View CSAF Summary Successful exploitation of these vulnerabilities could allow an attacker to disclose information and execute arbitrary code. The following versions of National Instruments LabView are affected: LabVIEW (CVE-2025-64461, CVE-2025-64462, CVE-2025-64463, CVE-2025-64464, CVE-2025-64465, CVE-2025-64466, CVE-2025-64467, CVE-2025-64468, CVE-2025-64469) LabVIEW (CVE-2025-64461, CVE-2025-64462,…
View CSAF Summary Successful exploitation of these vulnerabilities could result in a denial-of-service condition. The following versions of Rockwell Automation Micro820, Micro850, Micro870 are affected: Micro820 (CVE-2025-13823, CVE-2025-13824) CVSS Vendor Equipment Vulnerabilities v3 7.5 Rockwell Automation Rockwell Automation Micro820, Micro850, Micro870 Dependency on Vulnerable Third-Party Component, Release of…
Read more of the source summary
Invalid Pointer or Reference Background Critical Infrastructure Sectors: Critical Manufacturing Countries/Areas Deployed: Worldwide Company Headquarters Location: United States Vulnerabilities Expand All + CVE-2025-13823 A security issue was found in the IPv6 stack in the Micro850 and Micro870 controllers. This issue occurs when the controllers received multiple malformed packets during fuzzing, causing a recoverable fault. View CVE Details Affected Products Rockwell Automation Micro820, Micro850, Micro870 Vendor: Rockwell Automation Product Version: Rockwell Automation Micro820: <=V14.011 Product Status: known_affected Remediations Vendor fix Rockwell Automation recommends users of Micro820 V14.011 and prior update to newer Micro820 controllers (L20E V23.011 or later).…
View CSAF Summary Successful exploitation of these vulnerabilities could result in an attacker executing arbitrary code, executing a man-in-middle style attack, or bypass authentication. The following versions of Axis Communications Camera Station Pro, Camera Station, and Device Manager are affected: AXIS Camera Station Pro (CVE-2025-30023, CVE-2025-30025, CVE-2025-30026) AXIS Camera Station (CVE-2025-30023,…
Read more of the source summary
CVE-2025-30025, CVE-2025-30026) AXIS Device Manager (CVE-2025-30023, CVE-2025-30024, CVE-2025-30025) CVSS Vendor Equipment Vulnerabilities v3 9 Axis Communications Axis Communications Camera Station Pro, Camera Station, and Device Manager Deserialization of Untrusted Data, Improper Certificate Validation, Authentication Bypass Using an Alternate Path or Channel Background Critical Infrastructure Sectors: Commercial Facilities, Critical Manufacturing Countries/Areas Deployed: Worldwide Company Headquarters Location: Sweden Vulnerabilities Expand All + CVE-2025-30023 The communication protocol used between client and server had a flaw that could lead to an authenticated user performing a remote code execution attack. View CVE Details Affected Products Axis Communications Camera…
View CSAF Summary Successful exploitation of this vulnerability could result in denial-of-service (DoS), information tampering, and information disclosure. The following versions of Mitsubishi Electric Iconics Digital Solutions and Mitsubishi Electrics Products are affected: GENESIS64 (CVE-2025-11774) ICONICS Suite (CVE-2025-11774) MobileHMI (CVE-2025-11774) MC Works64 (CVE-2025-11774) CVSS Vendor Equipment…
Read more of the source summary
Vulnerabilities v3 8.2 Mitsubishi Electric Iconics Digital Solutions, Mitsubishi Electric Mitsubishi Electric Iconics Digital Solutions and Mitsubishi Electrics Products Improper Neutralization of Special Elements used in an OS Command ('OS Command Injection') Background Critical Infrastructure Sectors: Critical Manufacturing Countries/Areas Deployed: Worldwide Company Headquarters Location: Japan, United States Vulnerabilities Expand All + CVE-2025-11774 Malicious code execution vulnerability exists in the software keyboard function (hereinafter referred to as "keypad function") of ICONICS Suite, GENESIS64, MobileHMI, and MC Works64, which could lead to denial-of-service (DoS), information tampering, and information disclosure. An attacker may be able to execute arbitrary…
CISA released nine Industrial Control Systems (ICS) Advisories. These advisories provide timely information about current security issues, vulnerabilities, and exploits surrounding ICS. ICSA-25-352-01 Inductive Automation Ignition ICSA-25-352-02 Schneider Electric EcoStruxure Foxboro DCS Advisor ICSA-25-352-03 National Instruments LabView ICSA-25-352-04 Mitsubishi Electric Iconics Digital Solutions and Mitsubishi…
Read more of the source summary
Electrics Products ICSA-25-352-05 Siemens Interniche IP-Stack ICSA-25-352-06 Advantech WebAccess/SCADA ICSA-25-352-07 Rockwell Automation Micro820, Micro850, Micro 870 ICSA-25-352-08 Axis Communications Camera Station Pro, Camera Station, and Device Manager ICSA-24-291-03 Mitsubishi Electric CNC Series (Update C) CISA encourages users and administrators to review newly released ICS Advisories for technical details and mitigations.
CISA has added three new vulnerabilities to its Known Exploited Vulnerabilities (KEV) Catalog, based on evidence of active exploitation. CVE-2025-20393 Cisco Multiple Products Improper Input Validation Vulnerability CVE-2025-40602 SonicWall SMA1000 Missing Authorization Vulnerability CVE-2025-59374 ASUS Live Update Embedded Malicious Code Vulnerability These types of vulnerabilities are frequent attack vectors for…
Read more of the source summary
malicious cyber actors and pose significant risks to the federal enterprise. Binding Operational Directive (BOD) 22-01: Reducing the Significant Risk of Known Exploited Vulnerabilities established the KEV Catalog as a living list of known Common Vulnerabilities and Exposures (CVEs) that carry significant risk to the federal enterprise. BOD 22-01 requires Federal Civilian Executive Branch (FCEB) agencies to remediate identified vulnerabilities by the due date to protect FCEB networks against active threats. See the BOD 22-01 Fact Sheet for more information. Although BOD 22-01 only applies to FCEB agencies, CISA strongly urges all organizations to reduce their exposure to cyberattacks by prioritizing timely remediation of KEV Catalog vulnerabilities as part of their…
CISA has added one new vulnerability to its Known Exploited Vulnerabilities (KEV) Catalog, based on evidence of active exploitation. CVE-2025-59718 Fortinet Multiple Products Improper Verification of Cryptographic Signature Vulnerability This type of vulnerability is a frequent attack vector for malicious cyber actors and poses significant risks to the federal enterprise. Binding Operational Directive (BOD) 22-01:…
Read more of the source summary
Reducing the Significant Risk of Known Exploited Vulnerabilities established the KEV Catalog as a living list of known Common Vulnerabilities and Exposures (CVEs) that carry significant risk to the federal enterprise. BOD 22-01 requires Federal Civilian Executive Branch (FCEB) agencies to remediate identified vulnerabilities by the due date to protect FCEB networks against active threats. See the BOD 22-01 Fact Sheet for more information. Although BOD 22-01 only applies to FCEB agencies, CISA strongly urges all organizations to reduce their exposure to cyberattacks by prioritizing timely remediation of KEV Catalog vulnerabilities as part of their vulnerability management practice. CISA will continue to add vulnerabilities to the catalog that meet the specified criteria.
View CSAF Summary Successful exploitation of these vulnerabilities could allow an attacker to read or write encrypted traffic or perform a replay attack. The following versions of Johnson Controls PowerG, IQPanel and IQHub are affected: PowerG (CVE-2025-61738, CVE-2025-61739, CVE-2025-26379, CVE-2025-61740) IQHub (CVE-2025-61738, CVE-2025-61739, CVE-2025-26379, CVE-2025-61740) IQPanel 2 (CVE-2025-61738,…
Read more of the source summary
CVE-2025-61739, CVE-2025-26379, CVE-2025-61740) IQPanel 2+ (CVE-2025-61738, CVE-2025-61739, CVE-2025-26379, CVE-2025-61740) IQPanel 4 (CVE-2025-61738, CVE-2025-61739, CVE-2025-26379, CVE-2025-61740) CVSS Vendor Equipment Vulnerabilities v3 7.6 Johnson Controls Inc. Johnson Controls PowerG, IQPanel and IQHub Cleartext Transmission of Sensitive Information, Reusing a Nonce, Key Pair in Encryption, Use of Cryptographically Weak Pseudo-Random Number Generator (PRNG), Origin Validation Error Background Critical Infrastructure Sectors: Commercial Facilities Countries/Areas Deployed: Worldwide Company Headquarters Location: Ireland Vulnerabilities Expand All + CVE-2025-61738 The affected product is vulnerable due to cleartext transmission of sensitive information. This may allow an…
View CSAF Summary Successful exploitation of this vulnerability could compromise the integrity of the product data and disrupt its availability. The following versions of Hitachi Energy AFS, AFR and AFF Series are affected: AFS 660-B/C/S (CVE-2024-3596) AFS 665-B/S (CVE-2024-3596) AFS 670 v2.0 (CVE-2024-3596) AFS 650 (CVE-2024-3596) AFS 655 (CVE-2024-3596) AFS 670 (CVE-2024-3596) AFS 675 (CVE-2024-3596) AFS 677…
Read more of the source summary
(CVE-2024-3596) AFR 677 (CVE-2024-3596) AFF 660 (CVE-2024-3596) AFF 665 (CVE-2024-3596) CVSS Vendor Equipment Vulnerabilities v3 9 Hitachi Energy Hitachi Energy AFS, AFR and AFF Series Improper Enforcement of Message Integrity During Transmission in a Communication Channel Background Critical Infrastructure Sectors: Energy Countries/Areas Deployed: Worldwide Company Headquarters Location: Switzerland Vulnerabilities Expand All + CVE-2024-3596 The RADIUS protocol under RFC 2865 is susceptible to forgery attacks by a local attacker who can modify any valid response (access-accept, access-reject, or access-challenge) to any other response using a chosen-prefix collision attack against the MD5 response authenticator signature. View CVE Details Affected Products Hitachi Energy…
View CSAF Summary Successful exploitation of this vulnerability could allow an attacker obtain plaintext credentials from the project file for GT Designer3, which could result in illegally operating GOT2000 and GOT1000 series devices. The following versions of Mitsubishi Electric GT Designer3 are affected: GT Designer3 Version1 (GOT2000) (CVE-2025-11009) GT Designer3 Version1 (GOT1000) (CVE-2025-11009) CVSS Vendor…
Read more of the source summary
Equipment Vulnerabilities v3 5.1 Mitsubishi Electric Mitsubishi Electric GT Designer3 Cleartext Storage of Sensitive Information Background Critical Infrastructure Sectors: Critical Manufacturing Countries/Areas Deployed: Worldwide Company Headquarters Location: Japan Vulnerabilities Expand All + CVE-2025-11009 Information Disclosure vulnerability due to Cleartext Storage of Sensitive Information(CWE-312) exists in GT Designer3. GT Designer3 stores credentials and verifies them in plain text, therefore an attacker may be able to obtain plaintext credentials from the project file for GT Designer3. As a result, the attacker may be able to operate illegally GOT2000 series or GOT1000 series by using the obtained credentials. View CVE Details Affected Products Mitsubishi…