Based Buffer Overflow Vulnerability CVE-2010-0249 Microsoft Internet Explorer Use-After-Free Vulnerability CVE-2010-0806 Microsoft Internet Explorer Use-After-Free Vulnerability CVE-2026-41091 Microsoft Defender Elevation of Privilege Vulnerability CVE-2026-45498 Microsoft Defender Denial of Service Vulnerability These types of vulnerabilities are frequent attack vectors for malicious cyber actors and pose significant risks to the federal enterprise. Binding Operational Directive (BOD) 22-01: Reducing the Significant Risk of Known Exploited Vulnerabilities established the KEV Catalog as a living list of known Common Vulnerabilities and Exposures (CVEs) that carry significant risk to the federal enterprise. BOD 22-01 requires Federal Civilian Executive Branch (FCEB) agencies to remediate identified vulnerabilities by the due date to protect FCEB networks against active threats. See the BOD 22-01 Fact Sheet for more information. Although BOD 22-01 only applies to FCEB agencies, CISA strongly urges all organizations to reduce their exposure to cyberattacks by prioritizing timely remediation of KEV Catalog vulnerabilities as part of their vulnerability management practice. CISA will continue to add vulnerabilities to the catalog that meet the specified criteria.
· CISA Cybersecurity Advisory

Siemens RUGGEDCOM APE1808 Devices

View CSAF Summary A buffer overflow vulnerability in the User-ID™ Authentication Portal (aka Captive Portal) service of Palo Alto Networks PAN-OS software allows an unauthenticated attacker to execute arbitrary code with root privileges on the PA-Series and VM-Series firewalls by sending specially crafted packets. Siemens is preparing fix versions and recommends countermeasures for products where fixes are not, or…
Read full source summary
View CSAF Summary A buffer overflow vulnerability in the User-ID™ Authentication Portal (aka Captive Portal) service of Palo Alto Networks PAN-OS software allows an unauthenticated attacker to execute arbitrary code with root privileges on the PA-Series and VM-Series firewalls by sending specially crafted packets. Siemens is preparing fix versions and recommends countermeasures for products where fixes are not, or not yet available. Customers are advised to consult and implement the workarounds provided in Palo Alto Networks' upstream security notifications. [1] https://security.paloaltonetworks.com/ The following versions of Siemens RUGGEDCOM APE1808 Devices are affected: RUGGEDCOM APE1808 vers:all/* (CVE-2026-0300) CVSS Vendor Equipment Vulnerabilities v3 10 Siemens Siemens RUGGEDCOM APE1808 Devices Out-of-bounds Write Background Critical Infrastructure Sectors: Critical Manufacturing Countries/Areas Deployed: Worldwide Company Headquarters Location: Germany Vulnerabilities Expand All + CVE-2026-0300 A buffer overflow vulnerability in the User-ID™ Authentication Portal (aka Captive Portal) service of Palo Alto Networks PAN-OS software allows an unauthenticated attacker to execute arbitrary code with root privileges on the PA-Series and VM-Series firewalls by sending specially crafted packets. View CVE Details Affected Products Siemens RUGGEDCOM APE1808 Devices Vendor: Siemens Product Version: RUGGEDCOM APE1808 Product Status: known_affected Remediations Mitigation Disable Response Pages in the Interface Management Profile attached to every L3 interface in any zone where untrusted/internet traffic can ingress. Keep Response Pages enabled only on interfaces in trust/internal zones where legitimate users' browsers ingress Mitigation Disable User-ID™ Authentication Portal if not required Mitigation Restrict access to the User-ID Authentication Portal to trusted internal IP addresses only Vendor fix Contact customer support to receive patch and update information Relevant CWE: CWE-787 Out-of-bounds Write Metrics CVSS Version Base Score Base Severity Vector String 3.1 10 CRITICAL CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:H Acknowledgments Siemens ProductCERT reported this vulnerability to CISA. General Recommendations As a general security measure, Siemens strongly recommends to protect network access to devices with appropriate mechanisms. In order to operate the devices in a protected IT environment, Siemens recommends to configure the environment according to Siemens' operational guidelines for Industrial Security (Download: https://www.siemens.com/cert/operational-guidelines-industrial-security), and to follow the recommendations in the product manuals. Additional information on Industrial Security by Siemens can be found at: https://www.siemens.com/industrialsecurity Additional Resources For further inquiries on security vulnerabilities in Siemens products and solutions, please contact the Siemens ProductCERT: https://www.siemens.com/cert/advisories Terms of Use The use of Siemens Security Advisories is subject to the terms and conditions listed on: https://www.siemens.com/productcert/terms-of-use. Legal Notice and Terms of Use This product is provided subject to this Notification (https://www.cisa.gov/notification) and this Privacy & Use policy (https://www.cisa.gov/privacy-policy). Recommended Practices CISA recommends users take defensive measures to minimize the exploitation risk of these vulnerabilities. Minimize network exposure for all control system devices and/or systems, and ensure they are not accessible from the internet. Locate control system networks and remote devices behind firewalls and isolate them from business networks. When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most recent version available. Also recognize VPN is only as secure as its connected devices. CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures. CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies. CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets. Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies. Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents. Advisory Conversion Disclaimer This ICSA is a verbatim republication of Siemens ProductCERT SSA-967325 from a direct conversion of the vendor's Common Security Advisory Framework (CSAF) advisory. This is republished to CISA's website as a means of increasing visibility and is provided "as-is" for informational purposes only. CISA is not responsible for the editorial or technical accuracy of republished advisories and provides no warranties of any kind regarding any information contained within this advisory. Further, CISA does not endorse any commercial product or service. Please contact Siemens ProductCERT directly for any questions regarding this advisory. Revision History Initial Release Date: 2026-05-12 Date Revision Summary 2026-05-12 1 Publication Date 2026-05-19 2 Initial CISA Republication of Siemens ProductCERT SSA-967325 advisory Legal Notice and Terms of Use
· CISA Cybersecurity Advisory

Kieback & Peter DDC Building Controllers

View CSAF Summary Successful exploitation of this vulnerability could allow an attacker to take control of the victim's browser. The following versions of Kieback & Peter DDC Building Controllers are affected: DDC4002 <=1.12.14 (CVE-2026-4293) DDC4100 <=1.12.14 (CVE-2026-4293) DDC4200 <=1.12.14 (CVE-2026-4293) DDC4200-L <=1.12.14 (CVE-2026-4293) DDC4400 <=1.12.14 (CVE-2026-4293) DDC4002e <=1.23.4 (CVE-2026-4293)…
Read full source summary
View CSAF Summary Successful exploitation of this vulnerability could allow an attacker to take control of the victim's browser. The following versions of Kieback & Peter DDC Building Controllers are affected: DDC4002 <=1.12.14 (CVE-2026-4293) DDC4100 <=1.12.14 (CVE-2026-4293) DDC4200 <=1.12.14 (CVE-2026-4293) DDC4200-L <=1.12.14 (CVE-2026-4293) DDC4400 <=1.12.14 (CVE-2026-4293) DDC4002e <=1.23.4 (CVE-2026-4293) DDC4200e <=1.23.4 (CVE-2026-4293) DDC4400e <=1.23.4 (CVE-2026-4293) DDC4020e <=1.23.4 (CVE-2026-4293) DDC4040e <=1.23.4 (CVE-2026-4293) DDC520 <=1.24.1 (CVE-2026-4293) CVSS Vendor Equipment Vulnerabilities v3 5.3 Kieback & Peter Kieback & Peter DDC Building Controllers Improper Neutralization of Input During Web Page Generation ('Cross-site Scripting') Background Critical Infrastructure Sectors: Commercial Facilities, Communications, Financial Services, Food and Agriculture, Government Services and Facilities, Healthcare and Public Health, Information Technology Countries/Areas Deployed: Austria, China, France, Germany, United Arab Emirates Company Headquarters Location: Germany Vulnerabilities Expand All + CVE-2026-4293 The affected products are vulnerable to cross-site scripting (XSS), enabling JavaScript to be executed by the victim's browser, which allows the attacker to control the browser. View CVE Details Affected Products Kieback & Peter DDC Building Controllers Vendor: Kieback & Peter Product Version: Kieback & Peter DDC4002: <=1.12.14, Kieback & Peter DDC4100: <=1.12.14, Kieback & Peter DDC4200: <=1.12.14, Kieback & Peter DDC4200-L: <=1.12.14, Kieback & Peter DDC4400: <=1.12.14, Kieback & Peter DDC4002e: <=1.23.4, Kieback & Peter DDC4200e: <=1.23.4, Kieback & Peter DDC4400e: <=1.23.4, Kieback & Peter DDC4020e: <=1.23.4, Kieback & Peter DDC4040e: <=1.23.4, Kieback & Peter DDC520: <=1.24.1 Product Status: known_affected Remediations Mitigation Kieback & Peter DDC Building Controllers are developed and designed for use in closed building automation networks. The system is protected by a multi-level perimeter against attacks, especially from outside, by dividing it into operational technology (OT) zones with firewalls. Building automation systems (BA systems) in general should not be directly accessible from untrusted networks, especially from the Internet, but should be protected by consistently applying the defense-in-depth strategy. This concept is supported by organizational measures in the building as part of a safety management system. In order to achieve safety, measures are required at all levels. Vendor fix The DDC4002, DDC4100, DDC4200, DDC4200-L and DDC4400 controllers are end-of-maintenance, therefore the recommendations for these devices are as follows: These devices must be operated in a strictly separate OT environment. Vendor fix The DDC4002, DDC4100, DDC4200, DDC4200-L and DDC4400 controllers are end-of-maintenance, therefore the recommendations for these devices are as follows: Only trusted individuals should be granted network access to the DDC web portal. Vendor fix The DDC4002, DDC4100, DDC4200, DDC4200-L and DDC4400 controllers are end-of-maintenance, therefore the recommendations for these devices are as follows: Access to the web portal should be disabled in the device configuration if not required. Vendor fix The DDC4002, DDC4100, DDC4200, DDC4200-L and DDC4400 controllers are end-of-maintenance, therefore the recommendations for these devices are as follows: Users should be informed that only links from trusted sources should be used to access the web service. Vendor fix For the DDC520, DDC4002e, DDC4200e, DDC4400e, DDC4020e, and DDC4040e controllers, Kieback & Peter recommends the following safety measure: Restrict network access to the device Vendor fix For the DDC520, DDC4002e, DDC4200e, DDC4400e, DDC4020e, and DDC4040e controllers, Kieback & Peter recommends the following safety measure: Do not directly connect the device to the Internet Vendor fix Update the firmware to the latest available version: DDC4002e -> Update to version 1.23.5 or newer Vendor fix Update the firmware to the latest available version: DDC4200e -> Update to version 1.23.5 or newer Vendor fix Update the firmware to the latest available version: DDC4400e -> Update to version 1.23.5 or newer Vendor fix Update the firmware to the latest available version: DDC4020e -> Update to version 1.23.5 or newer Vendor fix Update the firmware to the latest available version: DDC4040e -> Update to version 1.23.5 or newer Vendor fix Update the firmware to the latest available version: DDC520 -> Update to version 1.24.2 or newer Relevant CWE: CWE-79 Improper Neutralization of Input During Web Page Generation ('Cross-site Scripting') Metrics CVSS Version Base Score Base Severity Vector String 3.1 5.3 MEDIUM CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:L/A:N Acknowledgments Maximilian Hildebrand of G DATA Advanced Analytics reported this vulnerability to CISA Legal Notice and Terms of Use This product is provided subject to this Notification (https://www.cisa.gov/notification) and this Privacy & Use policy (https://www.cisa.gov/privacy-policy). Recommended Practices CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability. Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet. Locate control system networks and remote devices behind firewalls and isolating them from business networks. When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as the connected devices. CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures. CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies. CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets. Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies. Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents. CISA also recommends users take the following measures to protect themselves from social engineering attacks: Do not click web links or open attachments in unsolicited email messages. Refer to Recognizing and Avoiding Email Scams for more information on avoiding email scams. Refer to Avoiding Social Engineering and Phishing Attacks for more information on social engineering attacks. No known public exploitation specifically targeting this vulnerability has been reported to CISA at this time. Revision History Initial Release Date: 2026-05-19 Date Revision Summary 2026-05-19 1 Initial Publication Legal Notice and Terms of Use
· CISA Cybersecurity Advisory

ZKTeco CCTV Cameras

View CSAF Summary Successful exploitation of this vulnerability could result in information disclosure, including capture of camera account credentials. The following versions of ZKTeco CCTV Cameras are affected: SSC335-GC2063-Face-0b77 Solution CVSS Vendor Equipment Vulnerabilities v3 9.1 ZKTeco ZKTeco CCTV Cameras Authentication Bypass Using an Alternate Path or Channel Background Critical Infrastructure Sectors:…
Read full source summary
View CSAF Summary Successful exploitation of this vulnerability could result in information disclosure, including capture of camera account credentials. The following versions of ZKTeco CCTV Cameras are affected: SSC335-GC2063-Face-0b77 Solution CVSS Vendor Equipment Vulnerabilities v3 9.1 ZKTeco ZKTeco CCTV Cameras Authentication Bypass Using an Alternate Path or Channel Background Critical Infrastructure Sectors: Commercial Facilities Countries/Areas Deployed: Worldwide Company Headquarters Location: China Vulnerabilities Expand All + CVE-2026-8598 An undocumented configuration export port is accessible on some models of ZKTeco CCTV cameras. This port does not require authentication and exposes critical information about the camera such as open services and camera account credentials. View CVE Details Affected Products ZKTeco CCTV Cameras Vendor: ZKTeco Product Version: ZKTeco SSC335-GC2063-Face-0b77 Solution: <V5.0.1.2.20260421 Product Status: known_affected Remediations Mitigation ZKTeco has patched this vulnerability in firmware version V5.0.1.2.20260421. ZKTeco recommends that users upgrade to firmware version V5.0.1.2.20260421 or later at their earliest opportunity. Mitigation Please see the security advisory from ZKTeco here: https://www.zkteco.com/en/announcement/23 for further information. https://www.zkteco.com/en/announcement/23 Relevant CWE: CWE-288 Authentication Bypass Using an Alternate Path or Channel Metrics CVSS Version Base Score Base Severity Vector String 3.1 9.1 CRITICAL CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:N Acknowledgments Souvik Kandar reported this vulnerability to CISA Legal Notice and Terms of Use This product is provided subject to this Notification (https://www.cisa.gov/notification) and this Privacy & Use policy (https://www.cisa.gov/privacy-policy). Recommended Practices CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability. Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the Internet. Locate control system networks and remote devices behind firewalls and isolating them from business networks. When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as the connected devices. CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures. CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies. CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets. Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies. Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents. No known public exploitation specifically targeting this vulnerability has been reported to CISA at this time. Revision History Initial Release Date: 2026-05-19 Date Revision Summary 2026-05-19 1 Initial Publication Legal Notice and Terms of Use
· CISA Cybersecurity Advisory

ScadaBR

View CSAF Summary Successful exploitation of these vulnerabilities could allow an attacker to perform unauthenticated remote code execution. The following versions of ScadaBR are affected: ScadaBR 1.2.0 (CVE-2026-8602, CVE-2026-8603, CVE-2026-8604, CVE-2026-8605) CVSS Vendor Equipment Vulnerabilities v3 9.1 ScadaBR ScadaBR Missing Authentication for Critical Function, Improper Neutralization of Special Elements used…
Read full source summary
View CSAF Summary Successful exploitation of these vulnerabilities could allow an attacker to perform unauthenticated remote code execution. The following versions of ScadaBR are affected: ScadaBR 1.2.0 (CVE-2026-8602, CVE-2026-8603, CVE-2026-8604, CVE-2026-8605) CVSS Vendor Equipment Vulnerabilities v3 9.1 ScadaBR ScadaBR Missing Authentication for Critical Function, Improper Neutralization of Special Elements used in an OS Command ('OS Command Injection'), Cross-Site Request Forgery (CSRF), Use of Hard-coded Credentials Background Critical Infrastructure Sectors: Critical Manufacturing, Dams, Chemical, Energy, Water and Wastewater Countries/Areas Deployed: Worldwide Company Headquarters Location: Brazil Vulnerabilities Expand All + CVE-2026-8602 In ScadaBR version 1.2.0, a Missing Authentication for Critical Function vulnerability could allow an unauthenticated attacker to send a HTTP GET requests to the SCADA system and inject arbitrary sensor readings. View CVE Details Affected Products ScadaBR Vendor: ScadaBR Product Version: ScadaBR ScadaBR: 1.2.0 Product Status: known_affected Remediations Vendor fix ScadaBR has not responded to requests to work with CISA to mitigate this vulnerability. Users of affected versions of ScadaBR are invited to contact ScadaBR customer support for additional information https://github.com/ScadaBR. https://github.com/ScadaBR Relevant CWE: CWE-306 Missing Authentication for Critical Function Metrics CVSS Version Base Score Base Severity Vector String 3.1 9.1 CRITICAL CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:H CVE-2026-8603 In ScadaBR version 1.2.0, an OS Command Injection vulnerability could allow an attacker to execute commands as root on the SCADA system. View CVE Details Affected Products ScadaBR Vendor: ScadaBR Product Version: ScadaBR ScadaBR: 1.2.0 Product Status: known_affected Remediations Vendor fix ScadaBR has not responded to requests to work with CISA to mitigate this vulnerability. Users of affected versions of ScadaBR are invited to contact ScadaBR customer support for additional information https://github.com/ScadaBR. https://github.com/ScadaBR Relevant CWE: CWE-78 Improper Neutralization of Special Elements used in an OS Command ('OS Command Injection') Metrics CVSS Version Base Score Base Severity Vector String 3.1 8.8 HIGH CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H CVE-2026-8604 In ScadaBR version 1.2.0, a CSRF vulnerability could allow an attacker to trigger any authenticated action through a victim's session by luring any logged-in user to a malicious webpage. View CVE Details Affected Products ScadaBR Vendor: ScadaBR Product Version: ScadaBR ScadaBR: 1.2.0 Product Status: known_affected Remediations Vendor fix ScadaBR has not responded to requests to work with CISA to mitigate this vulnerability. Users of affected versions of ScadaBR are invited to contact ScadaBR customer support for additional information https://github.com/ScadaBR. https://github.com/ScadaBR Relevant CWE: CWE-352 Cross-Site Request Forgery (CSRF) Metrics CVSS Version Base Score Base Severity Vector String 3.1 8.8 HIGH CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H CVE-2026-8605 In ScadaBR version 1.2.0, a Use of Hard-Coded Credentials vulnerability could allow an attacker to access the SCADA system as admin. View CVE Details Affected Products ScadaBR Vendor: ScadaBR Product Version: ScadaBR ScadaBR: 1.2.0 Product Status: known_affected Remediations Vendor fix ScadaBR has not responded to requests to work with CISA to mitigate this vulnerability. Users of affected versions of ScadaBR are invited to contact ScadaBR customer support for additional information https://github.com/ScadaBR. https://github.com/ScadaBR Relevant CWE: CWE-798 Use of Hard-coded Credentials Metrics CVSS Version Base Score Base Severity Vector String 3.1 6.1 MEDIUM CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:C/C:L/I:L/A:N Acknowledgments Arad Inbar, Nir Somech, Ben Grinberg, Daniel Lubel, Erez Cohen, and Adiel Sol of DREAM reported these vulnerabilities to CISA Legal Notice and Terms of Use This product is provided subject to this Notification (https://www.cisa.gov/notification) and this Privacy & Use policy (https://www.cisa.gov/privacy-policy). Recommended Practices CISA recommends users take defensive measures to minimize the risk of exploitation of these vulnerabilities. Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet. Locate control system networks and remote devices behind firewalls and isolating them from business networks. When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as the connected devices. CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures. CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies. CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets. Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies. Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents. CISA also recommends users take the following measures to protect themselves from social engineering attacks: Do not click web links or open attachments in unsolicited email messages. Refer to Recognizing and Avoiding Email Scams for more information on avoiding email scams. Refer to Avoiding Social Engineering and Phishing Attacks for more information on social engineering attacks. No known public exploitation specifically targeting these vulnerabilities has been reported to CISA at this time. Revision History Initial Release Date: 2026-05-19 Date Revision Summary 2026-05-19 1 Initial Publication Legal Notice and Terms of Use
Browse saved snapshots